UL 1449 CRD-2014 UL Standard for Safety Surge Protective Devices - Section Paragraph Reference 44 1 7 44 1 7 1 (new) Subject Cheesecloth proximity for conduit openings during Curr.pdf
《UL 1449 CRD-2014 UL Standard for Safety Surge Protective Devices - Section Paragraph Reference 44 1 7 44 1 7 1 (new) Subject Cheesecloth proximity for conduit openings during Curr.pdf》由会员分享,可在线阅读,更多相关《UL 1449 CRD-2014 UL Standard for Safety Surge Protective Devices - Section Paragraph Reference 44 1 7 44 1 7 1 (new) Subject Cheesecloth proximity for conduit openings during Curr.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): VZCA2Standard Number: UL 1449Standard Title: Standard for Surge Protective DevicesEdition Date: August 20, 2014Edition Number: 4Section / Paragraph Reference
3、: 1.1, Table 36.1, 79.1Subject: SPD Type 1 or 2CA with only N-G Protection Proposal that No SCCR isRequiredDECISION:1.1 These requirements cover Surge Protective Devices (SPDs) designed for repeated limiting of transientvoltage surges as specified in the standard on 50 or 60 Hz power circuits not ex
4、ceeding 1000 V anddesignated as follows:Type 1 - Permanently connected SPDs intended for installation between the secondary of theservice transformer and the line side of the service equipment overcurrent device, as well asthe load side, including watt-hour meter socket enclosures and Molded Case SP
5、Ds intended tobe installed without an external overcurrent protective device.Type 2 - Permanently connected SPDs intended for installation on the load side of the serviceequipment overcurrent device; including SPDs located at the branch panel and Molded CaseSPDs.Type 3 - Point of utilization SPDs, i
6、nstalled at a minimum conductor length of 10 meters (30feet) from the electrical service panel to the point of utilization, for example cord connected,direct plug-in, receptacle type and SPDs installed at the utilization equipment being protected.See marking in 80.3. The distance (10 meters) is excl
7、usive of conductors provided with or usedto attach SPDs.Type 4 Component Assemblies - Component assembly consisting of one or more Type 5components together with a disconnect (integral or external) or a means of complying with thelimited current tests in 44.4.Type 1, 2, 3 Component Assemblies - Cons
8、ists of a Type 4 component assembly with internalor external short circuit protection. Type 1 and Type 2 Component Assemblies for N-Gapplications only may not be provided with short circuit protection.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION F
9、ROM ULTable 36.1SPD Testing MatrixTest Section Reference SPD TypeType 1 Type 2 Type 3 Type 1, 2, 3ComponentAssembliesTemperature 39 A 2 Port A 2 Port A A 2 PortLeakage Current 37 NA NA A A for Type 3applicationDielectric VoltageWithstand38AAAASurge Test for VPR 40Nominal DischargeCurrent (In)40 A A
10、NAaA for Type 1 or 2applicationsOperating DutyCycle40 NA NA A A for Type 3application oraRepeat Surge Test 40 AAAAOperational voltage 43GroundingContinuity48 A A NA A for Type 1 or 2Current tests atshort circuit currentrating, intermediateand limited shortcircuit current levels44 A A A (No SCCR) A,
11、NA for Type 5SPDs. LimitedCurrent only forType 4 ComponentAssemblies. Shortcircuit, intermediateand limited for Type1, 2, 3 ComponentAssembliesbFault andOvercurrent Testsonly as required byException 2 of11.18 and 11.19 orby 21.3 or 21.4.49,50AAAAWithstand 51 A 2 Port A 2 Port NA A 2 Port, Type 1or 2
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL1449CRD2014ULSTANDARDFORSAFETYSURGEPROTECTIVEDEVICESSECTIONPARAGRAPHREFERENCE441744171NEWSUBJECTCHEESECLOTHPROXIMITYFORCONDUITOPENINGSDURINGCURRPDF

链接地址:http://www.mydoc123.com/p-1067487.html