《ASTM D1988-2006(2015) Standard Test Method for Mercaptans in Natural Gas Using Length-of-Stain Detector Tubes《使用色斑长度检测管测定天然气中的硫醇的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D1988-2006(2015) Standard Test Method for Mercaptans in Natural Gas Using Length-of-Stain Detector Tubes《使用色斑长度检测管测定天然气中的硫醇的标准试验方法》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D1988 06 (Reapproved 2015)Standard Test Method forMercaptans in Natural Gas Using Length-of-Stain DetectorTubes1This standard is issued under the fixed designation D1988; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision,
2、 the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers a rapid and simple field deter-mination of mercaptans in natural gas pipelines. A
3、vailabledetector tubes provide a total measuring range of 0.5 to 160ppm by volume of mercaptans, although the majority ofapplications will be on the lower end of this range (that is,under 20 ppm). Besides total mercaptans, detector tubes arealso available for methyl mercaptan (0.5 to 100 ppm), ethyl
4、mercaptan (0.5 to 120 ppm), and butyl mercaptan (0.5 to 30mg/M3or 0.1 to 8 ppm).NOTE 1Certain detector tubes are calibrated in terms of milligramsper cubic metre (mg/M3) instead of parts per million by volume. Theconversion is as follows for 25C (77F) and 760 mm Hg.mg/M35ppm 3molecular weight24.45(1
5、)1.2 Detector tubes are usually subject to interferences fromgases and vapors other than the target substance. Such inter-ferences may vary among brands because of the use of differentdetection principles. Many detector tubes will have a pre-cleanse layer designed to remove interferences up to somem
6、aximum level. Consult manufacturers instructions for spe-cific interference information. Hydrogen sulfide and othermercaptans are usually interferences on mercaptan detectortubes. See Section 5 for interferences of various methods ofdetection.1.3 This standard does not purport to address all of thes
7、afety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For specific hazardstatements, see 7.3.2. Referenced Documents2.1 Gas P
8、rocessors Association Standard:GPA Standard 2188 Tentative Method for the Determinationof Ethyl Mercaptan in LP Gas Using Length-of-StainDetector Tubes, Appendix B, Test for Ethyl MercaptanOdourant in Propane, Field Method, 198823. Summary of Test Method3.1 The sample is passed through a detector tu
9、be filled witha specially prepared chemical. Any mercaptan present in thesample reacts with the chemical to produce a color change, orstain. The length of the stain produced in the detector tube,when exposed to a measured volume of sample, is directlyproportional to the amount of mercaptan present i
10、n the sample.A hand-operated piston or bellows-type pump is used to drawa measured volume of sample through the tube at a controlledrate of flow. The length of stain produced is converted to partsper million (ppm) by volume mercaptan by comparison to acalibration scale supplied by the manufacturer f
11、or each box ofdetection tubes. The system is direct reading, easily portable,and completely suited to making rapid spot checks for mer-captans under field conditions (see Note 1).4. Significance and Use4.1 The measurement of mercaptans in natural gas isimportant, because mercaptans are often added a
12、s odorants tonatural gas to provide a warning property. The odor providedby the mercaptan serves to warn consumers (for example,residential use) of natural gas leaks at levels that are well belowthe flammable or suffocating concentration levels of natural gasin air. Field determinations of mercaptan
13、s in natural gas areimportant because of the tendency of the mercaptan concen-tration to fade over time.4.2 This test method provides inexpensive field screening ofmercaptans. The system design is such that it may be used bynontechnical personnel, with a minimum of proper training.5. Interferences5.
14、1 Interference from hydrogen sulfide gas (H2S) is acommon problem with mercaptan detector tubes and its extentshould be understood to make use of tube readings. There areat least three detection principles used in mercaptan detectortubes and each is summarized below.1This test method is under the ju
15、risdiction ofASTM Committee D03 on GaseousFuels and is the direct responsibility of Subcommittee D03.07 on Analysis ofChemical Composition of Gaseous Fuels.Current edition approved Nov. 1, 2015. Published December 2015. Originallyapproved in 1991. Last previous edition approved in 2011 as D1988 06 (
16、2011).DOI: 10.1520/D1988-06R15.2Available from Gas ProcessorsAssociation, 6526 E. 60th St., Tulsa, OK 74145.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States15.1.1 Palladium sulfate is used by at least one manufacturer.It has a positive
17、 interference from H2S, but H2S may beremoved in a preconditioning layer at the front of the tube. Ifthis is the case, the manufacturer will state some finite level ofH2S at which interference initiates (for example, greater than500-ppm H2S causes a positive error). Consult manufacturersinstruction
18、sheets for this information. Propylene and hydro-carbons of five or more carbon atoms will cause interferingdiscolorations making the palladium sulfate detection principleineffective for liquefied petroleum gas (LPG). (Palladiumchloride is used by at least one manufacturer, and it exhibitssimilar H2
19、S interference as with the palladium sulfate detectionprinciple. Palladium chloride may also exhibit the hydrocarboninterference described for the palladium sulfate detectionprinciple. Contact the manufacturer for specific interferenceinformation.)5.1.2 Mercuric chloride is used by at least one manu
20、facturer.It has a positive interference from H2S but does not have thehydrocarbon interference described above for palladium sul-fate. This detection principle is preferred for LPG applications.H2S will produce a stain on mercuric chloride tubes even ifmercaptans are not present. The approximate H2S
21、 sensitivityratio is as follows: One part per million H2S will produce areading of 0.4- to 0.7-ppm mercaptans. Consult manufacturersfor exact information if it does not appear in tube instructionsheets.5.1.3 A two-stage copper salt/sulfur reaction is used by atleast one manufacturer. This detection
22、principle has a positiveinterference from H2S with H2S being twice as sensitive (thatis, 10-ppm H2S will appear as 20-ppm mercaptan). Ammoniaor amines also interfere with this principle producing a secondcolor.6. Apparatus6.1 Length-of-Stain Detector TubeA sealed glass tubewith breakoff tips sized t
23、o fit the tube holder of the pump. Thereagent layer inside the tube, typically a silica gel substratecoated with the active chemicals, must be specific to mercap-tans and produce a distinct color change when exposed to asample of gas containing mercaptans. Any substances knownto interfere must be li
24、sted in the instructions accompanying thetubes. A calibration scale printed on the glass tube shallcorrelate mercaptan concentration to the length of the colorstain. A separate calibration scale supplied with the tubes shallbe acceptable. Shelf life of the detector tubes must be aminimum of two year
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD198820062015STANDARDTESTMETHODFORMERCAPTANSINNATURALGASUSINGLENGTHOFSTAINDETECTORTUBES 使用 长度 检测

链接地址:http://www.mydoc123.com/p-510791.html