ASTM E136-2004 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750&176 C《750℃时立式管炉材料特性的标准试验方法》.pdf
《ASTM E136-2004 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750&176 C《750℃时立式管炉材料特性的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E136-2004 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750&176 C《750℃时立式管炉材料特性的标准试验方法》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 136 04An American National StandardStandard Test Method forBehavior of Materials in a Vertical Tube Furnace at 750C1This standard is issued under the fixed designation E 136; the number immediately following the designation indicates the year oforiginal adoption or, in the case of rev
2、ision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This fire-test-re
3、sponse test method covers the determi-nation under specified laboratory conditions of combustioncharacteristics of building materials. It is not intended to applyto laminated or coated materials.1.2 This test method references notes and footnotes thatprovide explanatory information. These notes and
4、footnotes,excluding those in tables and figures, shall not be considered asrequirements of this test method.1.3 The values stated in SI units are to be regarded asstandard. The values given in brackets are for information only.1.4 This standard is used to measure and describe theresponse of material
5、s, products, or assemblies to heat andflame under controlled conditions, but does not by itselfincorporate all factors required for fire-hazard or fire-riskassessment of the materials, products, or assemblies underactual fire conditions.1.5 This standard does not purport to address all of thesafety
6、concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D 1929 Test Method for Ignition Pro
7、perties of PlasticsD 3174 Test Method for Ash in the Analysis Sample of Coaland Coke from CoalE 84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE 176 Terminology of Fire Standards2.2 ISO Standard:ISO 1182 Noncombustibility Test for Building Materials32.3 Other Standard:BS 476
8、Combustibility Test of Materials33. Terminology3.1 DefinitionsFor definitions of terms found in this testmethod, refer to Terminology E 176.4. Significance and Use4.1 While actual building fire exposure conditions are notduplicated, this test method will assist in indicating thosematerials which do
9、not act to aid combustion or add appre-ciable heat to an ambient fire.4.2 Materials passing the test are permitted limited flamingand other indications of combustion.5. Apparatus5.1 The apparatus, as shown in Fig. 1, shall consist prima-rily of the following:5.1.1 Refractory TubesTwo concentric, ref
10、ractory tubes,76 and 102 mm 3 and 4 in. in inside diameter and 210 to 250mm 812 to 10 in. in length, with axes vertical, and with heatapplied by electric heating coils outside of the larger tube. Acontrolled flow of air is admitted tangentially near the top ofthe annular space between the tubes and
11、passes to the bottomof the inner tube. The outer tube rests on a refractory bottomand the inner tube rests on three spacer blocks so as to afforda total opening under the inner tube equal to or greater than thatof the annular space. The refractory bottom plate has aremovable plug for cleaning.5.1.2
12、Transparent CoverA transparent cover of heat-resistant glass or other transparent material shall be providedover the top of the inner tubes. The cover shall have a circularopening 28.7 6 0.8 mm 118 6132 in. centered over the axisof the tubes. This opening has an area of 645 mm21.0 in.2.The cover sha
13、ll be in two equally-sized, movable parts.5.1.3 Thermocouples and an automatically recording deviceshall be provided. The thermocouples shall be located asfollows:1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.2
14、3 on Combustibil-ity.Current edition approved February 1, 2004. Published March 2004. Originallyapproved in 1958. Last previous edition approved in 1999 as E 136 99e1.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual
15、Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, P
16、A 19428-2959, United States.5.1.3.1 Thermocouple T1is located in the center of the airspace between the two concentric, refractory tubes; approxi-mately 204 mm 8 in. down from the top of the 102-mm4-in. diameter tube (Note 1).5.1.3.2 Thermocouple T3is located at the approximategeometric center of th
17、e specimen.5.1.3.3 Thermocouple T4is located on the surface, incontact with the specimen; in the same horizontal plane as T3.5.1.3.4 Thermocouples T1, T3and T4shall have a timeconstant (time to reach 63.2 % of the furnace air temperature of750C 1382F) of 5 to 10 s (Note 2).NOTE 1Thermocouple T1is us
18、ed for better regulation of the tempera-ture of the air in the furnace space.NOTE 2Ungrounded, metallic-sheathed thermocouples of 1-mm di-ameter have been found to meet the time constant requirements.5.2 Specimen HolderThe specimen holder for solid speci-mens shall be as shown in Fig. 2.5.2.1 Specim
19、ens in granular or powder form shall be con-tained in thin-wall, open-top vessels of inert materials whoseoutside dimensions conform to the specimen shape and maxi-mum size specified in 6.1. These vessels shall have walls ofeither solid or mesh construction.5.3 Specimen LocationDuring the test, the
20、geometriccenter of the specimen shall be located at the geometric center63mm618 in. of the 76-mm 3-in. diameter tube.6. Test Specimens6.1 All test specimens shall be 38 by 38 by 51 6 2.5 mm1.5 by 1.5 by 2.0 6 0.1 in. The specimens shall be dried at60 6 3C 140 6 5F for not less than 24 h but no more
21、than48 h. Specimens shall then be placed in a desiccator to cool atleast 1 h before testing.6.2 Not less than four identical specimens shall be tested.7. Procedure7.1 Furnace Preparation:7.1.1 Conduct the test at room conditions of 21 6 3C70 6 5F.7.1.2 Air FlowProvide an external air source to suppl
22、yclean air through a metal tube located near the furnace top,tangentially between the annular spaced ceramic tubes. The airshall be supplied at a steady and controllable rate of 0.0027m3/min 0.10 ft3/min 6 20 %, which will give an air flow of3 m 10 ft/min past a loaded specimen in the furnace at 750
23、CNOTEInch-Pound Equivalentsin.3 4 6101034 1 in.2No. 16 Awgmm 76 102 152 254 273 6.4 cm21.29FIG. 1 Cross Section of Furnace AssemblyE1360421382F. Measure the air at room temperature, as specified in7.1.1 and meter by a rotameter or other metering device in linewith the metal tube.7.1.3 Prepare the fu
24、rnace by bringing the temperature ofthermocouple T2(Note 3), located in the furnace at the positionto be occupied by the geometric center of the specimen, to atemperature of 750 6 5.5C 1382 6 10F. Maintain the tem-perature in the unloaded furnace for at least 15 min to assurestability.NOTE 3The temp
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME1362004STANDARDTESTMETHODFORBEHAVIOROFMATERIALSINAVERTICALTUBEFURNACEAT750176C750 立式 材料 特性 标准 试验

链接地址:http://www.mydoc123.com/p-526951.html