UL SUBJECT 1953-2014 UL Outline of Investigation for Power Distribution Blocks (Issue 5)《配电座调查大纲(议题5)》.pdf
《UL SUBJECT 1953-2014 UL Outline of Investigation for Power Distribution Blocks (Issue 5)《配电座调查大纲(议题5)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 1953-2014 UL Outline of Investigation for Power Distribution Blocks (Issue 5)《配电座调查大纲(议题5)》.pdf(22页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 29, 20141UL 1953Outline of Investigation for Power Distribution BlocksIssue Number: 5August 29, 2014Summary of TopicsThis Fifth issue of the Outline of Investigation for Power Distribution
2、Blocks , UL 1953, dated August 29, 2014 replaces the fifth issue publishedon August 19, 2014. The August 29, 2014 issue includes an editorialcorrection in Table 8.1, which increased the voltage limit maximum from600 to 1000 volts.ULs Outlines of Investigation are copyrighted by UL. Neither a printed
3、 norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2014 UNDERWRITERS LABORATORIES INC.UL
4、COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 29, 2014UL 19532No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .52 Glossary .53 Units
5、 of Measurement .64 Updated References 65 Components 6CONSTRUCTION6 Materials .66.1 Current-carrying parts .66.2 Insulation .77 Terminal Assemblies 77.1 General .77.2 Tightening torque .97.3 Minimum size of conductor for line side service applications .98 Spacings 108.1 General 108.2 Insulating barr
6、iers .118.3 Insulating Covers 12PERFORMANCE9 General .1210 Temperature Test .1411 Dielectric Voltage-Withstand Tests 1511.1 General .1511.2 Clamped insulating joint .1511.3 Insulating barriers 1612 Strength of Insulating Base and Support Test 1613 Short-Circuit Current Test 16RATINGS14 General 1715
7、Short-Circuit Current 17MARKINGS16 General 1717 Connectors 1818 Short Circuit Current 1919 Insulating Covers .2019.1 General .2019.2 Use on line side of service equipment 2020 Permanence of Marking .20AUGUST 29, 2014 UL 1953 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBU
8、TION WITHOUT PERMISSION FROM ULAPPENDIX AStandards for ComponentsA1AUGUST 29, 2014UL 19534UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover power distribution blocks that are rated 1000 volts or le
9、ss and intended tobe used on either the line side or load side of service equipment in accordance with the National ElectricalCode, NFPA 70. These blocks are used for splicing and tapping conductors in order to distribute powerto separate circuits or loads.1.2 A power-distribution block consists of
10、one or more connectors mounted on an insulating base. Eachconnector has provision for one or more incoming conductors and multiple tap-off conductors. A tap-offconductor is of the same or smaller size as the incoming conductor. The connectors may be of the lay-inconstruction which do not require the
11、 incoming conductor to be terminated.1.3 A power distribution block is intended to permanently support and insulate the wire terminations andjoints of each polarity from each other, and from the surface on which the power distribution block ismounted. A power distribution block may also be provided
12、with an insulating cover.1.4 These requirements do not cover terminal blocks which are covered by the Standard for TerminalBlocks, UL 1059.2 Glossary2.1 The following definitions apply in this Outline of Investigation.2.2 POWER DISTRIBUTION BLOCK A rigidly mounted device consisting of an insulating
13、base withbarriers having one or more electrically isolated terminal assemblies. Each terminal assembly serves asa junction to electrically connect two or more conductors.2.3 CONNECTOR A device that establishes the connection between one or more conductors in thefield as specified in the National Ele
14、ctrical Code, NFPA 70.2.4 TERMINAL ASSEMBLY A single pole of the power distribution block consisting of one or moreconnectors.AUGUST 29, 2014 UL 1953 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL3 Units of Measurement3.1 The values given i
15、n SI (metric) units shall be normative except for AWG/kcmil conductor sizes. Anyother values are for information only.4 Updated References4.1 Any undated reference to a code or standard appearing in the requirements of this Outline ofInvestigation shall be interpreted as referring to the latest edit
16、ion of that code or standard.5 Components5.1 Except as indicated in 5.2, a component of a product covered by this Outline of Investigation shallcomply with the requirements for that component. See Appendix A for a list of standards coveringcomponents generally used in the products covered by this Ou
17、tline of Investigation.5.2 A component need not comply with a specific requirement that:a) Involves a feature or characteristic not needed in the application of the component in theproduct covered by this outline, orb) Is superseded by a requirement in this outline.5.3 A component shall be used in a
18、ccordance with its recognized rating established for the intendedconditions of use.5.4 Specific components are recognized as being incomplete in construction features or restricted inperformance capabilities. Such components are intended for use only under limited conditions, such ascertain temperat
19、ures not exceeding specified limits, and shall be used only under those specific conditionsfor which they have been recognized.CONSTRUCTION6 Materials6.1 Current-carrying parts6.1.1 A current-carrying part intended for use with copper wire shall be of copper or a copper alloy.6.1.2 A current-carryin
20、g part intended for use with aluminum wire shall be of aluminum, an aluminumalloy, copper, or a copper alloy and shall be coated with an electrically conductive coating such as tin thatinhibits oxidation and corrosion.AUGUST 29, 2014UL 19536UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUC
21、TION ORDISTRIBUTION WITHOUT PERMISSION FROM UL6.2 Insulation6.2.1 A polymeric material used as part of a power distribution block shall comply with requirements inthe Standard for Polymeric Materials Use in Electrical Equipment Evaluations, UL 746C.6.2.2 An insulating material used as direct or indi
22、rect support of an uninsulated live part rated greater than600 volts shall comply with 6.2.1 and the Inclined Plane Tracking Test specified in the Standard forPolymeric Materials Short Term Property Evaluations, UL 746A. The insulating material shall not trackbeyond one inch in less than 60 minutes
23、using the time to track method. The voltage for the Inclined PlaneTracking Test shall be not less than the rated voltage of the equipment6.2.3 A live screw head, rivet, or nut on the underside of a base intended for surface mounting shall becountersunk not less than 1/8 inch (3.2 mm) in the clear, a
24、nd covered to a depth of not less than 1/8 inchwith a waterproof, insulating, sealing compound that will not soften at a temperature of 90C (194F) asdetermined by the test for softening point by the ball pressure test in the Standard for Polymeric Materials Short Term Property Evaluations, UL 746A.E
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT19532014ULOUTLINEOFINVESTIGATIONFORPOWERDISTRIBUTIONBLOCKSISSUE5 配电 调查 大纲 议题 PDF

链接地址:http://www.mydoc123.com/p-1069202.html