1、Designation: B496 13B496 13aStandard Specification forCompact Round Concentric-Lay-Stranded CopperConductors1This standard is issued under the fixed designation B496; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last
2、 revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers bare compact round concentric-lay-stranded conductors made from uncoated round copper wiresfor g
3、eneral use for electrical purposes. These conductors shall be constructed with a central core surrounded by one or more layersof helically laid compacted wires (Explanatory Note 1 and Note 2).1.2 The values stated in inch-pound or SI units are to be regarded separately as standard. The values given
4、in each system arenot exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systemsmay result in nonconformance with the specification.parentheses are mathematical conversions to SI units that are provided forinformation only and are not co
5、nsidered standard.1.2.1 For density, resistivity, and temperature, the values stated in SI units are to be regarded as standard.2. Referenced Documents2.1 The following documents of the issue in effect on date of material purchase form a part of this specification to the extentreferenced herein:2.2
6、ASTM Standards:2B3 Specification for Soft or Annealed Copper WireB263 Test Method for Determination of Cross-Sectional Area of Stranded ConductorsB354 Terminology Relating to Uninsulated Metallic Electrical Conductors3. Ordering Information3.1 Orders for material under this specification shall inclu
7、de the following information:3.1.1 Quantity of each size (Table 1),3.1.2 Conductor size; circular-mil area or AWG, (Section 6 and Table 1),3.1.3 Packaging (Section 15), if required,3.1.4 Special package marking, and3.1.5 Place of inspection (Section 14).4. Joints4.1 Welds and brazes may be made in r
8、ods or in wires prior to final drawing.4.2 Welds and brazes may be made in the individual round drawn wires for compact conductors, but shall not be closer togetherthan 1 ft (300 mm) for conductor of 19 wires or less or closer than 1 ft (300 mm) in a layer for conductor of more than 19 wires.4.3 No
9、joint nor splice shall be made in a compact-stranded conductor as a whole.5. Lay5.1 The lay length of every layerthe wires shall be not be less than 8 times nor more than 16 times the outside diameter of thecompleted conductor except that, for sizes 2 AWG finished conductor. The maximum length of la
10、y for compact conductors AWG1 This specification is under the jurisdiction of ASTM Committee B01 on Electrical Conductors and is the direct responsibility of Subcommittee B01.04 on Conductorsof Copper and Copper Alloys.Current edition approved April 1, 2013Oct. 1, 2013. Published April 2013October 2
11、013. Originally approved in 1969. Last previous edition approved in 20102013 asB496 10B496 13.1. DOI: 10.1520/B0496-13.10.1520/B0496-13A.2 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume in
12、formation, refer to the standards Document Summary page on the ASTM website.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately
13、 depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, P
14、A 19428-2959. United States12 (33.6 mm2) and smaller, the maximum lay length smaller shall be 17.5 times the outside diameter.diameter of that layer. Forconductors of 37 wires or more, this requirement shall apply to the wires of the outer two layers. The lay of the layers other thanthe outer two la
15、yers shall be at the option of the manufacturer, unless otherwise agreed upon.5.2 The direction of lay of the outer layer shall be left-hand, and it shall be reversed in successive layers, unidirectional, orunilay.6. Construction6.1 The construction of the compact round concentric-lay-stranded condu
16、ctors shall be as shown in Table 1.6.2 The starting round copper wires used in the fabrication of the compact round conductor shall be of such diameter as toproduce a finished conductor having a nominal cross-sectional area and diameter as prescribed in Table 1.7. Density7.1 For the purpose of calcu
17、lating linear densities, cross sections, and so forth, the density of the copper shall be taken as 8.89g/cm3 (0.32117 lb/in.3) at 20C.8. Mass and Resistance8.1 The mass per unit length and dc electrical resistance of a compact round conductor are greater than the total of thesecharacteristics of the
18、 compressed wires composing the finished conductor, depending upon the lay. The standard increment of massper unit length and electrical resistance shall be taken as 2 %. The nominal mass per unit length and dc resistance are shown inTable 1. When the dc resistance is measured at other than 20C, it
19、shall be corrected by using the multiplying factors given in Table2.8.2 In cases where the lay is definitely known, the increment may be calculated if desired (Explanatory Note 3).8.3 For conductors to be used in covered or insulated wires or cables, direct current (DC) resistance measurement may be
20、 usedinstead of the method outlined in Section 9, to determine compliance with this specification.9. Variation in Area9.1 The cross-sectional area of the compact round conductor shall be not less than 98 % of the cross-sectional area as specifiedin Column 1 of Table 1.9.2 The manufacturer shall dete
21、rmine the cross-sectional area by Test Method B263. In applying this method, the increment inmass per unit length resulting from stranding may be the applicable value specified in 9.1 or may be calculated from the measureddimensions of the sample under test. In case of question regarding area compli
22、ance, the actual mass per unit length increment dueto stranding shall be calculated.TABLE 1 Construction Requirements of Compact Round Concentric-Lay-Stranded Copper ConductorsConductor Size Number ofWiresCompact Conductor Diameter Mass,lb/1000 ftMass,kg/kmDC Resistance at 20Ccmil AWG mm2 in. mm /10
23、00 ft /km1 000 000 . 507 61A 1.060 26.9 3086 4590 0.0106 0.0347900 000 . 456 61A 0.999 25.4 2780 4140 0.0118 0.0386800 000 . 405 61A 0.938 23.8 2469 3680 0.0132 0.0433750 000 . 380 61A 0.908 23.0 2316 3450 0.0141 0.0462700 000 . 355 61A 0.877 22.3 2160 3220 0.0151 0.0495650 000 . 329 61A 0.845 21.4
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMB4962013ASTANDARDSPECIFICATIONFORCOMPACTROUNDCONCENTRICLAYSTRANDEDCOPPERCONDUCTORS 紧实 圆形 同心 纹绞合铜

链接地址:http://www.mydoc123.com/p-461392.html