1、 1 Copyright 2017 IEEE. All rights reserved. Interpretation Section 12. Installation and maintenance of equipment Rule 124 Guarding live parts (2017 Edition, page 48) (4 May 2017) IR582 Question: Rule 124 covers the guarding of live parts in substations. For the purposes of guarding, do cable termin
2、ations fall under parts of indeterminate potential (Rule 124A3) or insulating covering on conductors (Rule 124C6)? Discussion: The substations for our company utilize cable systems operating at 4160 V and 6900 V (phase to phase). The cables are multi-conductor, shielded, type MC and connect to the o
3、verhead bus via riser structures where the cables have cable termination kits (as per IEEE Std 48). Guarding for the live parts (the compression lugs) are governed by Rule 124A1 and are typically achieved using the clearances from Table 124-1. The insulated, shielded parts of the cable are guarded b
4、y insulation per Rule 124C6. The cable termination provides insulation from the conductor and the exposed live part (the lug) of the cable at the top of the termination and covers the grounded, shield wire that comes out of the bottom of the termination. The top of the termination is at line potenti
5、al, and the bottom of the termination is at ground potential, therefore the termination itself may be considered a part at indeterminate potential (Rule 124A3). However, the termination is also a non-shielded insulation covering the live parts of the cable, which for the 4160 V system would appear t
6、o meet the requirements of Rule 124C6a (less than 2500 V to ground). The 6900 V system exceeds the 2500 V to ground requirement of Rule 124C6a, as the termination itself is non-shielded. The exception for Rule 124C6a does reference Article 310.6 of the National Electrical Code (NEC) (NFPA 70) for us
7、e of non-shielded insulated conductors for use up to 8000 V (phase to phase). However, neither Article 310.6 nor the 8000 V exception are in the latest version of the 2017 Edition of the NEC. The 2002 Edition of the NEC was the last version to have the 8000 V exception. In the 2005 Edition, the exce
8、ption was changed to 2400 V; this change effectively required all 4160 V cable systems to use shielded conductors. Both the exception for NESC Rule 124C6a and the exception for NEC Article 310.6 required the non-shielded insulated conductors to be listed by a qualified testing laboratory. Following
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEENESCIR5822017ENNATIONALELECTRICALSAFETYCODEPDF

链接地址:http://www.mydoc123.com/p-1249381.html