《ASTM F2176-2002 Standard Specification for Mechanical Couplings Used on Polyethylene Conduit Duct and Innerduct《机械连接件用聚乙烯导管 排泄管和内部管道的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM F2176-2002 Standard Specification for Mechanical Couplings Used on Polyethylene Conduit Duct and Innerduct《机械连接件用聚乙烯导管 排泄管和内部管道的标准规范》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F 2176 02An American National StandardStandard Specification forMechanical Couplings Used on Polyethylene Conduit, Ductand Innerduct1This standard is issued under the fixed designation F 2176; the number immediately following the designation indicates the year oforiginal adoption or, in
2、 the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification establishes requirements for material,performance, workmanship
3、and test methods for the qualifica-tion of 2 in. and smaller mechanical couplings that connect toDR 15.5 and lower polyethylene conduit, duct and innerductcovered by Specification F 2160. Throughout this standard,“conduit” refers to “conduit, duct or innerduct” manufacturedin accordance with Specifi
4、cation F 2160.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units which are provided for informationonly and are not considered standard.1.3 The couplings covered by this specification are typicallydesigned
5、to join between conduit ends (in-line coupling). Thesame coupling-to-conduit joint design may be used as a part ofother coupling joint designs that telescope, or connect tobulkheads, or other adapter fitting designs. The requirements ofthis standard apply only to the coupling-to-conduit jointdesign.
6、 The performance requirements of other coupling jointdesigns are not a part of this standard.1.4 The following safety hazards caveat pertains only to thetest methods portion, Section 9 of this specification. Thisstandard does not purport to address all of the safety concerns,if any, associated with
7、its use. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices and determine the applicability of regulatory require-ments prior to use.2. Referenced Documents2.1 ASTM Standards:D 638 Test Methods for Tensile Properties of Plastics2D 1600 Terminolog
8、y Relating to Abbreviations, Acronymsand Codes for Terms Relating to Plastics2D 2444 Test Method for Impact Resistance of Thermoplas-tic Pipe and Fittings2F 412 Terminology Related to Plastic Piping Systems2F 2160 Specification for Solid Wall (PE) Conduit (DR)Based on Outside Diameter (OD)23. Termin
9、ology3.1 Definitions are in accordance with Terminology F 412and abbreviations are in accordance with Terminology D 1600,unless otherwise specified.3.2 Definitions of Terms Specific to This Standard:3.2.1 coupling joint, nthe connection between the cou-pling and a conduit end.3.2.2 duct, na conduit
10、(see Terminology F 412, conduit).3.2.3 inline mechanical couplings, na device used to jointwo conduit ends.3.2.4 innerduct, na conduit installed inside a conduit.4. Materials and Manufacture4.1 The physical properties of each material used to producemechanical couplings shall be available from the c
11、ouplingmanufacturer upon request.4.2 Specifications outlining all the physical properties andeffects of environmental conditions for materials of manufac-ture shall be available from the coupling manufacturer uponrequest.NOTE 1Materials should have a demonstrated resistance to environ-mental stress
12、cracking when exposed, under stress, to chemical com-pounds encountered in or external to conduit systems and a demonstratedresistance to bacteriological decomposition. Such compounds include, butare not limited to, alkalines, fertilizers, ice thawing chemicals, insecti-cides, herbicides, and acids.
13、5. Performance Requirements5.1 The following requirements shall be met on each cou-pling design and nominal size. Any revisions by the manufac-turer to the original coupling design after the initial qualifica-tion testing requires retesting to ensure conformance with theserequirements.NOTE 2It is pe
14、rmissible when accomplishing these tests to do so ononly the thickest and thinnest (lowest and highest DR) conduit wallsections in Specification F 2160 that the coupling is to be used on. If inthose tests all performance requirements are met, all wall thicknessesbetween those tested may be considere
15、d as having met the requirements.5.2 Pressure Requirements:1This specification is under the jurisdiction of ASTM Committee F17 on PlasticPiping Systems and is the direct responsibility of Subcommittee F17.10 on Fittings.Current edition approved April 10, 2002. Published June 2002.2Annual Book of AST
16、M Standards,Vol1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.5.2.1 Sustained Internal PressureThe coupling/conduitjoint shall not fail by leakage as described by and tested inaccordance with 9.1.5.2.2 Sustained External PressureThe
17、 coupling/conduitjoint shall not fail by leakage as described by and tested inaccordance with 9.2.5.3 Tensile Strength Requirements:5.3.1 Pullout ResistanceThe coupling/conduit joint as-semblies tested shall be able to comply with tensile loadingrequirements in Table 1 when tested in accordance with
18、 9.3.NOTE 3Minimum pullout resistances in Table 1 were derived by thefollowing formula. Double the requirements for constant tensile load inTable 2.5.4 Constant Tensile LoadThe joint or coupling shall notfail by pullout when loaded to axial tensile load requirementsin Table 2 and tested in accordanc
19、e with 9.4.NOTE 4The constant tensile load test is intended to demonstrate thata joint in the conduit system is resistant to the effects of long term creepthat may result from temperature changes and other forces after installa-tion. Load values in Table 2 were derived by the following methodology.N
20、ominal modulus of elasticity of high density polyethylene (113 000 psi)3 coefficient of thermal expansion (0.00011 in./in./F) 3 50F (10C)temperature change 3 average area of DR11 conduit wall.5.5 Impact ResistanceThe coupling shall not fail as de-fined by and tested in accordance with 9.5.6. Dimensi
21、ons6.1 The manufacturer, upon request of the user shall furnishcritical dimensions and tolerances of his couplings.NOTE 5Because of the varied fitting designs of couplings availablefor use on PE conduit a table of dimensions would be meaningless andwithout value and is therefore omitted from this st
22、andard.7. Workmanship, Finish and Appearance7.1 The manufacture of these couplings shall be in accor-dance with good commercial practice, uniform in color andfree of visual defects such as burrs, cracks, holes, foreignmaterials or voids so as to produce fittings meeting therequirements of this stand
23、ard.8. Specimen Preparation8.1 Conditioning:8.1.1 Unless otherwise specified, condition the specimens(coupling and conduit) at the standard laboratory temperatureof 73.4 6 3.6F (23 6 2C) for not less than 16 h beforeassembly.8.2 Preparation of Specimens for Testing:8.2.1 Prepare test specimens so th
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF21762002STANDARDSPECIFICATIONFORMECHANICALCOUPLINGSUSEDONPOLYETHYLENECONDUITDUCTANDINNERDUCT 机械

链接地址:http://www.mydoc123.com/p-537960.html