1、 1 Copyright 2017 IEEE. All rights reserved. Interpretation Section 32. Underground conduit systems Rule 323B Manholes, handholes, and vaultsDimensions (2017 Edition, page 254) (11 September 2017) IR583 Question: Do the working spaces described in Rule 323B apply to underground structures with cable
2、s other than manholes? General Discussion: Rule 323B only mentions manholes in describing the working space required for cables. However, Rule 323B is invoked by Rule 341B2 as the clearances to be used in both manholes and vaults. Rule 323B is not written in a manner to describe clearances and equip
3、ment likely to be encountered in some secondary network vaults, which may contain equipment other than cables or an unoccupied wall. Rule 323B in the 2017 NESC Handbook does address manholes with transformers, but describes operating cut-outs that are not found on subway-type network transformers. A