《ASTM C1290-2011 Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts《外部隔热HVAC管道用柔性纤维玻璃毡隔热材料的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1290-2011 Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts《外部隔热HVAC管道用柔性纤维玻璃毡隔热材料的标准规格》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1290 11Standard Specification forFlexible Fibrous Glass Blanket Insulation Used to ExternallyInsulate HVAC Ducts1This standard is issued under the fixed designation C1290; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revisio
2、n, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the composition, size, dimen-sions, and physical properties of flexible fiber
3、 glass blanket,ductwrap, used to externally insulate HVAC ducts used for thedistribution of condition air within the temperature range of35F (1.7C) and 250F (121C).1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to
4、SI units that are provided for information onlyand are not considered standard.1.3 When the installation and use of thermal insulationmaterials, accessories, and systems may pose safety and healthproblems, the manufacturer shall provide the user appropriatecurrent information regarding any known pro
5、blems associatedwith the recommended use of the companys products, andshall also recommend protective measures to be employed intheir safe utilization. The user shall establish appropriate safetyand health practices and determine the applicability of regula-tory requirements prior to use.1.4 The fol
6、lowing safety hazards caveat pertains only to thetest methods, Section 13, in this specification. This standarddoes not purport to address all of the safety concerns, if any,associated with its use. It is the responsibility of the user of thisstandard to establish appropriate safety and health pract
7、icesand determine the applicability of regulatory limitations priorto use.2. Referenced Documents2.1 ASTM Standards:2C167 Test Methods for Thickness and Density of Blanket orBatt Thermal InsulationsC168 Terminology Relating to Thermal InsulationC177 Test Method for Steady-State Heat Flux Measure-men
8、ts and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate ApparatusC390 Practice for Sampling and Acceptance of ThermalInsulation LotsC411 Test Method for Hot-Surface Performance of High-Temperature Thermal InsulationC518 Test Method for Steady-State Thermal TransmissionProperties by M
9、eans of the Heat Flow Meter ApparatusC665 Specification for Mineral-Fiber Blanket Thermal In-sulation for Light Frame Construction and ManufacturedHousingC1104/C1104M Test Method for Determining the WaterVapor Sorption of Unfaced Mineral Fiber InsulationC1136 Specification for Flexible, Low Permeanc
10、e VaporRetarders for Thermal InsulationC1045 Practice for Calculating Thermal Transmission Prop-erties Under Steady-State ConditionsC1304 Test Method for Assessing the Odor Emission ofThermal Insulation MaterialsC1338 Test Method for Determining Fungi Resistance ofInsulation Materials and FacingsE84
11、 Test Method for Surface Burning Characteristics ofBuilding MaterialsE96/E96M Test Methods for Water Vapor Transmission ofMaterialsE2231 Practice for Specimen Preparation and Mounting ofPipe and Duct Insulation Materials to Assess SurfaceBurning Characteristics2.2 Other Documents:CAN/ULC-S102 Standa
12、rd Method of Test for SurfaceBurning Characteristics of Building Materials and Assem-blies33. Terminology3.1 DefinitionsFor definitions of terms defined in thisspecification, see Terminology C168.4. Classification4.1 Fibrous glass flexible blanket HVAC duct externalinsulation consists of the followi
13、ng three types:4.1.1 Type IBlankets without facing.1This specification is under the jurisdiction of ASTM Committee C16 onTher-mal Insulation and is under the direct responsibility of Subcommittee C16.23 .Current edition approved April 1, 2011. Published May 2011. Originallyapproved in 1995. Last pre
14、vious edition approved in 2006 as C1290061. DOI:10.1520/C1290-11.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM webs
15、ite.3Available from Underwriters Laboratories (UL), 333 Pfingsten Rd., North-brook, IL 60062-2096, http:/.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.1.2 Type IIBlankets faced with a vapor-retarder facinghaving a water vapor pe
16、rmeance no higher than 1.0 Perm.4.1.3 Type IIIBlankets faced with a vapor-retarder facingwith a water vapor permeance no higher than 0.02 Perm thatmeet physical property requirements of Specification C1136.5. Ordering Information5.1 Specific installation, insulation type, thermal resistance,thicknes
17、s, length, and width suited for the intended use shall bespecified by the purchaser.6. Materials and Manufacture6.1 Basic Material The basic material shall be fibersmade from glass processed from the molten state into fibrousform.6.2 Manufacture Insulation shall consist of bonded fibersformed into f
18、lexible blanket rolls with or without variousadhered facings.7. Physical Properties7.1 Thermal ResistanceThe material shall be tested at theout of package thickness and at the installed thickness for thethermal resistance at 75F (24C) mean temperature in accor-dance with 13.2. The installed thermal
19、resistance shall be testedwith the material compressed to 75 % of the labeled out ofpackage thickness. For each case the tested thermal resistance,R, for the average of any four randomly selected samples, shallnot be more than 5% below the label R-Values, when tested inaccordance with 13.2 nor shall
20、 any single specimen be morethan 10 % below the label R-Values4.NOTE 1Consult the local or state building codes for the minimuminstalled thermal resistance, R-value, required to be installed.NOTE 2To obtain the measured installed R-value during installation,the duct wrap insulation shall be cut to a
21、 stretch-out as indicated in TableX1.1 in Appendix X1.7.2 Surface Burning CharacteristicsTypes I, II, and III,when tested in accordance with 13.3, shall have a flame spreadindex not greater than 25, and smoke developed index notgreater than 50.7.3 Hot Surface PerformanceInsulation shall not flame,gl
22、ow, or smolder when tested in accordance with 13.4 at 250F(121C).7.4 Water Vapor PermeanceWhen tested in accordancewith 13.5, the vapor-retarder facing of a Type III product shallhave a vapor permeance of no more than 0.02 Perm beforelaminating to fiber glass. The vaporretarder facing of the TypeII
23、product shall have a vapor permeance of no more than 1.0Perm before laminating to fiber glass.7.5 Water Vapor SorptionThe water vapor sorption of theinsulation blanket shall be not more than 5 % by weight, whentested in accordance with 13.6.7.6 Odor Emission A detectable odor of strong objection-abl
24、e nature recorded by more than two of the five panelmembers shall constitute rejection of the product when testedin accordance with 13.7.7.7 Corrosiveness When tested in accordance with 13.8,the steel plates in contact with the insulation shall show nocorrosion greater than that observed for compara
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC12902011STANDARDSPECIFICATIONFORFLEXIBLEFIBROUSGLASSBLANKETINSULATIONUSEDTOEXTERNALLYINSULATEHVACDUCTS

链接地址:http://www.mydoc123.com/p-464112.html