FORD EW3-1992 POWER SOURCES FOR EQUIPMENT - LIGHTING AND ACCESSORIES《设备的照明和附属装置用电源》.pdf
《FORD EW3-1992 POWER SOURCES FOR EQUIPMENT - LIGHTING AND ACCESSORIES《设备的照明和附属装置用电源》.pdf》由会员分享,可在线阅读,更多相关《FORD EW3-1992 POWER SOURCES FOR EQUIPMENT - LIGHTING AND ACCESSORIES《设备的照明和附属装置用电源》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、 Manufacturing StandardsFord Motor Company199212 POWER SOURCES FOR EQUIPMENT - LIGHTING EW3AND ACCESSORIESEngineering Standards & Printed copies are uncontrolled.Systems Engineering (ESSE) Page 1 of 31. SCOPE:1.1 This standard describes acceptable 120 VAC power sources, commonlyreferred to as Lighti
2、ng Transformer Disconnects (LTDs) forauxiliary electrical apparatus which is part of production machinesand industrial equipment. Examples of auxiliary apparatus include,but are not limited to, work lights on machine or other industrialequipment, lights within the main electrical control enclosure,
3、anisolated power source for programmable controllers and relatedaccessories, and instrumentation.1.2 GENERAL:1.2.1 Wiring of lighting circuits and other details shall conform tosection E10.2 as specified in Ford Manufacturing Standard EX1.1.2.2 Fuses specified in paragraph 2.1 shall be sized for the
4、transformer furnished. See Table 4-5 in Standard EX1.2. LIGHTING SYSTEM SOURCES:2.1 BASIC REQUIREMENTS: The 120 VAC power source for the lamp or lampsand receptacle(s) in the control enclosure and/or on the industrialequipment, shall be obtained from a 480/120 volt transformer. Thepower for the tran
5、sformer shall be taken from the LINE side of themain disconnecting means on the control panel. A two-pole disconnectswitch shall interrupt the primary winding of the transformer, andshall be capable of being locked ONLY in the OFF position, usinglocks described in Ford Standard ES20. Escutcheon plat
6、es or othersuitable means shall be provided to clearly indicate the positionsof the operating handle, with the words “OFF“ and “ON“ in 1/2-inchhigh letters with an Arrow in the Off direction as a minimum.Overcurrent protection shall be provided in both primary leads withtype ATM or FNQ fuses or equa
7、l, and in one secondary lead with a250V, type FNA or equal, dual element fuse. The other secondary leadshall be grounded in an approved manner.2.2 ASSEMBLY: The transformer, disconnect switch, fuses, and allterminals shall be mounted in a NEMA Type 1 enclosure with hingeddoor or in a NEMA 12 enclosu
8、re for externally mounted LTDs. Thedoor swing shall be to the left and not exceed 90 degrees. A yellowplate with black lettering shall be affixed to the door which reads:CAUTION: WIRED TO LINE SIDE OF MAIN DISCONNECT. The plate shallconform to Standard EX1, 2.12.1. The disconnect switch shall bemech
9、anically interlocked with the door of the LTD enclosure, so thedoor cannot be opened with the switch in the “ON“ position. Damageshall not occur to the disconnect switch or its handle mechanism ifthe door is swung shut with the switch inadvertently moved to the“On“ position. The terminals on the lin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- FORDEW31992POWERSOURCESFOREQUIPMENTLIGHTINGANDACCESSORIES 设备 照明 附属 装置 用电 PDF

链接地址:http://www.mydoc123.com/p-746699.html