《ASTM C667-2001 Standard Specification for Prefabricated Reflective Insulation Systems for Equipment and Pipe Operating at Temperatures above Ambient Air《环境温度空气以上管道操作和设备的预制纤维反射绝缘的标准.pdf》由会员分享,可在线阅读,更多相关《ASTM C667-2001 Standard Specification for Prefabricated Reflective Insulation Systems for Equipment and Pipe Operating at Temperatures above Ambient Air《环境温度空气以上管道操作和设备的预制纤维反射绝缘的标准.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 667 01Standard Specification forPrefabricated Reflective Insulation Systems for Equipmentand Pipe Operating at Temperatures above Ambient Air1This standard is issued under the fixed designation C 667; the number immediately following the designation indicates the year oforiginal adopt
2、ion or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the requirements for all metalprefabricated, r
3、eflective insulation systems for equipment andpiping operating at temperatures above ambient in air. Typicalapplications are in nuclear power-generating plants and indus-trial plants.1.2 Reflective insulation is thermal insulation that reducesradiant heat transfer across spaces by the use of surface
4、s ofhigh reflectance and low emittance.1.3 The values stated in inch-pound units are to be regardedas the standard. The values given in parentheses are providedfor information only.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresp
5、onsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:C 168 Terminology Relating to Thermal Insulating Materi-als2C 335 Test Method for Steady-Sta
6、te Heat Transfer Proper-ties of Horizontal Pipe Insulation2C 411 Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation2C 835 Test Method for Total Hemispherical Emittance ofSurfaces from 20 to 1400C2C 854 Test for Resistance to External Loads on MetalReflective Pipe Insulati
7、on3C 1033 Test Method for Steady-State Heat Transfer Prop-erties of Pipe Insulation Installed Vertically2C 1061 Test Method for Thermal Transmission Propertiesof Non-Homogeneous Insulation Panels Installed Verti-cally43. Terminology3.1 Definitions:3.1.1 Terms relating to thermal insulation materials
8、 andtesting are in accordance with Terminology C 168.3.2 Definitions of Terms Specific to This Standard:3.2.1 convection stopsseals used to reduce convectionlosses.3.2.2 end supportsstructural members placed at the end ofa unit of insulation and fastened to both the inner and outercase. Their primar
9、y purpose is to increase the structuralintegrity of the unit.3.2.3 inner casethe innermost sheet of the unit of insula-tion (closest to the hot surface). It may perform structuralfunctions in addition to its thermal functions.3.2.4 insulation assemblyan assembly of insulation unitsarranged and secur
10、ed together in a prescribed order thatcomprises the complete insulation for a vessel, pump, pipeline,or other component for a single design objective.3.2.5 insulation systema collection of insulation assem-blies, that when secured together in a prescribed order, com-prises the complete insulation fo
11、r a vessel, pump, pipeline, orother component for a single design objective.3.2.6 lap strapsstrips that overlap a longitudinal or cir-cumferential joint in the insulation which aligns adjacentinsulation units and may also serve to restrict air infiltrationand convection losses and to shed external f
12、alling water. Theymay be integral with one piece of the outer case or separatestrips secured to it.3.2.7 outer casethe outermost sheet or the unit of insula-tion (farthest from the hot surface). It usually performsstructural functions in addition to its thermal functions.3.2.8 penetrationsopenings i
13、n a unit of insulation fromthe cold surface through to the hot surface.3.2.9 reflective linersthose reflective sheets or foil inter-posed between the inner and outer case to reflect radiantenergy, to minimize emission of radiant energy, and to restrictinternal convection.1This specification is under
14、 the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.21 onReflective Insulation.Current edition approved Nov. 10, 2001. Published December 2001. Originallypublished as C 667-92. last previous edition C 667-92 (1996)e1.2Annual Book of ASTM
15、Standards, Vol 04.06.3Discontinued. See 1997 Annual Book of ASTM Standard, Vol 04.06.4Discontinued. See 1994 Annual Book of ASTM Standard, Vol 04.06.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2.10 thickness(see Fig. 1).3.2.11
16、unit of insulationa single structurally independentassembly of inner case, outer case, reflective liners, and endsupports (if required).4. Ordering Information4.1 Ordering information should include the following:4.1.1 Service requirements including operating hot surfacetemperature, expected ambient
17、 temperatures, and ambient airvelocities,4.1.2 Expected service life and any special environmentalexposures,4.1.3 Permitted average heat loss per unit of cold surface oras otherwise specified,4.1.4 Personnel exposure surface temperature limitations,4.1.5 Expected seismic, loading, and vibration expo
18、sures,4.1.6 Purchasers systems and equipment drawings,4.1.7 Limits, if any, on size, maximum thickness, weight, ornumber of insulation units requiring removal for inspection,4.1.8 Location of components or maintenance, or both, andsystems requiring removal of units for inspections,4.1.9 Any unusual
19、operating or test conditions, and4.1.10 Cleanliness level required.5. Materials and Manufacture5.1 Each insulation unit is a rigid, self-contained, prefabri-cated metal construction comprised of an inner casing and anouter casing, and if needed, one or more reflective linerssupported and spaced so a
20、s to minimize internal convectionand conduction. These parts are arranged to form a durablerigid assembly with separated air spaces between the inner andouter casing and the individual reflective liners.5.2 The reflective insulation described herein is limited tosystems of insulating units, designed
21、 by the manufacturer to fitthe equipment or piping to be insulated, and engineered for thepurchasers service requirements.5.3 All parts of reflective insulation units should be made ofmetals that meet the thermal, physical, and chemical require-ments not only of the insulation as a unit, but also as
22、 anassembly of units forming the insulation system. The materialsshall perform their functions for the service life specified andbe compatible with the environment in which they will be used.6. Temperature Limitations6.1 Each insulation unit must effectively limit the flow ofheat through the insulat
23、ion by radiation, convection, andconduction. The reflective liners (also referred to as radiationshields) are made of metals having low surface emittance andhigh surface reflectance. The emittance should be testedaccording to Test Method C 835. The number and spacing ofthe liners are determined by t
24、he required limitation of heatflow.6.2 The temperature limits of various materials should bebased on the potential increase in radiant heat transfer acrossspaces due to a reduction in reflectance and a correspondingincrease in emittance resulting from surface oxidation. Indi-vidual components of the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC6672001STANDARDSPECIFICATIONFORPREFABRICATEDREFLECTIVEINSULATIONSYSTEMSFOREQUIPMENTANDPIPEOPERATINGATTEMPERATURESABOVEAMBIENTAIR

链接地址:http://www.mydoc123.com/p-507961.html