UL SUBJECT 1856-2013 OUTLINE OF INVESTIGATION FOR UNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMS (Issue 1)《地下燃料箱内部改造系统的调查大纲 (议题1)》.pdf
《UL SUBJECT 1856-2013 OUTLINE OF INVESTIGATION FOR UNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMS (Issue 1)《地下燃料箱内部改造系统的调查大纲 (议题1)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 1856-2013 OUTLINE OF INVESTIGATION FOR UNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMS (Issue 1)《地下燃料箱内部改造系统的调查大纲 (议题1)》.pdf(30页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJune 14, 20131UL 1856OUTLINE OF INVESTIGATIONFORUNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMSIssue Number 1June 14, 2013Summary of TopicsThis is the First Issue of Subject 1856, Outline of Inve
2、stigation forUnderground Fuel Tank Internal Retrofit Systems covers lining, upgradeand structural types of nonmetallic retrofit systems (products) intendedfor field installation inside of steel or fiberglass underground fuel tanks incommercial (public) or private (fleet) automotive fueling stationap
3、plications. These products are also intended for primary containment oftypical liquid fuels as identified in this Outline, and may provide otherfeatures, such as secondary containment and structural improvements, asdescribed for each specific type of retrofit system.This issue becomes effective JUNE
4、 14, 2017.COPYRIGHT 2013 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJUNE 14, 2013UL 18562No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION F
5、ROM ULCONTENTSINTRODUCTION1 Scope .52 General 72.1 Units of measurement .72.2 Undated references .73 Glossary .7CONSTRUCTION4 General 94.7 Lining systems 104.8 Upgrade systems 104.9 Structural systems .114.10 Interstitial spaces .114.11 Manways and fittings .114.12 Tank compartments 11PERFORMANCE5 G
6、eneral .125.1 Test tank preparation 125.2 System installation .125.3 System material tests 145.4 System leakage tests 146 Tank Burial Tests 156.1 General sample and test preparation 156.2 Fitting torque and bending tests .166.3 Interstitial strength test .176.4 Saturated soil load test .176.5 Inters
7、titial communication test .187 Long Term Compatibility 187.1 General sample and test preparation 187.2 Physical property and visual exam tests 207.2.2 Visual exam test .207.2.3 Bond Strength Test 217.2.4 Flexural strength test .217.2.5 Tensile strength test .227.3 Test sample exposures 228 Installat
8、ion and Production Tests 238.1 General 238.2 Tank tests 238.3 Impact test .238.4 Leakage test 24MARKINGS9 General .24JUNE 14, 2013 UL 1856 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINSTRUCTIONS10 General 25Appendix A Test Fuel Formulati
9、onsA1 Representative Aggressive Combustible Test Fuel Mixtures and UL-B100 .A1A2 Representative Aggressive Flammable Test Fuels and Mixtures .A2Appendix B PULL-OFF DISK PREPARATIONB1 Bond Strength Test Pull-Off Disks B1JUNE 14, 2013UL 18564UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCT
10、ION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover nonmetallic retrofit systems (products) intended for field installation insideof steel or fiberglass underground fuel tanks in commercial (public) or private (fleet) automotive fuelingstation applications. T
11、hese products are intended for containment of typical liquid fuels as identified in thisOutline, and may provide other features as described for each specific type of retrofit system.1.2 These products are nonmetallic thermoset (such as FRP, epoxy, PUR or polyesters) or thermoplastic(such as PE) mat
12、erials that may or may not be bonded to the interior tank wall, depending upon thesystem type. These products typically use pre-fabricated sections with coatings applied on site, orhomogeneous or layered spray-on/roll-on materials applied on site, and may optionally be covered forminor repair of the
13、 host tank.1.2.1 Lining systems provide only primary containment of stored fuels, and do not add significantstructural strength to the host tank.1.2.2 Upgrade systems provide both primary containment and secondary containment of stored fuels withinterstitial monitoring, and are co-structural with th
14、e host tank.1.2.3 Structural systems provide both primary containment and secondary containment of stored fuelswith interstitial monitoring, and are self-structural without the host tank.1.3 These products are intended for containment of automotive fuels and exposure to soil fluids that havesimilar
15、chemical, physical and material compatibility properties as represented by the test liquids in theserequirements based on fuels formulated in accordance with 40 CFR Part 80, Regulation of Fuels and FuelAdditives, and meeting the following ASTM Fuel Specifications and blend limitations:a) ASTM D-975,
16、 Standard Specification for Diesel Fuel Oils, with biodiesel blends up to amaximum of 5 percent (B5);b) ASTM D-7467, Standard Specification for Low Blend Biodiesel, with biodiesel blends from 6to 20 percent (B6 to B20).c) ASTM D-4814, Standard Specification for Automotive Spark-Ignition Engine Fuel,
17、 gasoline oroxygenated gasoline, with limited ethanol blends up to a maximum of 10 percent (E10);d) ASTM D-5798, Standard Specification for Ethanol Fuel Blends for Flexible-Fuel AutomotiveSpark-Ignition Engines, high blend ethanol, with gasoline/ethanol mixtures blends from 51 to 83percent (E51 E83)
18、; ande) Mid Range Ethanol Blends (E11 to E50) using variable mixtures of ASTM D4814 Low BlendEthanol and ASTM D5798 High Blend Ethanol1.4 Products covered by this outline are intended to be installed and used in accordance with one or moreof the following:a) Flammable and Combustible Liquids Code, N
19、FPA 30;b) Code for Motor Fuel Dispensing Facilities and Garages, NFPA 30A;c) Uniform Fire Code, NFPA 1;JUNE 14, 2013 UL 1856 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULd) International Fire Code published by the International Fire Counci
20、l; ore) Other applicable federal and state regulations for the specific product or application it isbeing utilized in.1.5 These products are intended for field installation, by only qualified persons, inside the host tankwithout a need for excessive excavation, in accordance with the manufacturers i
21、nstructions and the localrequirements. Prior to installation, cleaning, inspecting, repairing and preparing the host tank interiorsurface is also conducted by qualified persons in accordance with the manufacturers instructions.1.6 These products are intended to be periodically inspected and maintain
22、ed for continued service, ortaken out of service if deemed necessary by qualified persons in accordance with industry recommendedpractices, the manufacturers instructions or applicable regulations.1.7 These products and the manufacturers installation instructions have not been investigated for their
23、physiological effect, if any, for safety of any persons during the installation process, and the potential riskassociated with the opening, entering, purging, cleaning, inspecting, surface preparation, systeminstallation, and testing of a tank that has been used to store flammable or combustible liq
24、uids.1.8 These products and requirements are not intended to cover or evaluate the installation equipment,safety of the installer, compliance with worker safety regulations (such as confined spaces, hazardouslocations, or OSHA), or any environmental emissions or disposal regulations, (such as EPA).1
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT18562013OUTLINEOFINVESTIGATIONFORUNDERGROUNDFUELTANKINTERNALRETROFITSYSTEMSISSUE1 地下 燃料箱 内部

链接地址:http://www.mydoc123.com/p-1069200.html