《ASTM F25-2004 Standard Test Method for Sizing and Counting Airborne Particulate Contamination in Cleanrooms and Other Dust-Controlled Areas《洁净室及其它防尘区域空气中粒状杂质的测量和计数的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM F25-2004 Standard Test Method for Sizing and Counting Airborne Particulate Contamination in Cleanrooms and Other Dust-Controlled Areas《洁净室及其它防尘区域空气中粒状杂质的测量和计数的标准试验方法》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F 25 04Standard Test Method forSizing and Counting Airborne Particulate Contamination inCleanrooms and Other Dust-Controlled Areas1This standard is issued under the fixed designation F 25; the number immediately following the designation indicates the year of originaladoption or, in the
2、 case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A superscriptepsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers counting and sizing airborneparticulate matter 5 m and larger
3、(macroparticles). Thesampling areas are specifically those with contamination levelstypical of cleanrooms and dust-controlled areas.1.2 The values stated in SI units are to be regarded as thestandard. The values given in parentheses are for informationonly.1.3 This standard does not purport to addre
4、ss all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory requirements prior to use.2. Referenced Documents2.1 ASTM Standards:2F50 Practice f
5、or Continuous Sizing and Counting of Air-borne Particles in Dust-Controlled Areas and Clean RoomsUsing Instruments Capable of Detecting Single Sub-Micrometre and Larger Particles2.2 ISO Standard:ISO 14644-1 Cleanrooms and Associated ControlledEnvironmentsPart 1: Classification of Air Cleanliness32.3
6、 IEST Document:IEST-G-CC1003 Measurement of Airborne Macroparticles(1999)42.4 SAE Document:SAE AbstractARP-743, Procedure for the Determination ofParticulate Contamination of Air in Dust-ControlledSpaces by Particle Count Method, August 196253. Terminology3.1 Definitions:3.1.1 airflow:3.1.1.1 unidir
7、ectional airflowair flow which has a singu-lar direction of flow and may or may not contain uniformvelocities of air flow along parallel lines.NOTE 1Formerly known as laminar airflow.3.1.1.2 non-unidirectional airflowair distribution wherethe supply air entering the room mixes with the internal air
8、bymeans of induction.3.1.2 critical pressurefor an orifice, with a constant up-stream pressure, the downstream pressure at which the flowwill not increase when the downstream pressure decreases.3.1.3 critical pressure ratiothe ratio of the critical pres-sure of an orifice to the entrance pressure.3.
9、1.4 customerorganization, or the agent thereof, respon-sible for specifying the requirements of a cleanroom or cleanzone.3.1.5 fiberparticle having an aspect (length-to-width) ra-tio of 10 or more.3.1.6 macroparticleparticle with an equivalent diametergreater than 5 m.3.1.7 M descriptormeasured or s
10、pecified concentration ofmacroparticles per cubic metre of air, expressed in terms of theequivalent diameter that is characteristic of the measurementmethod used.3.1.7.1 DiscussionThe M descriptor may be regarded asan upper limit for the averages at sampling locations (or as anupper confidence limit
11、, depending upon the number of sam-pling locations used to characterize the cleanroom or cleanzone). M descriptors cannot be used to define airborne particu-late cleanliness classes, but they may be quoted independentlyor in conjunction with airborne particulate cleanliness classes.1This test method
12、 is under the jurisdiction of ASTM Committee E21 on SpaceSimulation and Applications of Space Technology and is the direct responsibility ofSubcommittee E21.05 on Contamination.Current edition approved Sept. 1, 2004. Published September 2004. Originallyapproved in 1963. Last previous edition approve
13、d in 1999 as F 25 68 (1999).2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National
14、 Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036.4Available from Institute of Environmental Sciences and Technology (IEST),5005 Newport Dr., Suite 506, Rolling Meadows, IL 60008-3841.5Available from Society of Automotive Engineers (SAE), 400 CommonwealthDr., Warrendale, PA 1
15、5096-0001.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.1.8 occupancy states:3.1.8.1 as-builtcondition where the installation is com-plete with all services connected and functioning but with noadditional equipment, materials, or
16、 personnel present.3.1.8.2 at-restcondition where the installation is completewith equipment installed and operating in a manner agreedupon by the customer and supplier, but with no personnelpresent.3.1.8.3 operationalcondition where the installation isfunctioning in the specified manner, with the s
17、pecified numberof personnel present and working in the manner agreed upon.3.1.9 particle sizemajor projected dimension of the par-ticle.4. Summary of Test Method4.1 The test method is based on the microscopical exami-nation of particles impinged upon a membrane filter with theaid of a vacuum. The nu
18、mber of sampling points is propor-tional to the floor area of the enclosure to be checked. Theapparatus and facilities required are typical of a laboratory forthe study of macroparticle contamination. The operator musthave adequate basic training in microscopy and the techniquesof particle sizing an
19、d counting.5. Apparatus5.1 Filter Holder,6aerosol open type having an effectivefiltering area of 960 6 25 mm2.5.2 Adapter.75.3 Flow-Limiting Orifice,810 L/min.5.4 Membrane Filters,9black, 0.80-m mean pore size,47-mm diameter, with imprinted grid squares having sides 3.106 0.08 mm. Pressure drop acro
20、ss the filter used shall be nogreater than 50 torr for an air flow rate of 1 L/mincm2.5.5 Forceps, with unserrated tips.5.6 Vacuum Pump, capable of producing a pressure of 34kPa (260 torr) (vacuum of 500 torr) downstream of the orificeat a flow rate of 10 L/min through the orifice.5.7 Flowmeter, cal
21、ibrated and having a capacity in excess of10 L/min.5.8 Glass Microscope Slides, 50 mm by 75 mm, or 47-mmplastic disposable petri dishes.5.9 Binocular Microscope, (Fig. 1) with ocular-objectivecombinations to obtain 40 to 453 and 90 to 1503 magnifica-tions. Latter objective shall have numerical apert
22、ure of 0.15min.5.10 Normal Counter,10(2 gang) or equivalent.5.11 Microscope Lamp, 6 V, 5 A, high-intensity.5.12 Ocular Micrometer Scale, 5-mm linear scale with 100divisions.5.13 Stage Micrometer, standard 0.01-mm to 0.1-mm scale.6The sole source of supply of the apparatus known to the committee at t
23、his timeis 47 mm Stainless Steel, Millipore XX5004710, available from Millipore Corpo-ration, 290 Concord Rd., Billerica, MA 01821. If you are aware of alternativesuppliers, please provide this information to ASTM International Headquarters.Your comments will receive careful consideration at a meeti
24、ng of the responsibletechnical committee,1which you may attend.7The sole source of supply of the apparatus known to the committee at this timeis Luer slip to14 in. -38 in. ID hose Stainless Steel, XX6200004, available fromMillipore Corporation, 290 Concord Rd., Billerica, MA 01821. If you are aware
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF252004STANDARDTESTMETHODFORSIZINGANDCOUNTINGAIRBORNEPARTICULATECONTAMINATIONINCLEANROOMSANDOTHERDUSTCONTROLLEDAREAS

链接地址:http://www.mydoc123.com/p-532521.html