《ASTM D2802-2014 Standard Specification for Ozone-Resistant Ethylene-Alkene Polymer Insulation for Wire and Cable《电线和电缆用耐臭氧乙烯烃聚合物绝缘材料的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM D2802-2014 Standard Specification for Ozone-Resistant Ethylene-Alkene Polymer Insulation for Wire and Cable《电线和电缆用耐臭氧乙烯烃聚合物绝缘材料的标准规格》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D2802 03 (Reapproved 2010)D2802 14Standard Specification forOzone-Resistant Ethylene-Alkene Polymer Insulationfor Wire and Cable1This standard is issued under the fixed designation D2802; the number immediately following the designation indicates the year oforiginal adoption or, in the
2、case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.1. Scope Scope
3、*1.1 This specification covers an ozone-resisting crosslinked rubber insulation compound for electrical wires and cables. Thepolymer shall consist substantially of ethylene-alkene copolymer (EAM) or ethylene-alkene diene terpolymer (EADM). Thispolymer type includes ethylenepropylene copolymer (EPM)
4、and ethylenepropylene diene terpolymer (EPDM).1.2 This type of insulation is considered suitable for use on wire or cable which will be used in wet and dry locations withconductor temperatures up to 90C during continuous operation, to 130C during emergency overload conditions, and to 250Cduring shor
5、t-circuit conditions. It is considered suitable for all sizes and voltage classifications of single- and multiple-conductorpower cables up to 35 000 V 35 000 V phase-to-phase at the 100 % insulation level and up to 25 000 V 25 000 V at the 133 %insulation level as listed in Table 1D, Conductor Sizes
6、, Insulation Thicknesses, Test Voltages, and Corona Extinction Levels forEthylene-Propylene Rubber Insulation, Table 1D of Test Methods D470. Single-conductor cables shall have a supplementarycovering over the insulation, and multiple-conductor cables shall have an overall covering.1.3 Whenever two
7、sets of values are presented, in different units, the values in the first set are the standard, while those inparentheses are for information only.1.4 In many instances the insulation material cannot be tested unless it has been formed around a conductor or cable. Therefore,tests are done on insulat
8、ed wire or cable in this specification solely to determine the relevant property of the insulation and notto test the conductor or completed cable.2. Referenced Documents2.1 ASTM Standards:2D470 Test Methods for Crosslinked Insulations and Jackets for Wire and CableD1711 Terminology Relating to Elec
9、trical Insulation2.2 ICEA Standard:3T-24-380 Guide for Partial Discharge Procedure3. Terminology3.1 Definitions: DefinitionsFor definitions of terms used in this specification, refer to Terminology D1711.3.2 Definitions of Terms Specific to This Standard:3.2.1 aging (act of), nvexposure of materials
10、 to air at a temperature of 121C for 168 h.4. Physical Properties4.1 The crosslinked insulation shall conform to the requirements for physical properties specified in Table 1.1 This specification is under the jurisdiction of ASTM Committee D09 on Electrical and Electronic Insulating Materials and is
11、 the direct responsibility of SubcommitteeD09.18 on Solid Insulations, Non-Metallic Shieldings and Coverings for Electrical and Telecommunication Wires and Cables. Members of ASTM Committees D02 onPetroleum Products and Lubricants, and B07 on Light Metals and Alloys, have contributed to this specifi
12、cation.Current edition approved Oct. 1, 2010Nov. 1, 2014. Published October 2010November 2014. Originally approved in 1970. Last previous edition approved in 20032010as D2802 03.D2802 03 (2010). DOI: 10.1520/D2802-03R10.10.1520/D2802-14.2 For referencedASTM standards, visit theASTM website, www.astm
13、.org, or contactASTM Customer Service at serviceastm.org. ForAnnual Book ofASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.3 Available from the Insulated Cable Engineers Assn., P.O. Box 440, S. Yarmouth, MA 02664.This document is not an ASTM standar
14、d and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases o
15、nly the current versionof the standard as published by ASTM is to be considered the official document.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States14.2 The values spec
16、ified in Table 1 are applicable only to insulation having a nominal wall thickness of 0.030 in. (0.76 mm)(0.76 mm) or greater.5. Electrical Requirements5.1 Order of TestingPerform the ac voltage withstand, insulation resistance, and dc voltage withstand tests in that order whenany of these tests are
17、 required. The sequence for other testing is not specified.5.2 AC Voltage Withstand TestEach insulated conductor in the completed cable shall withstand for 5 min the ac test voltageshown in Table 1D, Conductor Sizes, Insulation Thicknesses, Test Voltages, and Corona Extinction Levels for Ethylene-Pr
18、opyleneRubber Insulation, Table 1D of Test Methods D470, except that for . For nonshielded conductors rated 5000 V or less, use thiswithstand test, or use as an acceptable substitute (see the dc test voltage described in 5.5 may be substituted.).5.3 Insulation Resistance:5.3.1 Each insulated conduct
19、or in the completed cable shall have an insulation resistance value of not less than thatcorresponding to a constant of 20 000 M-1000 ft at 15.6C. When the temperature of the water in which the insulation is testeddiffers from 15.6C, the measured value obtained shall be multiplied by the proper corr
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD28022014STANDARDSPECIFICATIONFOROZONERESISTANTETHYLENEALKENEPOLYMERINSULATIONFORWIREANDCABLE 电线

链接地址:http://www.mydoc123.com/p-513530.html