ASTM E2816-2013a Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf
《ASTM E2816-2013a Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2816-2013a Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf(22页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2816 13a An American National StandardStandard Test Methods forFire Resistive Metallic HVAC Duct Systems1This standard is issued under the fixed designation E2816; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the y
2、ear of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONHeating, Ventilation, Air Conditioning (HVAC) duct systems may be subjected to fire- exposureconditions. ISO 69
3、44 is a standard test method used to evaluate ventilation ducts. However, ISO 6944does not address all of the fire resistive attributes deemed necessary by some authorities havingjurisdiction, for example, (1) the fire-resistive, combustibility, flame spread and smoke generation, anddurability prope
4、rties of the fire-resistive materials protecting the HVAC duct, (2) the transition fromthe horizontal to a vertical HVAC duct, (3) the attachment of the HVAC ducts supports to thefire-separating elements, (4) the termination of an HVAC duct system and the protection of its ends,(5) the effects of ra
5、pid cooling and erosion upon the HVAC duct system, (6) the use of fire dampersand (7) the effect of the HVAC duct system on its supporting construction. Many types of fire-resistivematerials are used to protect HVAC ducts. These fire-resistive materials are either applied to HVACducts in the field o
6、r are fabricated as an integral part of the HVAC duct system when shipped from thefactory. Evaluating fire-resistive materials used to protect a HVAC duct from fire is an aid forpredicting their fire performance and helps to establish uniformity in requirements of variousauthorities. To do this it i
7、s necessary that the fire-resistance properties of HVAC ducts protected withfire-resistive materials be measured and specified according to a common standard expressed in termsthat are applicable alike to a wide variety of materials, situations, and conditions of exposure.1. ScopeNOTE 1Use of the st
8、andard designation ISO 6944 refers to both ISO6944:1985 and ISO 6944-1:2008.1.1 These test methods evaluate the fire-resistive materialsand the HVAC duct systems surface burning characteristics,non-combustibility, fire resistance, durability, and fire-engulfment with horizontal and vertical through-
9、penetrationfirestops.NOTE 2The intent of these test methods is to provide authoritieshaving jurisdiction a means to evaluate the fire performance of HVACduct systems to enable their application and use.1.2 These test methods evaluate the fire performance ofHVAC ducts, including both supply (pressuri
10、zed: Condition A Horizontal and Condition B Vertical) and return (exhaust:Condition C Horizontal and Condition D Vertical).1.3 These test methods evaluate the ability of a HVAC ductsystem to resist the spread of fire from one compartment toother compartments separated by a fire resistance rated con-
11、struction when the HVAC duct system is exposed to fire underone or more of the following conditions:1.3.1 Condition AFire exposure from the outside of thehorizontal HVAC duct system without openings,1.3.2 Condition BFire exposure from the outside of thevertical HVAC duct system without openings,1.3.
12、3 Condition CFire exposure from the outside with hotgases entering the inside of the horizontal HVAC duct systemwith unprotected openings, andNOTE 3Unprotected openings are openings that are not protected byfire dampers.1.3.4 Condition DFire exposure from the outside with hotgases entering the insid
13、e of the vertical HVAC duct systemwith unprotected openings.1.4 These test methods provide a means for determining thefire-resistance of vertical and horizontal HVAC duct systems,when subjected to the standard time-temperature curve of TestMethods E119.1.4.1 Condition AThese test methods provide a m
14、eans forevaluating a horizontal HVAC duct system, without openingsexposed to fire, passing through a vertical fire-separatingelement.1.4.2 Condition BThese test methods provide a means forevaluating a vertical HVAC duct system, without openings1These test methods are under the jurisdiction of ASTM C
15、ommittee E05 on FireStandards and are the direct responsibility of Subcommittee E05.11 on FireResistance.Current edition approved Aug. 1, 2013. Published September 2013. Originallyapproved in 2011. Last previous edition approved in 2013 as E2816-13. DOI:10.1520/E2816-13A.Copyright ASTM International
16、, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1exposed to fire and outfitted with a horizontal connection,passing through a horizontal fire-separating element.1.4.3 Condition CThese test methods provide a means forevaluating a horizontal HVAC duct system, with
17、unprotectedopenings exposed to fire, passing through a vertical fire-separating element.1.4.4 Condition DThese test methods provide a means forevaluating a vertical HVAC duct system with a horizontalconnection, and with unprotected openings exposed to fire,passing through a horizontal fire-separatin
18、g element.1.5 These test methods prescribe a standardized fire expo-sure for comparing the test results of the fire resistive materialsand HVAC duct systems. The results of these tests are onefactor in assessing predicted fire performance of HVAC ductsystems. Using these test results to predict the
19、performance ofactual HVAC duct systems requires the evaluation of testconditions.1.6 The values stated in inch-pound units are to be regardedas the standard. The SI values given in parentheses are forinformation only, unless the SI units are used consistently toperform all of the test methods refere
20、nced herein. In this case,the SI units will be regarded as the standard and will be usedin Section 17, Report.1.7 The text of these test methods references notes andfootnotes which provide explanatory material and (excludingthose in tables and figures) shall not be considered as require-ments of the
21、 fire-test-response standard.1.8 This document specifically excludes evaluating ductsthat carry combustibles, flammable vapors, combustible gases,and commercial kitchen ventilation systems commonly calledgrease ducts or hazardous exhaust ducts, which are tested incompliance with Test Methods E2336.1
22、.9 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat and flameunder controlled conditions, but does not by itself incorporateall factors required for fire hazard or fire risk assessment of thematerials, products, or assemblies under actual fire c
23、onditions.1.10 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.11
24、 Fire testing is inherently hazardous. Adequate safe-guards for personnel and property shall be employed inconducting these tests.2. Referenced Documents2.1 ASTM Standards:2C411 Test Method for Hot-Surface Performance of High-Temperature Thermal InsulationC518 Test Method for Steady-State Thermal Tr
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME28162013ASTANDARDTESTMETHODSFORFIRERESISTIVEMETALLICHVACDUCTSYSTEMS 防火 金属 采暖 通风 空调 管道 系统 标准 试验 方法

链接地址:http://www.mydoc123.com/p-531938.html