1、 INCH-POUND A-A-59534 January 12,2000 COMMERCIAL ITEM DESCRIPTION RECLAIMER, REFRIGERANT The General Services Administration has authorized the use of this commercial item description by all federal agencies. 1. SCOPE. This Commercial Item Description (CID) covers the general requirements for a port
2、able refrigerant reclaimer (FR) recovery and recycling center. The FR will be used to recover and recycle refrigerants such as R-12, R-22, R-500 and F-502. The FR is frame mounted with casters, fan cooled electrically driven reciprocating compressor, and has its own oil separator. 2. SALIENT CHARACT
3、RERISTICS. 2.1 Method of operation. The FR shall be capable of recovering and recycling refrigerant simultaneously. Recovery and recycling shall be completed in 10 to 15 minutes as compared to a minimum of 30 minutes using multi-pass systems. Automatic shutdown at the end of the operation shall be p
4、rovided in order to minimize monitoring of the system. A single air and oil purge valve shall be provided for operation. A digital panel-mounted gauge shall conduct monitoring of the air conditioning system and tank pressure. 2.2 Dimensions and weight. The FR shall be within the following dimensiona
5、l characteristics and weight limitations: a. Length: maximum 18 inches b. Width: maximum 16 inches c. Height: maximum 45 inches. d. Weight: maximum 120 pounds. Beneficial comments, recommendations, additions, deletions, clarifications, etc. and any data which may improve this document should be sent
6、 to: The Technology & Industrial Services Division, SA-ALCTILDD, 485 Quentin Roosevelt Rd., Kelly AFB, TX 78241-6425. AMSC NIA FSC 4940 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59534 2.3 Multiple refrigerant. The FR shall be capable of rec
7、overing and resettling R-12, R-22, R-500 and R-502 using only one unit. 2.4 Tank. The FR shall be provided with a size of tank having the refrigerant capacity 50 pounds. This tank shall meet the Department of Transportation (DOT) specifications. 2.5 Filter(s). The FR filters shall be of the replacab
8、le core style for ease of maintainance. 2.6 Liquid level sensor. The FR shall have the ability of determining when the refrigerant tank is at full capacity condition. When detecting this full condition indicator light(s) shall illuminate and the FR shall automatically shutdown. 2.7 Noise. The FR noi
9、se level during any operating condition shall be maximum 90 dbA slow scale. This level shall be measured at a maximum three feet from the perimeter of the FR. 2.8 Electrical power requirements. The FR shall be capable of operation from a 1 lOV, 5 amps, 50/60 Hz, and 1 phase source. 2.9 Maintainabili
10、ty. The manufacturer of the FR shall make available parts to provide basic purifier maintenance. Parts requiring routine replacement shall be accessible by maintenance personnel without disassembling the FR. 2.10 Spare parts. Each FR shall be provided with the following minimum of additional compone
11、nts: one 50 lb. refillable tank, five filter cores, and one oil measuring cup. If more than the quantity of these components are required, this quantity shall be identified in 6.1. A storage compartment for the spare parts shall be provided within the FR cabinet. 2.11 Data plate. A corrosion resista
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
2000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AIRFORCEAA595342000RECLAIMERREFRIGERANT 冷煤堆取料 PDF

链接地址:http://www.mydoc123.com/p-427110.html