VA 23 22 23-2010 STEAM CONDENSATE PUMPS.pdf
《VA 23 22 23-2010 STEAM CONDENSATE PUMPS.pdf》由会员分享,可在线阅读,更多相关《VA 23 22 23-2010 STEAM CONDENSATE PUMPS.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、02-10 23 22 23 - 1 SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between / - / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraph. PART 1 - GENERAL 1.1 DESCRIPTION A. Steam condensate pumps for Heating
2、, Ventilating and Air Conditioning. 1.2 RELATED WORK A. Section 01 00 00, GENERAL REQUIREMENTS. B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. /C. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS./ D. Section 23 05 11, COMMON WORK RESULTS FOR HVAC and ST
3、EAM GENERATION. E. Section 23 05 41, NOISE and VIBRATION CONTROL FOR HVAC PIPING and EQUIPMENT. F. Section 23 22 13, STEAM AND CONDENSATE HEATING PIPING. G. Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC and STEAM GENERATION EQUIPMENT. 1.3 QUALITY ASSURANCE A. Refer to Paragraph, QUALITY ASSU
4、RANCE in Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION. B. Design Criteria: 1. Pumps design and manufacturer shall conform to Hydraulic Institute Standards. 2. Pump sizes, capacities, pressures, operating characteristics and efficiency shall be as scheduled. 3. Select pumps so
5、that required net positive suction head (NPSHR) does not exceed the net positive head available (NPSHA). 4. Pump Driver: Furnish with pump. Size shall be non-overloading at any point on the head-capacity curve including one pump operation in a parallel or series pumping installation. 5. Provide all
6、pumps with motors, impellers, drive assemblies, bearings, coupling guard and other accessories specified. Statically and dynamically balance all rotating parts. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 23 22 23 - 2 6. Furnish each pump a
7、nd motor with a nameplate giving the manufacturers name, serial number of pump, capacity in GPM and head in feet at design condition, horsepower, voltage, frequency, speed and full load current and motor efficiency. 7. Test all pumps before shipment. The manufacturer shall certify all pump ratings.
8、8. After completion of balancing, provide replacement of impellers or trim impellers to provide specified flow at actual pumping head, as installed. 9. Furnish one spare seal and casing gasket for each pump to the / Resident Engineer/ Project Manager /. C. Allowable Vibration Tolerance for Pump Unit
9、s: Section 23 05 41, NOISE and VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Manufacturers Literature and Data: 1. Pumps and accessories. 2. Motors and drives. C. Manufacturers installation,
10、 maintenance and operating instructions, in accordance with Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION. D. Characteristic Curves: Head-capacity, efficiency-capacity, brake horsepower-capacity, and NPSHR-capacity for each pump. 1.5 APPLICABLE PUBLICATIONS A. The publications
11、listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only: B. American Iron and Steel Institute (AISI): AISI 1045 Cold Drawn Carbon Steel Bar, Type 1045 AISI 416 . Type 416 Stainless Steel C. American National S
12、tandards Institute (ANSI): ANSI B15.1-00(R2008)Safety Standard for Mechanical Power Transmission Apparatus ANSI B16.1-05 Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 and 800 D. American Society for Testing and Materials (ASTM): A48-03(2008) . Standard Specification for Gray Iron C
13、astings Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 23 22 23 - 3 B62-09 . Standard Specification for Composition Bronze or Ounce Metal Castings E. Maintenance and Operating Manuals in accordance with Section 01 00 00, GENERAL REQUIREMENTS.
14、1.6 DEFINITIONS A. Capacity: Liters per second (L/s) (Gallons per minute (GPM) of the fluid pumped. B. Head: Total dynamic head in kPa (feet) of the fluid pumped. PART 2 - PRODUCTS 2.1 CONDENSATE PUMP, PAD-MOUNTED A. General: Factory assembled unit consisting of vented receiver tank, motor-driven pu
15、mps, interconnecting piping and wiring, motor controls (including starters, if necessary) and accessories, designed to receive, store, and pump steam condensate. B. Receiver Tank: Cast iron with threaded openings for connection of piping and accessories and facilities for mounting float switches. Re
16、ceivers for simplex pumps shall include all facilities for future mounting of additional pump and controls. C. Furnish seals for condensate pump with a minimum temperature rating of 121 degrees C (250 degrees F). D. Centrifugal Pumps: Bronze fitted with mechanical shaft seals. 1. Designed to allow r
17、emoval of rotating elements without disturbing connecting piping or pump casing mounting. 2. Shafts: Stainless steel, AISI Type 416 or alloy steel with bronze shaft sleeves. 3. Bearings: Regreaseable ball or roller type. 4. Casing wearing rings: Bronze. E. Motors: Refer to Section 23 05 12, GENERAL
18、MOTOR REQUIREMENTS FOR HVAC and STEAM GENERATION EQUIPMENT. F. Pump Operation: 1. Float Switches: NEMA 1, mounted on receiver tank, to start and stop pumps in response to changes in the water level in the receiver and adjustable to permit the controlled water levels to be changed. Floats and connect
19、ing rods shall be copper, bronze or stainless steel. 2. Alternator: Provide for duplex units to automatically start the second pump when the first pump fails in keeping the receiver water level from rising and to alternate the order of starting the pumps. Provided by IHSNot for ResaleNo reproduction
20、 or networking permitted without license from IHS-,-,-02-10 23 22 23 - 4 For units 0.25 kW (1/3 horsepower) and smaller, the alternator may be the mechanical type for use in lieu of float switches. G. Control Cabinet for 3 Phase (0.37 kW (1/2 hp) and larger) Units: NEMA 1, UL approved, factory wired
21、, enclosing all controls, with indicating lights, manual switches and resets mounted on the outside of the panel. Attach cabinet to the pump set with rigid steel framework, unless remote mounting is noted on the pump schedule. 1. Motor starters: Magnetic contact types with circuit breakers or combin
22、ation fusible disconnect switches. Provide low voltage control circuits (120 volt maximum) and “hand-off-automatic“ (H-O-A) switches for each pump. 2. Indicating lights for each pump: Green to show that power is on, red to show that the pump is running. H. Electric Wiring: Suitable for 93 degrees C
23、(200 degrees F) service; enclosed in liquid-tight flexible metal conduit where located outside of control cabinet. I. Receiver Accessories: 1. Thermometer: 34-216 degrees C (100 - 420 degrees F), mounted below minimum water level. 2. Water level gage glass: Brass with gage cocks which automatically
24、stop the flow of water when the glass is broken. Provide drain on the lower gage cock and protection rods for the glass. 2.2 CONDENSATE PUMP, SUMP TYPE A. General: Factory assembled unit consisting of motor-driven pump(s) mounted on a horizontal cover plate bolted to a vented sump-type receiver, int
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2322232010STEAMCONDENSATEPUMPSPDF