《ASTM C1146-2009 Standard Guide for Prefabricated Panel and H&x2013 bar Insulation Systems for Vessels Ducts and Equipment Operating at Temperatures Above Ambient Air《在室温以上温度操作的导管及设.pdf》由会员分享,可在线阅读,更多相关《ASTM C1146-2009 Standard Guide for Prefabricated Panel and H&x2013 bar Insulation Systems for Vessels Ducts and Equipment Operating at Temperatures Above Ambient Air《在室温以上温度操作的导管及设.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 1146 09Standard Guide forPrefabricated Panel and Hbar Insulation Systems forVessels, Ducts and Equipment Operating at TemperaturesAbove Ambient Air1This standard is issued under the fixed designation C 1146; the number immediately following the designation indicates the year oforigina
2、l adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide describes design, fabrication, shipping, han-dling, job
3、site storage, and installation of prefabricated paneland H-Bar insulation systems for vessels, ducts, and equipmentoperating at temperatures above ambient. Typical applicationsinclude, but are not limited to, air and gas ducts, steamgenerating units, air quality control systems, fans, storagetanks,
4、process vessels, and coke drums1.2 The insulation described herein is limited to systemsconsisting of insulating units specially designed to fit thesurfaces to be insulated, and engineered for the service andenvironmental requirements. The insulation unit may alsoinclude special design features whic
5、h facilitate the removal andreplacement for maintenance and inspection.1.3 When prefabricated panels are used, each insulation unitfactory preassembled and typically comprised of the insulation,an outer lagging to which the insulation is attached, an innerretaining wire mesh, optional foil lining, a
6、nd means formechanically securing multiple units together in an assembly.1.4 H-bar systems represent insulation units that are typi-cally comprised of the insulation, outer lagging and a uniquelyconfigured subgirt design which both supports the insulationand provides a means for mechanically securin
7、g multiple unitstogether in an assembly. The design of the subgirt creates an“H” configuration which is fabricated from light gauge sheetmetal. The subgirt components consist of: (1) a “J-bar” shapewhich frames the perimeter edges of the surface to be insu-lated, holds the insulation in place along
8、the outer edge andprovides a screen attachment point for the outer lagging; (2) the“H-bar” shape is placed at defined intervals. The web section ofthe “H-bar” supports the insulation while the exterior flangeallows for the outer lagging to be attached with threadedfasteners.1.5 The values stated in
9、inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It i
10、s theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.NOTE 1When prefabricated panel or H-Bar insulation systems arespecified, Test Methods C 167, C 177 and C 1061, Material Speci
11、ficationsA 36/A 36M, A 463/A 463M, B 209, C 612, and Terminology C 168should be considered.2. Referenced Documents2.1 ASTM Standards:2A 36/A 36M Specification for Carbon Structural SteelA 463/A 463M Specification for Steel Sheet, Aluminum-Coated, by the Hot-Dip ProcessB 209 Specification for Aluminu
12、m and Aluminum-AlloySheet and PlateC 167 Test Methods for Thickness and Density of Blanketor Batt Thermal InsulationsC 168 Terminology Relating to Thermal InsulationC 177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate Apparat
13、usC 612 Specification for Mineral Fiber Block and BoardThermal InsulationC 1061 Test Method for Thermal Transmission Propertiesof Non-Homogeneous Insulation Panels Installed Verti-cally33. Terminology3.1 Terminology C 168 shall be considered as applying tothe terms in this specification.1This guide
14、is under the jurisdiction of ASTM Committee C16 on ThermalInsulation and is the direct responsibility of Subcommittee C16.40 on InsulationSystems.Current edition approved June 1, 2009. Published August 2009. Originallyapproved in 1989. Last previous edition approved in 2003 as C 1146 03.2For referen
15、ced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Withdrawn. The last approved version of this historical standard is refe
16、rencedon www.astm.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2 Definitions of Terms Specific to This Standard:3.2.1 convection barrier (flue stop)barriers to internal airflow sometimes refered to as “chimney effect”) which
17、 areplaced between the inner liner and the hot surface beinginsulated. The barriers are generally a combination of sheetmetal and with the insulation material mechanically attached.Convection barriers are required when the insulation is not indirect contact with the plate surface and only on vertica
18、l andsloping surfaces of less than 45 incline.3.2.2 flashingsheet metal of the same material as thelagging, used to cover openings in the insulation typicallyoccurring at locations, such as corners, penetrations framing ofdoors and closures. Flashing may be fixed (permanent) orremovable to allow for
19、 inspection and maintenance, that is,expansion joints.3.2.3 inner linerthe innermost surface or cover of theprefabricated panel (closest to the hot surface) composed ofreflective aluminum foil and wire mesh.3.2.4 insulationessentially homogenous insulation, gener-ally in semi-rigid board from and, i
20、n which relevant propertiesare not a function of position within the material itself, but maybe a function of such variables as time and temperature.3.2.5 laggingthe outermost cover or sheet of the prefab-ricated panel or Hbar system (farthest from the hot surface),which performs a structural functi
21、on as well as providesprotection from weather and mechanical abuse. The lagging isgenerally fabricated from corrugated, ribbed, or flat sheet;smooth or stucco-embossed; mill finish or painted; clad ornon-clad.3.2.6 penetrationsopenings through a unit of insulationfrom the hot plate surface through t
22、o the exterior cold surface.Penetrations such as test ports should be covered with remov-able insulation assemblies. The insulation thickness should beequal to the surface being insulated.3.2.7 retaining devices3.2.7.1 prefabricated panelsmetallic members passingthrough the insulation between the ho
23、t surface and the coldsurface. Generally, these include: pins, prongs, or other accept-able means used and secured with washers and speed clips tohold the assembly together.3.2.7.2 H-bar systemsH-bar systems includes retainingdevices such as a backing strap or expanded metal between theH-bar. These
24、devices are placed midway between the insula-tion boards and provide support on wall applications. On top ofsurfaces, the H-bar retaining device may be either expandedmetal or a corrugated inner-liner to hold the insulation in theH-bar track3.2.9 support member (subgrit)straps, bars, or anglesattach
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC11462009STANDARDGUIDEFORPREFABRICATEDPANELANDHX2013BARINSULATIONSYSTEMSFORVESSELSDUCTSANDEQUIPMENTOPERATINGATTEMPERATURESABOVEAMBIENTAIR

链接地址:http://www.mydoc123.com/p-463535.html