1、Comments, suggestions, or questions on this document should be addressed to WR-ALC/LGEC, 480 Richard Way Blvd. Suite 200, Robins AFB, GA 31098-1640 or emailed to bob.yoherobins.af.mil . Since contact information can change, you may want to verify the currency of this address information using the AS
2、SIST Online database at www.dodssp.daps.mil. AMSC N/A FSC 4120 DISTRIBUTION STATEMENT A: Approved for public release; distribution is unlimited. A-A-59501 02 July 2004 COMMERCIAL ITEM DESCRIPTION AIR CONDITIONING UNIT, ELECTRIC DRIVEN, TRAILER MOUNTED The General Services Administration has authoriz
3、ed the use of this commercial item description by all federal agencies. 1. SCOPE. This commercial item description (CID) covers a wheel-mounted, electric motor driven single-pass air conditioning unit of not less than 110 tons nominal cooling capacity (EAC110). 2. PRECEDENCE. 2.1 Precedence. The EAC
4、110 shall comply with the requirements of this document and shall comply with the applicable requirements of ASHRAE Standard 52.2; Federal Acquisition Regulations; FED-STD 595; NFPA 70 (Class 1, Division II, Group D hazardous area); OSHA; SAE AIR 1375, SAE ARP1247, SAE ARP1801, SAE ARP5374, SAE AS80
5、90, (Type II, Group C), SAE AS38386, SAE J447, and SAE J551 in effect at the time of manufacture, unless otherwise stated. Unless otherwise stated, this document has precedence over a referenced document. Where referenced documents may conflict in characteristic or performance, the more stringent re
6、quirement shall establish the minimum. 3. SALIENT CHARACTERISTICS. 3.1 Description. The EAC110 shall selectively operate as an air conditioning unit, a ventilation unit, or a heating unit. The EAC110 shall consist of electric motor driven; vapor cycle air conditioning system, air delivery and distri
7、bution system, and the necessary controls, wiring, piping, instrumentation, and housing with wheel-mounted fully suspended undercarriage, as specified herein. The EAC110 shall deliver not less than 600 pounds per minute (ppm) of conditioned air to military aircraft through three 12-inch diameter fle
8、xible supply air ducts. The EAC110 shall be designed; to operate in any mode continuously, to require not less than 200 hours between service maintenance, to operate not less than 2000 hours per year, and for a service life of 20 years. Major component rebuilds shall not be required more frequently
9、than every 10,000 hours operation. INCH-POUND Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59501 23.1.1 Performance. The EAC110 shall be capable of storage, and operation under the following environmental conditions: a. Storage temperature ran
10、ge from -60F to +165F. b. Operating temperatures range from 0F to +125F. c. Exposure to relative humidity up to 100 percent. d. Exposure to salt fog consistent with a seaside environment. e. Exposure to blowing sand and dust particles as encountered in desert areas. 3.1.1.1 Cooling. The EAC110 shall
11、 deliver not less than 1,320,000 British Thermal Units (BTU)s of cooling, as measured by air enthalpy method of SAE ARP5374, at entering ambient air conditions of 97F dry-bulb and 85F wet-bulb. Cooling mode shall operate between ambient conditions of +40F and +125F. Leaving air conditions in cooling
12、 mode shall be manually resettable down to +50F. System controls shall maintain discharge temperature setting automatically, up to total system cooling capacity. Exceeding system capacity shall only cause a loss of set-point control and shall not disengage the function. 3.1.1.2 Heating. The EAC110 s
13、hall deliver not less than 750,000 BTUs of reverse cycle cooling at entering ambient conditions of 47F. Cooling mode shall operate between ambient conditions of +20F and +70F. Leaving air temperature shall be manually resettable up to 80F. System controls shall maintain discharge temperature setting
14、 automatically, up to total system heating capacity. Exceeding system capacity shall only cause a loss of set-point control, and shall not disengage the function. 3.2 Standard commercial product. The EAC110 shall, as a minimum, be in accordance with the requirements of this CID and shall be the manu
15、facturers standard commercial product. Additional or better features, not specifically prohibited by this CID, but which are a part of the manufacturers standard commercial product, shall be included in the air conditioner furnished. 3.3 Interchangeability. All delivered EAC110 units shall be identi
16、cal to the extent necessary to ensure interchangeability of component parts. 3.4 Electric power requirements. The EAC110 shall operate on 480 V, 3 phase, 60 Hz power. A 100-foot flexible insulated power cable (three conductor with ground) shall be provided with the EAC110. The cable shall be attache
17、d to a power distribution box within the EAC110, shall store within the housing, and shall be unterminated at the free end. All power from the distribution box shall be circuit protected from overload. Electric motors shall be time delay over-current protected. Electric motor starting shall be acros
18、s the line for motors of 20 h.p. or less, and reduced voltage for motors exceeding 20 h.p. Power shall be transformed to reduced voltage for operation of all systems controls and instruments. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59501
19、33.5 Reversible vapor-cycle system. The EAC110 vapor-cycle system shall operate on a single phase refrigerant that is neither a Class I or Class II Ozone Depleting Substance/Compound (ODS/ODC). The EAC110 reversible vapor-cycle system shall include compressor(s), condenser and evaporator coil(s), am
20、bient air fan(s), expansion valve(s) and operational controls. The compressor manufacturer shall coordinate on the system configuration and the engagement method. The compressor shall not be a piston type design. Motor driven components shall be vibration isolated from the housing and connected syst
21、ems. Controls shall maintain discharge air quality below saturation and shall maintain temperature within 3 F from the set-point, while operating within total system design capacity. Coil defrost shall be automatically controlled. Controls shall isolate at least 95% of the system refrigerant during
22、normal shut-down sequence. Should the vapor-cycle system be shutdown by a safety device or emergency action, upon re-establishment of power, the controls shall start and complete a normal shut-down sequence prior to re-starting vapor-cycle operation in accordance with controls settings. Safety featu
23、res shall shut down the system, if any set-point limit for temperatures, fluid levels, flows, or pressures are exceeded. 3.6 Air delivery and distribution system. The air delivery system design point shall be 600 ppm at an external static pressure of not less than 40 inches water column. Total air d
24、elivery volume shall be adjustable between 300 and 700 ppm. Air shall be routed through three 12-inch discharge outlets with individual duct volume controls. Discharge outlets shall include mating connections for attachment of 12-inch female air duct hose connectors in accordance with SAE AS38386/2.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AIRFORCEAA595012004AIRCONDITIONINGUNITELECTRICDRIVENTRAILERMOUNTED 安置 拖车 电力 驱动 空调 机组 PDF

链接地址:http://www.mydoc123.com/p-427102.html