IEEE NESCIR579-2016 en National Electrical Safety Code《国家电气安全规范》.pdf
《IEEE NESCIR579-2016 en National Electrical Safety Code《国家电气安全规范》.pdf》由会员分享,可在线阅读,更多相关《IEEE NESCIR579-2016 en National Electrical Safety Code《国家电气安全规范》.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、 1 Copyright 2016 IEEE. All rights reserved. Interpretation Section 11. Protective arrangements in electric supply stations Rule 110A General requirements Enclosure of equipment (2012 Edition, page 36) (24 May 2016) IR579 Question: An Interpretation from the NESC is requested on the following: Are f
2、ences around solar farms required to be grounded by NESC Rules? Duke Energy owns a solar farm that was designed and built by a firm that designs and builds solar farms. The facilities were designed and installed per National Electrical Code(NEC) requirements. Because the utility owns the solar farm,
3、 two questions have been raised about requirements for grounding the fence around the solar farm per the NESC. Question 1: Because the solar farm was designed and built to NEC requirements, would the NESC grounding requirements apply to the fence even though it is owned by the utility? Question 2: I
4、f the NESC does apply, is it the intent of Rule 110A to require fence grounding when there are no exposed conductors or equipment? Discussion: The NESC definition of electric supply stations includes generation stations, and paragraph 1, generation stations, includes solar in the definition. In sect
5、ion 11, Rule 110A, the following rule requires fences to be grounded: “Metal fences, when used to enclose electric supply stations having energized electric conductors or equipment, shall have a height not less than 2.13 m (7 ft) overall and shall be grounded in accordance with Section 9.” Article 2
6、50-194 in the NEC (NFPA 70, 2014 edition) has a similar rule, but it includes the word “exposed” electrical conductors and equipment. This is interpreted to mean no fence grounding is required if there are no exposed electrical conductors or equipment. 2 Copyright 2016 IEEE. All rights reserved. Int
7、erpretation This Interpretation is based on an understanding that your request (1) involves a fence around a utility owned solar farm (“perimeter fence”), (2) the solar panels are enclosed by this fence, and (3) the perimeter fence is the only fence or other means used to enclose the solar panels. S
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEENESCIR5792016ENNATIONALELECTRICALSAFETYCODE 国家 电气 安全 规范 PDF

链接地址:http://www.mydoc123.com/p-1249380.html