ASTM C846-2016 Standard Practice for Application of Cellulosic Fiber Insulating Board for Wall Sheathing《墙护蔽用绝热纤维素纤维板应用的标准实施规程》.pdf
《ASTM C846-2016 Standard Practice for Application of Cellulosic Fiber Insulating Board for Wall Sheathing《墙护蔽用绝热纤维素纤维板应用的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM C846-2016 Standard Practice for Application of Cellulosic Fiber Insulating Board for Wall Sheathing《墙护蔽用绝热纤维素纤维板应用的标准实施规程》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C846 16Standard Practice forApplication of Cellulosic Fiber Insulating Board for WallSheathing1This standard is issued under the fixed designation C846; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last
2、revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the requirements for storing,handling, and application of cellulosic fiber insulating boardproducts.1.
3、2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.3 This standard does not purport to address all of thesafety concerns, if any, associ
4、ated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C208 Specification for Cellulosic Fiber Insulating BoardD15
5、54 Terminology Relating to Wood-Base Fiber and Par-ticle Panel Materials2.2 Federal Specifications:FF-N-105-B with Interim Amendment 4 Nails, Brads,Staples and Spikes: Wire Cut and Wrought3UU-B-790-A Building Paper, Vegetable Fiber: (Kraft,Waterproofed, Water Repellent and Fire Resistant)33. Termino
6、logy3.1 Definitions of Terms Specific to This Standard:3.1.1 exterior finishthe shingle, lap, or panel sidingmaterial, masonry veneer, or stucco applied over the sheathingas a protective, decorative exterior finish of the building.3.1.2 fastenersnails, staples, or screws used for applica-tion of the
7、 sheathing.3.1.3 framing membersthose portions of the studs,headers, bracing, and blocking which serve to receive thesheathing. Framing members can be wood or metal.3.1.4 regular wall sheathingdescribed in DefinitionsD1554 and Specification C208. It is 4 ft (1.22 m) wide withsquare-cut edges on all
8、sides and12 in. (12.7 mm) in thickness.3.1.5 structural wall sheathingdescribed in DefinitionsD1554 and Specification C208. When installed in accordancewith Section 7, it is considered a structural sheathing providingadequate racking resistance. It is 4 ft (1.22 m) wide and12 in.(12.7 mm) or2532 in.
9、 (19.8 mm) in thickness with square-cutedges on all sides.3.1.6 vertical applicationsheathing applied with the longedges parallel to the studs.4. Significance and Use4.1 This standard provides recommendations for the instal-lation in a safe and effective manner. Actual conditions mayvary greatly, an
10、d additional care should be taken to ensure asafe and effective installation.4.2 This standard presents requirements that are general innature and considered practical. They are not intended asspecific recommendations. The user should consult the manu-facturer for recommended application methods and
11、 procedures.4.3 This standard does not address the applicability ofregulatory limitations. This is the responsibility of the user.5. Materials5.1 Sheathing shall conform to Specification C208.5.2 Nails for application of sheathing to wood framing shallconform to Federal Specification FF-N-105-B, inc
12、luding In-terim Amendment 4, and shall be in accordance with Table 1.1This practice is under the jurisdiction of ASTM Committee C16 on ThermalInsulation and is the direct responsibility of Subcommittee C16.40 on InsulationSystems.Current edition approved Sept. 1, 2016. Published September 2016. Orig
13、inallyapproved in 1976. Last previous edition approved in 2009 as C846 94 (2009).DOI: 10.1520/C0846-16.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards
14、 Document Summary page onthe ASTM website.3Available from Standardization Documents Order Desk, DODSSP, Bldg. 4,Section D, 700 Robbins Ave., Philadelphia, PA 19111-5098, http:/www.dodssp.daps.mil.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. Unit
15、ed States15.3 Staples for application of12-in. and2532-in. sheathing towood framing shall meet the following requirements:Gage 16Thickness, min, in. (mm) 0.057 (1.45)Width, min, in. (mm) 0.063 (1.59)Length, min, in. (mm) 112 (38.1)Crown, min, in. (mm)716 (11.1)Points chisel pointdivergent pointdiver
16、gent chisel point5.4 Screws for application of12-in. and2532-in. sheathing on14-gage (0.075-in.) (1.90-mm) to 20-gage (0.036-in.)(0.91mm) steel studs shall meet the following requirements:Head type bugle headHead diameter, min, in. (mm)516 (7.94)Length, min, in. (mm) 114 (31.8)Major diameter, in. (m
17、m)964 (3.57)Minor diameter, in. (mm)764 (2.78)Point drill point5.5 Framing Members shall be of such size and quality as tobe structurally adequate for the type of building being con-structed.5.5.1 Stud spacing shall be 16 in. (0.41 m) or 24 in. (0.61 m)on center depending on code requirements.6. Sto
18、rage6.1 Sheathing shall be stored flat, and supported and pro-tected from direct contact with the ground. Sheathing shall notbe stored in a heated warehouse and shall be allowed to cometo equilibrium at job site conditions prior to application.Sheathing should be protected from rain prior to install
19、ation.7. Application (see Table 2)7.1 Vertical Application (see Fig. 1)Apply 4-ft (1.22-m)wide by12-in. (12.7-mm) or by2532-in. (19.8-mm) sheathingvertically with long edges parallel to the vertical studs. Centerall joints over the framing members with a18-in. (3.18-mm)gap between edges. Leave a18-i
20、n. gap at doors, windows, andhorizontal joints. Sheathing should extend from sill to plate. Ifnot, headers for adequate nailing should be provided at allhorizontal joints. Apply fasteners for12-in. or2532-in. materialusing roofing nails, common nails (5.2) or staples (5.3) forwood framing and screws
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC8462016STANDARDPRACTICEFORAPPLICATIONOFCELLULOSICFIBERINSULATINGBOARDFORWALLSHEATHING 墙护蔽用 绝热 纤维素

链接地址:http://www.mydoc123.com/p-508524.html