《ASTM F2045-2000(2006) Standard Specification for Indicators Sight Liquid Level Direct and Indirect Reading Tubular Glass Plastic《直接和间接读取液位的管形玻璃和塑料观测指示器标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM F2045-2000(2006) Standard Specification for Indicators Sight Liquid Level Direct and Indirect Reading Tubular Glass Plastic《直接和间接读取液位的管形玻璃和塑料观测指示器标准规范》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F 2045 00 (Reapproved 2006)An American National StandardStandard Specification forIndicators, Sight, Liquid Level, Direct and Indirect Reading,Tubular Glass/Plastic1This standard is issued under the fixed designation F 2045; the number immediately following the designation indicates the
2、 year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the requirements for dir
3、ect andindirect reading sight liquid level indicators for general appli-cations. General applications for indirect reading sight glassesare water and fuel service at working pressures 2.07 MPa (300lb/in.2) and below, temperatures of 149C (300F) and below.General applications for direct reading sight
4、 glasses are appli-cations in which the temperature does not exceed 66C(150F).1.2 Direct reading sight glass indicators may consist of glassor plastic tubes with fittings including shutoff valves. Glasstubes may be used for low shock direct reading sight glassindicators in which the fluid is not com
5、patible with plastic.1.3 Indirect reading indicators may consist of a sealedchamber with a magnetic float or flag indicator.1.4 Special requirements for naval shipboard applicationsare included in the supplement to this standard.1.5 The values stated in SI units are to be regarded as thestandard. Th
6、e values given in parentheses are for informationonly.2. Referenced Documents2.1 ASTM Standards:2D 3951 Practice for Commercial Packaging2.2 ANSI Standards:B16.5 Pipe Flanges and Flanged Fittings (DoD adopted)33. Terminology3.1 Definitions:3.1.1 SI (Le Systeme International dUnites) Unitsunits ofmea
7、surement recognized by the CIPM (Comite Internationaldes Poids et Mesures).4. Design Classification4.1 TypesIndicator designs are classified as either directreading or indirect reading. Both types are depicted in Fig. 1,complete with dimensions that facilitate ordering.4.2 Special ConsiderationsSpec
8、ial considerations thatmay affect selection and installation are listed below. This isnot to be construed as a complete listing.(1) Type of indicator,(2) Manual or automatic shutoff valves,(3) Indication length of liquid level range,(4) Method of connection,(5) Location of indicator relative to vibr
9、ating equipment,(6) Protection of the instrumentation,(7) Application of each indicator,(8) Cleaning procedure or reference to the cleaning proce-dure being used, and(9) Selection of indicator for compatibility with materials,temperature, pressure, ambient environment, and with theparameter being me
10、asured.5. Ordering Information5.1 The buyer shall provide the manufacturer with all of thepertinent application data outlined in the acquisition require-ments.5.2 Acquisition RequirementsAcquisition documentsshall specify the following:(1) Title, number, and date of this specification;(2) Type and q
11、uantity of indicators required;(3) Manufacturers part number;(4) When qualification testing is required;(5) Final disposition of qualification test samples;(6) Environmental requirements;(7) Operating media;(8) Viscosity and specific gravity of fluid for indirectindicators;(9) Materials;(10) Indicat
12、ion length;(11) Size and type of connections;(12) Shutoff valve requirements;(13) Cleaning requirements;(14) When certification is required;(15) Marking requirements;1This specification is under the jurisdiction of ASTM Committee F25 on Shipsand Marine Technology and is the direct responsibility of
13、Subcommittee F25.10 onElectrical.Current edition approved Feb. 1, 2006. Published February 2006. Originallyapproved in 2000. Last previous edition approved in 2000 as F 2045 00.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. F
14、or Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Consh
15、ohocken, PA 19428-2959, United States.(16) Unique packaging requirements; and(17) Unique preservation requirements.6. Materials and Manufacture6.1 MaterialsThe materials for all wetted parts shall beselected for long-term compatibility with the process mediumand ambient conditions.6.2 Material Inspe
16、ctionThe manufacturer shall be respon-sible for ensuring that materials used are manufactured, exam-ined, and tested in accordance with the specifications andstandards as applicable.6.3 Gaskets and O-RingsGaskets and O-rings shall befabricated of materials suitable to the operating pressure,temperat
17、ure, and process medium for each application.7. Physical Properties7.1 ConnectionsSight indicators are usually installed us-ing standard pipe fittings or flanges. Pipe fittings and materialshould match that of the existing pipe for each installation.Type and size of fittings shall be specified in th
18、e acquisitionrequirements. Welding or brazing shall be performed in accor-dance with industry standards.7.2 Flanged ConnectionsWhere sight indicators are in-stalled using flanges, flanges shall be in accordance with ANSIB16.5. Standard flange sizes include 1.27 cm (12 in.), 1.9 cm(34 in.), 2.54 cm (
19、1 in.), 3.8 cm (1-12 in.), and 5.08 cm (2 in.).Standard flange pressure ratings include 1.034 MPa (150 psi),2.07 MPa (300 psi), and 4.14 MPa (600 psi). Other flangerequirements shall be specified in the acquisition requirements.7.3 Vent and Drain ConnectionsWhere required, vent anddrain connections
20、are usually plugged,12-or34-in. NPT orwith NPT valves. Other vent and drain connections shall bespecified in the acquisition requirements.8. Performance Requirements8.1 Performance ConsiderationsIn many applications,certain performance characteristics are deemed critical to theintended or desired fu
21、nction of a sight liquid level indicator.The following are prime examples:(1) Accuracy,FIG. 1 Indicator Design TypesF 2045 00 (2006)2(2) Shock and vibration classifications, and(3) Operating pressure and temperature ranges.9. Workmanship, Finish, and Appearance9.1 Finish and AppearanceAny special su
22、rface finish andappearance requirements shall be specified in the acquisitionrequirements.9.2 Sight Glass CleaningAny special cleaning require-ments shall be specified in the acquisition requirements.10. Inspection10.1 Classification of InspectionsThe inspection require-ments specified herein are cl
23、assified as follows:(1) Qualification testing and(2) Quality conformance testing.10.2 Qualification TestingQualification test requirementsshall be specified where applicable. Qualification test methodsshould be identified for each design and performance charac-teristic specified. Test report documen
24、tation requirementsshould also be specified.10.3 Quality Conformance TestingQuality conformancetesting is accomplished when qualification testing was satisfiedby a previous acquisition or product has demonstrated reliabil-ity in similar applications. Quality conformance testing isusually less intens
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF204520002006STANDARDSPECIFICATIONFORINDICATORSSIGHTLIQUIDLEVELDIRECTANDINDIRECTREADINGTUBULARGLASSPLASTIC

链接地址:http://www.mydoc123.com/p-536384.html