ASTM F2487-2006 Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Corrugated High Density Polyethylene Pipelines《已安装高密度聚乙烯波纹管道渗入和渗出验收测试用标准实施规程》.pdf
《ASTM F2487-2006 Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Corrugated High Density Polyethylene Pipelines《已安装高密度聚乙烯波纹管道渗入和渗出验收测试用标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM F2487-2006 Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Corrugated High Density Polyethylene Pipelines《已安装高密度聚乙烯波纹管道渗入和渗出验收测试用标准实施规程》.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F 2487 06Standard Practice forInfiltration and Exfiltration Acceptance Testing of InstalledCorrugated High Density Polyethylene Pipelines1, 2This standard is issued under the fixed designation F 2487; the number immediately following the designation indicates the year oforiginal adoptio
2、n or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Sc
3、ope1.1 This practice covers procedures for testing installednon-perforated, gasketed corrugated high-density polyethylene(HDPE) pipelines using either water infiltration or exfiltrationacceptance limits to demonstrate the integrity via the level ofleakage of the installed materials, construction pro
4、cedures andinstallation qualityvia the level of leakage. Pipe to be testedunder this practice shall include corrugated HDPE drainagepipe meeting the requirements of AASHTO M 252, AASHTOM 294 and Specification F 2306/F 2306M.NOTE 1The performance criteria specified in this standard may beused for oth
5、er plastic pipe products. The engineer, however, must assess ifthe testing procedures are adequate for the particular material andinstallation being considered.NOTE 2The user of this practice is advised that test criteria presentedin this practice are similar to those in general use. Pipe, 600-mm (2
6、4-in.)diameter or larger, may be accepted by visual inspection when testing forinfiltration.1.2 The values stated in SI units are to be regarded as thestandard. The values in parentheses are mathematical conver-sions to inch-pounds, which are provided for informationalpurposes only and are not consi
7、dered standard.1.3 This test method shall be performed on lines after allconnections and service laterals have been plugged and bracedadequately to withstand the test pressures. The time betweencompletion of the backfill operations and testing shall bespecified by the approving authority.1.4 This st
8、andard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. The testingrequired under
9、 this standard necessitates operating in confinedspaces. The user must insure that all OSHA and local safetycodes are duly observed.2. Referenced Documents2.1 ASTM Standards:3D 3212 Specification for Joints for Drain and Sewer PlasticPipes Using Flexible Elastomeric SealsF 412 Terminology Relating t
10、o Plastic Piping SystemsF 2306/F 2306M Specification for 12 to 60 in. 300 to 1500mm Annular Corrugated Profile-Wall Polyethylene (PE)Pipe and Fittings for Gravity-Flow Storm Sewer andSubsurface Drainage Applications2.2 AASHTO Standards2M 252 Standard Specification for Corrugated PolyethyleneDrainage
11、 Pipe 75 to 250-mm (3 to 10-inch) DiameterM 294 Standard Specification for Corrugated PolyethyleneDrainage Pipe 300 to 1500-mm (12 to 60-inch) Diameter3. Terminology3.1 DefinitionsFor definitions of terms relating to plasticpipe, see Terminology F 412.4. Summary of Practice4.1 Determine the groundwa
12、ter conditions surrounding thesection of pipeline to be tested and select the type of test to beconducted.4.2 For the infiltration test, the amount of water leaking intothe pipeline is measured, and the rate of infiltration is deter-mined. If the rate is less than or equal to the allowable limit, th
13、esection of pipe tested is acceptable.4.3 For the exfiltration test, the pipeline is filled with waterto the specified test head and the rate of water loss isdetermined. If the rate is less than or equal to the allowablelimit, the section of pipe tested is acceptable.5. Significance and Use5.1 This
14、is not a routine test. The values recorded areapplicable only to the pipe being tested and at the time oftesting.1This practice is under the jurisdiction of ASTM Committee F17 on PlasticPiping Systems and is the direct responsibility of Subcommittee F17.20 on Joining.Current edition approved Dec. 15
15、, 2006. Published January 2007.2Available from American Association of State Highway and TransportationOfficials (AASHTO), 444 N. Capitol St., NW, Suite 249, Washington, DC 20001,http:/www.transportation.org.3For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Custome
16、r Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.6. Preparation of the Pipeline6.1 The
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF24872006STANDARDPRACTICEFORINFILTRATIONANDEXFILTRATIONACCEPTANCETESTINGOFINSTALLEDCORRUGATEDHIGHDENSITYPOLYETHYLENEPIPELINES

链接地址:http://www.mydoc123.com/p-538829.html