ASTM D2156-2009(2013) Standard Test Method for Smoke Density in Flue Gases from Burning Distillate Fuels《燃料馏分燃烧产生烟道气中烟密度的标准试验方法》.pdf
《ASTM D2156-2009(2013) Standard Test Method for Smoke Density in Flue Gases from Burning Distillate Fuels《燃料馏分燃烧产生烟道气中烟密度的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D2156-2009(2013) Standard Test Method for Smoke Density in Flue Gases from Burning Distillate Fuels《燃料馏分燃烧产生烟道气中烟密度的标准试验方法》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D2156 09 (Reapproved 2013)Standard Test Method forSmoke Density in Flue Gases from Burning Distillate Fuels1This standard is issued under the fixed designation D2156; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the
2、 year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This test method covers the
3、evaluation of smoke densityin the flue gases from burning distillate fuels. It is intendedprimarily for use with home heating equipment burning kero-sine or heating oils. It can be used in the laboratory or in thefield to compare fuels for clean burning or to compare heatingequipment.1.2 The values
4、stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.2.1 Arbitrary and relative units are also used.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user
5、of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2E97 Test Method for Directional Reflectance Factor, 45-deg0-deg, of Opaque Specimens by Broad-Band Filter Re-flect
6、ometry33. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 smoke spot number, nthe number of the spot on thestandard scale most closely matching the color (or shade) of thetest spot.4. Summary of Test Method4.1 A test smoke spot is obtained by pulling a fixed volumeof flue gas thr
7、ough a fixed area of standard filter paper. Thecolor (or shade) of the spot thus produced is visually matchedwith a standard scale, and the smoke density is expressed as a“smoke spot number.”5. Significance and Use5.1 This test method provides a means of controlling smokeproduction in home heating e
8、quipment to an acceptable level.Excessive smoke density adversely affects efficiency by heat-exchanger fouling.5.2 The range of smoke densities covered by this testmethod is that which has been found particularly pertinent tohome-heating application. It is more sensitive to small amountsof smoke tha
9、n several other smoke tests as indicated in thefollowing comparison:Smoke SpotNumberIcham, percentTransmissionRingelmanSmoke Number0 100 0295480654818 0909 0 0to56. Apparatus6.1 Sampling DeviceA suitable device providing a totalflue gas sample volume of 36.9 6 1.65 L at 16C, 101 kPa foreach 645 mm2e
10、ffective surface area of filter paper shall beemployed. The sampling device and connections shall be ofsuch construction that the total travel of flue gas sample fromflue to filter paper shall not exceed 410 mm. The device shallprovide for cooling the sample below the charring temperaturefor the fil
11、ter paper but not below the dew point of the sample.Suitable laboratory and portable field service equipment isillustrated in Fig. 1 and Fig. 2.6.2 Smoke ScaleThe smoke scale required consists of tenspots numbered consecutively from 0 to 9, ranging in equalphotometric steps from white through neutra
12、l shades of gray toblack, imprinted or otherwise processed on white paper orplastic stock having a surface reflectance of between 82.5 and87.5 % 45, 0 daylight luminous directional reflectance inaccordance with Test Method E97. The smoke scale spotnumber is defined as the reduction (due to smoke) in
13、 reflectedincident light divided by 10. Thus, the first spot, which is the1This method is under the jurisdiction of ASTM Committee D02 on PetroleumProducts, Liquid Fuels, and Lubricants and is the direct responsibility of Subcom-mittee D02.E0 on Burner, Diesel, Non-Aviation Gas Turbine, and Marine F
14、uels.Current edition approved Oct. 1, 2013. Published October 2013. Originallyapproved in 1963. Last previous edition approved in 2009 as D2156 09. DOI:10.1520/D2156-09R13.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For An
15、nual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Withdrawn. The last approved version of this historical standard is referencedon www.astm.orgCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2
16、959. United States1color of the unimprinted scale, will be No. 0, since in the caseof this spot there will be no reduction in reflected incident lightdirected thereon. The last spot, however, is very dark, reflectingonly 10% of the incident light directed thereon; thus in thiscase the reduction in r
17、eflected incident light is 90 %, whichgives to this darkest spot the No. 9. Intermediate spot numbersare similarly established. Limits of permissible reflectancevariation of any smoke scale spot shall not exceed 63%relative reflectance (Note 1 and Note 2).NOTE 1Such smoke scales are sufficiently acc
18、urate for field use andfor many laboratory smoke testing applications. However, speciallycalibrated scales (known as certified smoke scales) will sometimes berequired. A certified smoke scale is obtained by individually calibratingeach smoke spot of a normal smoke scale.NOTE 2Where the smoke scale i
19、s protected with a plastic ortransparent cover the construction employed shall be such that when thesmoke spot on the filter paper is viewed for matching with the numberspots on the smoke scale, both shall be visible through the same thicknessand number of sheets of transparent protective cover.7. M
20、aterials7.1 Test Filter Paper, made from white filter paper stockhaving a surface reflectance of 82.5 to 87.5 % 45, 0 daylightluminous directional reflectance, in accordance with the TestMethod E97. When clean air at standard conditions is drawnthrough clean filter paper at a rate of 476 L/sm2effect
21、ivesurface area of filter paper, the pressure drop across the filterpaper falls between limits of 1.7 and 8.4 kPa.8. Procedure8.1 The sampling procedure used is critical. Therefore, theprocedure recommended by the equipment manufacturer shallbe rigidly followed.8.2 Use a clean, dry, sampling device.
22、 If a hand sampler isused, warm it above room temperature to prevent condensationon the filter paper. (This can usually be done conveniently byplacing the sampler on the boiler or furnace to be tested.)8.3 Insert filter paper in the sampler and tighten the filterpaper holder. Connect the sampling de
23、vice to the flue gasprobe. When taking smoke measurements in the flue pipe,position the end of the sampling probe at the center line of theflue pipe.8.4 Draw the required sample. When a hand sampler isused, permit the pressures in the flue gas stream and thesampler to equalize after each stroke.8.5
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD215620092013STANDARDTESTMETHODFORSMOKEDENSITYINFLUEGASESFROMBURNINGDISTILLATEFUELS 燃料 馏分 燃烧 产生 烟道

链接地址:http://www.mydoc123.com/p-511097.html