IEEE NESCIR577A-2014 en National Electrical Safety Code《国家电气安全规范》.pdf
《IEEE NESCIR577A-2014 en National Electrical Safety Code《国家电气安全规范》.pdf》由会员分享,可在线阅读,更多相关《IEEE NESCIR577A-2014 en National Electrical Safety Code《国家电气安全规范》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、 1 Copyright 2014 IEEE. All rights reserved. Interpretation Section 23. Clearances Rule 232.A. Table 1 Vertical clearance of wires above ground or rails Basic clearances Minimum vertical clearance of wires above ground or rails (1961, 6th Edition; Volume 12, NESC Archives, pages 56-57) (9 December 2
2、014) IR577a Question: What is the appropriate column in Table 1 contained within Rule 232.A. Basic Clearances to evaluate a service drop for minimum clearance? NOTE Perspective 1 the ”open” is implicit to service drops and they would fall into column 1 and 2, while perspective 2 is the use of column
3、 2. 2 Copyright 2014 IEEE. All rights reserved. The issue arises when attempting to evaluate service drop clearances for an insulated 120 V to ground service drop at the point of attachment to the building that are above spaces or ways accessible to pedestrians only to the terms of the 1961 Edition.
4、 One opinion is that in the text of the heading, “Open supply line wires, arc wires and service drops,” the “open” carries through the entire heading “Open supply line wires,” “Open arc wires” and “Open service drops.” This would indicate that only open wire service drops fall within column 2, and t
5、hat the applicable footnotes would be footnote 14 and footnote 8. In this first opinion, an insulated service drop would fall into column 1 under “insulated conductors supported on and cabled together with an effectively 3 Copyright 2014 IEEE. All rights reserved. grounded messenger,” and the applic
6、able footnote would be footnote 7. This opinion allows for a 120 V to ground service drop at the point of attachment to the building that was constructed with open wire under certain conditions to have a minimum 8 clearance, and for an insulated service drop under certain conditions to have a minimu
7、m clearance of 10 ft. A second opinion is that column 2, “Open supply line wires, arc wires and service drops” applies to all service drops as defined. This opinion allows for a 120 V to ground service drop at the point of attachment to the building under certain conditions to have a minimum 8 ft cl
8、earance. A complicating factor to applying either opinion to evaluating a service drop as the point of attachment is defined as customer equipment and subject to the National Electric Code, while the service drop is utility equipment and subject to the National Electric Safety Code. If the use of “o
9、pen” is implicit in establishing clearances for insulated 120 V to ground service drops, it is unclear how the transition between utility clearance requirements and customer attachment height requirements can be accommodated. Discussion: Additional Definitions and Rules 63. Service means the conduct
10、ors and equipment for delivering electric energy from the secondary distribution or street main, or other distribution feeder, or from the transformer, to the wiring system of the premises served. For overhead circuits, it includes the conductors from the last line pole to the service switch or fuse
11、. The portion of the overhead service between the pole and building is designated as “service drop.” 230. C Supply Cables As far as clearances are concerned, supply cable having effectively grounded continuous metal sheath, or insulated conductors supported on and cabled together with an effectively
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEENESCIR577A2014ENNATIONALELECTRICALSAFETYCODE 国家 电气 安全 规范 PDF

链接地址:http://www.mydoc123.com/p-1249378.html