ASTM B174-2010 Standard Specification for Bunch-Stranded Copper Conductors for Electrical Conductors《电导线用成束绞捻的铜导线标准规范》.pdf
《ASTM B174-2010 Standard Specification for Bunch-Stranded Copper Conductors for Electrical Conductors《电导线用成束绞捻的铜导线标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM B174-2010 Standard Specification for Bunch-Stranded Copper Conductors for Electrical Conductors《电导线用成束绞捻的铜导线标准规范》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: B174 10Standard Specification forBunch-Stranded Copper Conductors for ElectricalConductors1This standard is issued under the fixed designation B174; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revi
2、sion. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification covers bare bunch-stranded
3、conduc-tors made from round copper wires, either uncoated or coatedwith tin, lead, or lead-alloy for use as electrical conductors(Explanatory Note 1 and Explanatory Note 2).1.2 Coated wires shall include only those wires with fin-ished diameters and densities substantially equal to the respec-tive d
4、iameters and densities of uncoated wires.1.3 The values stated in either SI units or inch-pound unitsare to be regarded separately as standard. The values stated ineach system may not be exact equivalents; therefore, eachsystem shall be used independently of the other. Combiningvalues from the two s
5、ystems may result in non-conformancewith the standard.1.3.1 For conductor sizes designated by AWG or kcmil, therequirements in SI units have been numerically converted fromcorresponding values, stated or derived, in inch-pound units.For conductor sizes designated by SI units only, the require-ments
6、are stated or derived in SI units.2. Referenced Documents2.1 The following documents of the issue in effect at thetime of reference form a part of this specification to the extentreferenced herein:2.2 ASTM Standards:2B3 Specification for Soft or Annealed Copper WireB33 Specification for Tin-Coated S
7、oft or Annealed CopperWire for Electrical PurposesB172 Specification for Rope-Lay-Stranded Copper Con-ductors Having Bunch-Stranded Members, for ElectricalConductorsB189 Specification for Lead-Coated and Lead-Alloy-Coated Soft Copper Wire for Electrical PurposesB193 Test Method for Resistivity of El
8、ectrical ConductorMaterialsB263 Test Method for Determination of Cross-SectionalArea of Stranded ConductorsB354 Terminology Relating to Uninsulated Metallic Elec-trical Conductors2.3 American National Standard:ANSI C42.35 Definitions of Electrical Terms33. Classification3.1 For the purpose of this s
9、pecification bunch-strandedconductors are classified as shown in Tables 1 and 2.4. Ordering Information4.1 Orders for material under this specification shall includethe following information:4.1.1 Quantity of each size and class,4.1.2 Conductor size: circular-mil area or AWG (see 7.1),4.1.3 Class (S
10、ection 3 and Table 3),4.1.4 Whether coated or uncoated; if coated, designate typeof coating (see 11.1),4.1.5 Maximum length of lay (see 6.3),4.1.6 Whether separator is required (see 7.2),4.1.7 Package size (see section 15.1),4.1.8 Special package marking, if required (Section 14), and4.1.9 Place of
11、inspection (Section 13).5. Joints5.1 Necessary joints in wires shall be made in accordancewith accepted commercial practice.5.2 Joints shall be so constructed and so disposed through-out the conductor that the diameter or configuration of thecompleted conductor is not substantially affected, and so
12、thatthe flexibility of the completed conductor is not adverselyaffected.1This specification is under the jurisdiction of ASTM Committee B01 onElectrical Conductors and is the direct responsibility of Subcommittee B01.04 onConductors of Copper and Copper Alloys.Current edition approved April 1, 2010.
13、 Published May 2010. Originallyapproved in 1941. Last previous edition approved in 2002 as B174 02 (2007)1.DOI: 10.1520/B0174-10.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume informati
14、on, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, Unit
15、ed States.6. Lay6.1 Conductors of the same size and description furnishedon one order shall have the same lay.6.2 The direction of lay shall be at the option of themanufacturer unless otherwise specified.TABLE 1 A Classification and Construction Requirements of Bunch-Stranded ConductorsAClass I Bunc
16、h Stranded ConductorsArea ofCross SectionClassification,Size,andMinimumNumberof WiresUncoated Copper Coated CopperSize,AWGClass INominalWire Diameter0.0201 In.(0.511 mm)Nominal dcresistance20CMaximum dcresistance20CNominal dcresistance20CMaximum dcresistance20CNominal dcresistance20CMaximum dcresist
17、ance20CNominal dcresistance20CMaximum dcresistance20Ccmil mm 24 AWG ohm/kft ohm/kft ohm/km ohm/km ohm/kft ohm/kft ohm/km ohm/km20820 10.5 7 52 0.508 0.518 1.67 1.70 0.528 0.539 1.73 1.7716510 8.37 8 41 0.641 0.654 2.10 2.14 0.666 0.679 2.19 2.2313090 6.63 9 33 0.808 0.824 2.65 2.70 0.840 0.857 2.76
18、2.8110380 5.26 10 26 1.02 1.04 3.34 3.41 1.06 1.08 3.48 3.55TABLE 1 B Classification and Construction Requirements of Bunch-Stranded ConductorsClass J Bunch Stranded ConductorsAArea ofCross SectionClassification,Size,andMinimumNumberof WiresUncoated Copper Coated CopperSize,AWGClass JNominalWireDiam
19、eter0.0126 In.(0.320 mm)Nominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20Ccmil mm 28 AWG ohm/kft ohm/kft ohm/km ohm/km ohm/kft ohm/kft ohm/km ohm/km10380 5.26 10 65 1.02 1.04
20、 3.34 3.41 1.08 1.10 3.54 3.616530 3.31 12 41 1.62 1.65 5.31 5.42 1.72 1.75 5.64 5.764110 2.08 14 26 2.57 2.62 8.44 8.61 2.73 2.79 8.96 9.142580 1.31 16 16 4.10 4.18 13.5 13.7 4.35 4.44 14.3 14.61620 0.821 18 10 6.53 6.66 21.4 21.9 6.94 7.07 22.8 23.21020 0.517 20 7 10.4 10.6 34.0 34.7 11.0 11.2 36.
21、1 36.8TABLE 1 C Classification and Construction Requirements of Bunch-Stranded ConductorsClass K Bunch Stranded ConductorsAArea ofCross SectionClassification,Size,andMinimumNumberof WiresUncoated Copper Coated CopperSize,AWGClass KNominalWireDiameter0.0100 In.(0.254 mm)Nominaldcresistance20CMaximumd
22、cresistance20CNominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20CNominaldcresistance20CMaximumdcresistance20Ccmil mm 30 AWG ohm/kft ohm/kft ohm/km ohm/km ohm/kft ohm/kft ohm/km ohm/km10380 5.26 10 104 1.02 1.04 3.35 3.41 1.09 1.12 3.58 3.656530 3.31 12 65 1.62 1.
23、65 5.31 5.42 1.74 1.77 5.71 5.824110 2.08 14 41 2.57 2.62 8.43 8.60 2.76 2.82 9.06 9.242580 1.31 16 26 4.10 4.18 13.5 13.7 4.40 4.49 14.4 14.71620 0.821 18 16 6.53 6.66 21.4 21.9 7.01 7.15 23.0 23.51020 0.517 20 10B10.4 10.6 34.1 34.8 11.1 11.4 36.4 37.1640 0.324 22 7 16.5 16.9 54.1 55.2 17.7 18.1 5
24、8.1 59.2AThe constructions shown in these tables are typical of those used in the industry. It is intended that these tables preclude other constructions which may be desirablefor specific applications. The constructions shown provide for a finished stranded conductor approximately of the area indic
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMB1742010STANDARDSPECIFICATIONFORBUNCHSTRANDEDCOPPERCONDUCTORSFORELECTRICALCONDUCTORS 导线 用成束绞捻 标准规范

链接地址:http://www.mydoc123.com/p-460531.html