ASTM C1146-2009(2013) Standard Guide for Prefabricated Panel and H&ndash bar Insulation Systems for Vessels Ducts and Equipment Operating at Temperatures Above Ambient Air《在室温以上温度操.pdf
《ASTM C1146-2009(2013) Standard Guide for Prefabricated Panel and H&ndash bar Insulation Systems for Vessels Ducts and Equipment Operating at Temperatures Above Ambient Air《在室温以上温度操.pdf》由会员分享,可在线阅读,更多相关《ASTM C1146-2009(2013) Standard Guide for Prefabricated Panel and H&ndash bar Insulation Systems for Vessels Ducts and Equipment Operating at Temperatures Above Ambient Air《在室温以上温度操.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1146 09 (Reapproved 2013)Standard Guide forPrefabricated Panel and Hbar Insulation Systems forVessels, Ducts and Equipment Operating at TemperaturesAbove Ambient Air1This standard is issued under the fixed designation C1146; the number immediately following the designation indicates th
2、e year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide describes design, fabrication, shipping
3、,handling, jobsite storage, and installation of prefabricatedpanel and H-Bar insulation systems for vessels, ducts, andequipment operating at temperatures above ambient. Typicalapplications include, but are not limited to, air and gas ducts,steam generating units, air quality control systems, fans,s
4、torage tanks, process vessels, and coke drums1.2 The insulation described herein is limited to systemsconsisting of insulating units specially designed to fit thesurfaces to be insulated, and engineered for the service andenvironmental requirements. The insulation unit may alsoinclude special design
5、 features which facilitate the removal andreplacement for maintenance and inspection.1.3 When prefabricated panels are used, each insulation unitfactory preassembled and typically comprised of the insulation,an outer lagging to which the insulation is attached, an innerretaining wire mesh, optional
6、foil lining, and means formechanically securing multiple units together in an assembly.1.4 H-bar systems represent insulation units that are typi-cally comprised of the insulation, outer lagging and a uniquelyconfigured subgirt design which both supports the insulationand provides a means for mechan
7、ically securing multiple unitstogether in an assembly. The design of the subgirt creates an“H” configuration which is fabricated from light gauge sheetmetal. The subgirt components consist of: (1) a “J-bar” shapewhich frames the perimeter edges of the surface to beinsulated, holds the insulation in
8、place along the outer edge andprovides a screen attachment point for the outer lagging; (2) the“H-bar” shape is placed at defined intervals. The web section ofthe “H-bar” supports the insulation while the exterior flangeallows for the outer lagging to be attached with threadedfasteners.1.5 The value
9、s stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with i
10、ts use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.NOTE 1When prefabricated panel or H-Bar insulation systems arespecified, Test Methods C167, C177 and C1061, Mater
11、ial SpecificationsA36/A36M, A463/A463M, B209, C612, and Terminology C168 shouldbe considered.2. Referenced Documents2.1 ASTM Standards:2A36/A36M Specification for Carbon Structural SteelA463/A463M Specification for Steel Sheet, Aluminum-Coated, by the Hot-Dip ProcessB209 Specification for Aluminum a
12、nd Aluminum-AlloySheet and PlateC167 Test Methods for Thickness and Density of Blanket orBatt Thermal InsulationsC168 Terminology Relating to Thermal InsulationC177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate ApparatusC612
13、 Specification for Mineral Fiber Block and BoardThermal InsulationC1061 Test Method for Thermal Transmission Properties ofNon-Homogeneous Insulation Panels Installed Vertically(Withdrawn 1995)33. Terminology3.1 Terminology C168 shall be considered as applying tothe terms in this specification.1This
14、guide is under the jurisdiction of ASTM Committee C16 on ThermalInsulation and is the direct responsibility of Subcommittee C16.40 on InsulationSystems.Current edition approved Nov. 1, 2013. Published January 2014. Originallyapproved in 1989. Last previous edition approved in 2009 as C1146 09. DOI:1
15、0.1520/C1146-09R13.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3The last approved version of this histori
16、cal standard is referenced onwww.astm.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States13.2 Definitions of Terms Specific to This Standard:3.2.1 convection barrier (flue stop)barriers to internal airflow sometimes refered to as “chi
17、mney effect”) which areplaced between the inner liner and the hot surface beinginsulated. The barriers are generally a combination of sheetmetal and with the insulation material mechanically attached.Convection barriers are required when the insulation is not indirect contact with the plate surface
18、and only on vertical andsloping surfaces of less than 45 incline.3.2.2 flashingsheet metal of the same material as thelagging, used to cover openings in the insulation typicallyoccurring at locations, such as corners, penetrations framing ofdoors and closures. Flashing may be fixed (permanent) orrem
19、ovable to allow for inspection and maintenance, that is,expansion joints.3.2.3 inner linerthe innermost surface or cover of theprefabricated panel (closest to the hot surface) composed ofreflective aluminum foil and wire mesh.3.2.4 insulationessentially homogenous insulation, gener-ally in semi-rigi
20、d board from and, in which relevant propertiesare not a function of position within the material itself, but maybe a function of such variables as time and temperature.3.2.5 laggingthe outermost cover or sheet of the prefab-ricated panel or Hbar system (farthest from the hot surface),which performs
21、a structural function as well as providesprotection from weather and mechanical abuse. The lagging isgenerally fabricated from corrugated, ribbed, or flat sheet;smooth or stucco-embossed; mill finish or painted; clad ornon-clad.3.2.6 penetrationsopenings through a unit of insulationfrom the hot plat
22、e surface through to the exterior cold surface.Penetrations such as test ports should be covered with remov-able insulation assemblies. The insulation thickness should beequal to the surface being insulated.3.2.7 retaining devices3.2.7.1 prefabricated panelsmetallic members passingthrough the insula
23、tion between the hot surface and the coldsurface. Generally, these include: pins, prongs, or other accept-able means used and secured with washers and speed clips tohold the assembly together.3.2.7.2 H-bar systemsH-bar systems includes retainingdevices such as a backing strap or expanded metal betwe
24、en theH-bar. These devices are placed midway between the insula-tion boards and provide support on wall applications. On top ofsurfaces, the H-bar retaining device may be either expandedmetal or a corrugated inner-liner to hold the insulation in theH-bar track3.2.8 support member (subgrit)straps, ba
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC114620092013STANDARDGUIDEFORPREFABRICATEDPANELANDHNDASHBARINSULATIONSYSTEMSFORVESSELSDUCTSANDEQUIPMENTOPERATINGATTEMPERATURESABOVEAMBIENTAIR

链接地址:http://www.mydoc123.com/p-463536.html