1、CEPT T/L*02-10*E 87 m 232b4l14 0005947 9 m 1 TlLO;-ii; (old reference: T/TR 02-1 O E) Recommendation T/L 02-10 (Copenhagen 1987) POWER SUPPLIES FOR TELECOMMUMCATIONS EQUIPMENT INSTALLED IN CUSTOMERS PREMISES Recommendation proposed by Working Group T/WG 12 “Transmission and multiplexing” (TM) Text o
2、f Recommendation adopted by the “Telecommmications” Commission: “The European Conference of Post and Telecommunications Administrations, considering - that telecommunications equipment may be installed in customers premises, - that the power supply for telecommunications equipment from various origi
3、ns requires standardisation, - that existing CCITT and CCIR Recommendations in such matters do not ensure the required standardisation, - that the CCITT and CCIR do not envisage standardising the power supply interface for telecommunications equipment installed in customers premises, - that the Admi
4、nistrations are amendable to the harmonisation of telecommunications equipment, which will lead to a lowering of development and manufacturing costs for the industry which is supplying equipment to several countries, a recommends that the members of the CEPT should apply the specifications contained
5、 in this Recommendation.” Edition of December 15, 1987 7 CEPT T/L*02-3O*E ? I 2326434 0005948 O m T/L 02-10 E Page 2 1. 2. 3. 3.1. 3.2. 4. 4.1. 4.2. 4.3. 4.3.1, 4,3.2. 5. 5,l. 5.1.1. 5.1.2. 5.1.3. 5.2. 5.3. 5.3.1. 5.3.2. 6. 7. Contents AREA OF APPLICATION . . . . . . . . . . . . . . . . . . . . . .
6、. . . . . . . . . 2 OBJECTIVES . . , , . . . . . . . . . . . . . . . . . . . . . . . . . . . . . , , . . 2 POWER SUPPLY INTERFACES . . . . , , . . . . . . . , . . . . . . . , . . . . . . 2 Power supply at interface I,. . , . . . . . . , . . . . . . , . . . . . . . . , , . . . . . 2 Power supply at i
7、nterface I,. . . , . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SAFETY REQUIREMENTS. . , . . . . , . . . . . . . , , . . . . . . . . . . . . . . 3 General 3 Safety requirements for the power supply installations and interfaces . . . . . . . , . . . . . . 3 Safety requirements of equipme
8、nt , . . . . . . . . . . . . . . . . . . . . . . . . , . . . 3 Telecoms equipment . . . . . . . . . , . . . . . . . . . . . . . . . . . . . . . . . , , 3 Other. equipment connected to Telecoms equipment or Telecoms network . . . . . . . . . . . . 3 PERFORMANCE CHARACTERISTICS . . . . . . . . . . . .
9、 . . . . . . , . . . . . . 3 Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Nominal values andfiequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Tolerance of voltages andflequency in normal service . . . . . . . . . . , . . . . . . .
10、 . . 4 Impulse withstand voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Surge current. , , . . . . . . . . . . . . . . . . . . . . . . . . . . . . . , . , . . . 4 Reaction of equipment to the power supply source . . . . . . . . . . . . . . . . . . . . . . 5 Harmonics re-i
11、njected into the ac supply . . . . . , . . . . . . . , . . . . . . . , . . . . 5 Noise re-injected on ac supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 EARTHING AND EQUIPOTENTIAL BOUNDING . . . . . . . . . . . . . . . . . . . . 5 LISTOFQUOTEDCEPTRECONDATIONSANDIECSTANDARDS . .
12、 . . . . . . 5 1. AREA OF APPLICATION This Recommendation applies to all telecommunications equipment installed in customers premises : - directly connected to the Administrations network, - having a primary or secondary power supply interface as shown in Figure 1 (T/L 02-10), - and is operated by t
13、he customer. Equipment should be developed in such a way that the power supply specifications are observed at the interfaces. These interfaces should be at a physical point at the power input to the equipment. 2. OBJECTIVES - To facilitate the harmonisation of telecommunication equipments. - To faci
14、litate the installation, operation and maintenance in customers premises, of equipment and - To define the power supply interface between the telecommunications equipment and the customers - To define safety requirements for the protection of persons either inside or outside customers premises. tele
15、communications systems from different origins. premises. 3. POWER SUPPLY INTERFACES The power supply interfaces are as shown in Figure 1 (T/L 02-10). Power supply at interface I, Where equipment is connected to the public mains/local ac generator supply via interface I, the primary power supply spec
16、ification shall be as described in sections 4 and 5. Power supply at interface I, Where equipment is connected to a secondary voltage via interface I, the secondary voltage supply specification should be in accordance with Recommendation T/L 02-02. 3.1. 3.2. Edition of December 15, 1987 CEPT T/L*OZ-
17、LO*E 87 I 2326434 0005949 2 m TIL 02-10 E Page 3 4. 4.1. 4.2. 4.3. 4.3.1. 4.3.2. 5. 5.1. 5.1.1. SAFETY REQUIREMENTS General The principle adopted in this Recommendation is that safety of persons or equipment should be assured with regard to the hazards that may come from: i) the power supply install
18、ation and interfaces, ii) the Telecoms equipment, iii) the Telecoms network, iv) other equipment connected to Telecoms equipment or the network. In each case safety specifications are given in accordance with IEC standards having a pilot function and/or the appropriate group and product standards ac
19、cording to IEC Guide 104. If no IEC standards are published for a particular aspect, appropriate Recommendations are specified from similar or other applicable IEC standards. Safety requirements for the power supply installations and interfaces Safety requirements for ac supply installations are giv
20、en in IEC Publication 364, which is the standard with pilot function for protection against electric shock and also the product standard concerning electrical installations of buildings. Where ac is used, whether at interface Il or 12, the installation must comply with IEC Publication 364. When dc i
21、s the power supply at interface I2 within the voltage ranges given in TIL 02-02 it must come from a safety source according to IEC Publication 364-4-41. Where protective earthing of the equipment is prescribed in the relevant equipment safety standards as a means of implementing the required touch-s
22、afe conditions, the protective earthing should not rely on the telecommunication network to which the equipment is connected. In situations where protective earthing does not exist, class I equipment should not be connected to telecommunications networks. Safety requirements of equipment Telecoms eq
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- CEPTTL0210E1987POWERSUPPLIESFORTELECOMMUNICATIONSEQUIPMENTINSTALLEDINCUSTOMERSPREMISES 电源 供给 作为 电信设备

链接地址:http://www.mydoc123.com/p-593117.html