ASTM E136-2012 2054 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750° C《750℃垂直管炉内材料性能的标准试验方法》.pdf
《ASTM E136-2012 2054 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750° C《750℃垂直管炉内材料性能的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E136-2012 2054 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750° C《750℃垂直管炉内材料性能的标准试验方法》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E136 12An American National StandardStandard Test Method forBehavior of Materials in a Vertical Tube Furnace at 750C1This standard is issued under the fixed designation E136; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revis
2、ion, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This fire-test-respo
3、nse test method covers the determi-nation under specified laboratory conditions of combustioncharacteristics of building materials.1.2 Limitations of this fire-test response test method areshown below.1.2.1 This test method does not apply to laminated or coatedmaterials.1.2.2 This test method is not
4、 suitable or satisfactory formaterials that soften, flow, melt, intumesce or otherwiseseparate from the measuring thermocouple.1.2.3 This test method does not provide a measure of anintrinsic property.1.2.4 This test method does not provide a quantitativemeasure of heat generation or combustibility;
5、 it simply servesas a test method with selected (end point) measures ofcombustibility.1.2.5 The test method does not measure the self-heatingtendencies of materials.1.2.6 In this test method materials are not being tested in thenature and form used in building applications. The test speci-men consis
6、ts of a small, specified volume that is either (1) cutfrom a thick sheet; (2) assembled from multiple thicknesses ofthin sheets; or (3) placed in a container if composed of granularpowder or loose-fiber materials.1.2.7 Results from this test method apply to the specific testapparatus and test condit
7、ions and are likely to vary whenchanges are made to one or more of the following: (1) the size,shape, and arrangement of the specimen; (2) the distribution oforganic content; (3) the exposure temperature; (4) the airsupply; (5) the location of thermocouples.1.3 This test method includes two options,
8、 both of whichuse a furnace to expose test specimens of building materials toa temperature of 750C (1382F).1.3.1 The furnace for the apparatus for Option A consists ofa ceramic tube containing an electric heating coil, and twoconcentric vertical refractory tubes.1.3.2 The furnace for the apparatus f
9、or Option B (TestMethod E2652) consists of an enclosed refractory tube sur-rounded by a heating coil with a cone-shaped airflow stabilizer.1.4 This test method references notes and footnotes thatprovide explanatory information. These notes and footnotes,excluding those in tables and figures, shall n
10、ot be considered asrequirements of this test method.1.5 The values stated in SI units are to be regarded asstandard. The values given in parentheses are for informationonly.1.6 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat andflame under cont
11、rolled conditions, but does not by itselfincorporate all factors required for fire-hazard or fire-riskassessment of the materials, products, or assemblies underactual fire conditions.1.7 Fire testing is inherently hazardous. Adequate safe-guards for personnel and property shall be employed inconduct
12、ing these tests.1.8 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use
13、.2. Referenced Documents2.1 ASTM Standards:2D1929 Test Method for Determining Ignition Temperatureof PlasticsD3174 Test Method for Ash in the Analysis Sample of Coaland Coke from CoalE84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE176 Terminology of Fire StandardsE2652 Test
14、Method for Behavior of Materials in a TubeFurnace with a Cone-shaped Airflow Stabilizer, at 750C2.2 ISO Standard:31This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.23 on Combustibil-ity.Current edition approved Aug
15、. 1, 2012. Published September 2012. Originallyapproved in 1958. Last previous edition approved in 2011 as E136 11. DOI:10.1520/E0136-12.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume i
16、nformation, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-29
17、59, United States.ISO 1182 Noncombustibility Test for Building MaterialsISO 13943 Fire Safety-Vocabulary2.3 Other Standard:BS 476 Combustibility Test of Materials33. Terminology3.1 DefinitionsFor definitions of terms found in this testmethod, refer to Terminology E176 and ISO 13943. In case ofconfli
18、ct, the definitions given in Terminology E176 shallprevail.4. Summary of Test Method4.1 This test method uses a furnace to expose buildingmaterials to a temperature of 750C (1382F) until failureoccurs or for at least 30 min.4.2 This test method offers the choice of two options:Option A (Sections 6 t
19、hrough 9) and Option B (Test MethodE2652).4.3 The furnace for Option A consists of two concentricvertical refractory tubes.4.4 The furnace for Option B (Test Method E2652) consistsof an enclosed refractory tube surrounded by a heating coilwith a cone-shaped airflow stabilizer.4.5 Thermocouples are u
20、sed to assess the temperature in-creases resulting from combustion of the building material.4.6 Visual observation is used to assess the occurrence offlaming.4.7 Section 15 is the report and acceptance criteria sectionfor this test method (both options).5. Significance and Use5.1 While actual buildi
21、ng fire exposure conditions are notduplicated, this test method will assist in indicating thosematerials which do not act to aid combustion or add appre-ciable heat to an ambient fire.5.2 Materials passing the test are permitted limited flamingand other indications of combustion.6. Apparatus for Opt
22、ion A6.1 The test apparatus shown in Fig. 1, shall be used forOption A and shall consist primarily of the following:6.1.1 Refractory TubesTwo concentric, refractory tubes,76 and 102 mm (3 and 4 in.) in inside diameter and 210 to 250mm (812 to 10 in.) in length, with axes vertical, and with heatappli
23、ed by electric heating coils outside of the larger tube. Acontrolled flow of air is admitted tangentially near the top ofthe annular space between the tubes and passes to the bottomof the inner tube. The outer tube rests on a refractory bottomand the inner tube rests on three spacer blocks so as to
24、afforda total opening under the inner tube equal to or greater than thatof the annular space. The refractory bottom plate has aremovable plug for cleaning.6.1.2 Transparent CoverA transparent cover of heat-resistant glass or other transparent material shall be providedNOTEInch-Pound Equivalentsin. 3
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME13620122054STANDARDTESTMETHODFORBEHAVIOROFMATERIALSINAVERTICALTUBEFURNACEAT750DEGC750 垂直 管炉内 材料

链接地址:http://www.mydoc123.com/p-526956.html