ASTM E2816-2013 Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf
《ASTM E2816-2013 Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2816-2013 Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf(23页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2816 12aE2816 13 An American National StandardStandard Test Methods forFire Resistive Metallic HVAC Duct Systems1This standard is issued under the fixed designation E2816; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revisio
2、n, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONHeating, Ventilation, Air Conditioning (HVAC) duct systems may be subjected to fire- exposureconditions
3、. ISO 6944 is a standard test method used to evaluate ventilation ducts. However, ISO 6944does not address all of the fire resistive attributes deemed necessary by some authorities havingjurisdiction, for example, (1) the fire-resistive, combustibility, flame spread and smoke generation, anddurabili
4、ty properties of the fire-resistive materials protecting the HVAC duct, (2) the transition fromthe horizontal to a vertical HVAC duct, (3) the attachment of the HVAC ducts supports to thefire-separating elements, (4) the termination of an HVAC duct system and the protection of its ends,(5) the effec
5、ts of rapid cooling and erosion upon the HVAC duct system, (6) the use of fire dampersand (7) the effect of the HVAC duct system on its supporting construction. Many types of fire-resistivematerials are used to protect HVAC ducts. These fire-resistive materials are either applied to HVACducts in the
6、 field or are fabricated as an integral part of the HVAC duct system when shipped from thefactory. Evaluating fire-resistive materials used to protect a HVAC duct from fire is an aid forpredicting their fire performance and helps to establish uniformity in requirements of variousauthorities. To do t
7、his it is necessary that the fire-resistance properties of HVAC ducts protected withfire-resistive materials be measured and specified according to a common standard expressed in termsthat are applicable alike to a wide variety of materials, situations, and conditions of exposure.1. ScopeNOTE 1Use o
8、f the standard designation ISO 6944 refers to both ISO 6944:1985 and ISO 6944-1:2008.1.1 These test methods evaluate the fire-resistive materials and the HVAC duct systems surface burning characteristics,non-combustibility, fire resistance, durability, and fire-engulfment with horizontal and vertica
9、l through-penetration firestops.NOTE 2The intent of these test methods is to provide authorities having jurisdiction a means to evaluate the fire performance of HVAC duct systemsto enable their application and use.1.2 These test methods evaluate the fire performance of HVAC ducts, including both sup
10、ply (pressurized: Condition A Horizontal and Condition B Vertical) and return (exhaust: Condition C Horizontal and Condition D Vertical).1.3 These test methods evaluate the ability of a HVAC duct system to resist the spread of fire from one compartment to othercompartments separated by a fire resist
11、ance rated construction when the HVAC duct system is exposed to fire under one or moreof the following conditions:1.3.1 Condition AFire exposure from the outside of the horizontal HVAC duct system without openings,1.3.2 Condition BFire exposure from the outside of the vertical HVAC duct system witho
12、ut openings,1.3.3 Condition CFire exposure from the outside with hot gases entering the inside of the horizontal HVAC duct system withunprotected openings, andNOTE 3Unprotected openings are openings that are not protected by fire dampers.1.3.4 Condition DFire exposure from the outside with hot gases
13、 entering the inside of the vertical HVAC duct system withunprotected openings.1.4 These test methods provide a means for determining the fire-resistance of vertical and horizontal HVAC duct systems, whensubjected to the standard time-temperature curve of Test Methods E119.1 These test methods are u
14、nder the jurisdiction of ASTM Committee E05 on Fire Standards and are the direct responsibility of Subcommittee E05.11 on Fire Resistance.Current edition approved Dec. 1, 2012May 1, 2013. Published December 2012May 2013. Originally approved in 2011. Last previous edition approved in 2012 asE2816-12.
15、-12a. DOI: 10.1520/E2816-12A.10.1520/E2816-13.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately
16、, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States11.
17、4.1 Condition AThese test methods provide a means for evaluating a horizontal HVAC duct system, without openingsexposed to fire, passing through a vertical fire-separating element.1.4.2 Condition BThese test methods provide a means for evaluating a vertical HVAC duct system, without openings exposed
18、to fire and outfitted with a horizontal connection, passing through a horizontal fire-separating element.1.4.3 Condition CThese test methods provide a means for evaluating a horizontal HVAC duct system, with unprotectedopenings exposed to fire, passing through a vertical fire-separating element.1.4.
19、4 Condition DThese test methods provide a means for evaluating a vertical HVAC duct system with a horizontalconnection, and with unprotected openings exposed to fire, passing through a horizontal fire-separating element.1.5 These test methods prescribe a standardized fire exposure for comparing the
20、test results of the fire resistive materials andHVAC duct systems. The results of these tests are one factor in assessing predicted fire performance of HVAC duct systems. Usingthese test results to predict the performance of actual HVAC duct systems requires the evaluation of test conditions.1.6 The
21、 values stated in inch-pound units are to be regarded as the standard. The SI values given in parentheses are forinformation only, unless the SI units are used consistently to perform all of the test methods referenced herein. In this case, theSI units will be regarded as the standard and will be us
22、ed in Section 17, Report.1.7 The text of these test methods references notes and footnotes which provide explanatory material and (excluding those intables and figures) shall not be considered as requirements of the fire-test-response standard.1.8 This document specifically excludes evaluating ducts
23、 that carry combustibles, flammable vapors, combustible gases, andcommercial kitchen ventilation systems commonly called grease ducts or hazardous exhaust ducts, which are tested in compliancewith Test Methods E2336.1.9 This standard is used to measure and describe the response of materials, product
24、s, or assemblies to heat and flame undercontrolled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials,products, or assemblies under actual fire conditions.1.10 This standard does not purport to address all of the safety concer
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME28162013STANDARDTESTMETHODSFORFIRERESISTIVEMETALLICHVACDUCTSYSTEMS 防火 金属 采暖 通风 空调 管道 系统 标准 试验 方法

链接地址:http://www.mydoc123.com/p-531937.html