ASTM E1966-2007(2011) Standard Test Method for Fire-Resistive Joint Systems《耐火连接系统的标准试验方法》.pdf
《ASTM E1966-2007(2011) Standard Test Method for Fire-Resistive Joint Systems《耐火连接系统的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E1966-2007(2011) Standard Test Method for Fire-Resistive Joint Systems《耐火连接系统的标准试验方法》.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E1966 07 (Reapproved 2011)An American National StandardStandard Test Method forFire-Resistive Joint Systems1This standard is issued under the fixed designation E1966; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the
2、 year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONJoint systems are positioned in joints, voids, gaps, or other discontinuities between or bounded bytwo or mor
3、e supporting elements. Normally such openings are denoted as “linear” because the lengthis greater than their widthdefined by a typical ratio of at least 10:1 as in practice. Joints are presentin buildings as a result of:(i) Design to accommodate various movements induced by thermal differentials, s
4、eismicity, andwind loads and exist as a clearance separation.(ii) Acceptable dimensional tolerances between two or more building elements, for example,between non-loadbearing walls and floors.(iii) Inadequate design, inaccurate assembly, repairs or damage to the building.1. Scope1.1 This fire-test-r
5、esponse test method measures the perfor-mance of joint systems designed to be used with fire ratedfloors and walls during a fire endurance test exposure. The fireendurance test end point is the period of time elapsing beforethe first performance criteria is reached when the joint systemis subjected
6、to one of two time-temperature fire exposures.1.2 The fire exposure conditions used are either thosespecified by Test Method E119 for testing assemblies tostandard time-temperature exposures or Test Method E1529 fortesting assemblies to rapid-temperature rise fires.1.3 This test method specifies the
7、 heating conditions, meth-ods of test, and criteria for the evaluation of the ability of ajoint system to maintain the fire resistance where hourly ratedfire-separating elements meet.1.4 Test results establish the performance of joint systemsduring the fire-exposure period and shall not be construed
8、 ashaving determined the joint systems suitability for use afterthat exposure.1.5 This test method does not provide quantitative informa-tion about the joint system relative to the rate of leakage ofsmoke or gases or both. However, it requires that suchphenomena be noted and reported when describing
9、 the generalbehavior of joint systems during the fire endurance test but isnot part of the conditions of compliance.1.6 Potentially important factors and fire characteristics notaddressed by this test method include, but are not limited to:1.6.1 The performance of the fire-resistive joint systemcons
10、tructed with components other than those tested.1.6.2 The cyclic movement capabilities of joint systemsother than the cycling conditions tested.1.7 The values stated in inch-pound units are to be regardedas the standard. The SI values given in parentheses are forinformation only.1.8 The text of this
11、 standard references notes and footnoteswhich provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be consideredas requirements of the standard.1.9 This standard is used to measure and describe theresponse of materials, products, or assemblies to h
12、eat andflame under controlled conditions, but does not by itselfincorporate all factors required for fire hazard or fire riskassessment of the materials, products, or assemblies underactual fire conditions.1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the
13、direct responsibility of Subcommittee E05.11 on FireResistance.Current edition approved July 1, 2011. Published September 2011. Originallyapproved in 1998. Last previous edition approved in 2007 as E196607. DOI:10.1520/E1966-07R11.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, We
14、st Conshohocken, PA 19428-2959, United States.1.10 Fire testing is inherently hazardous. Adequate safe-guards for personnel and property shall be employed inconducting these tests.1.11 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresp
15、onsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2E84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE119 Test Methods f
16、or Fire Tests of Building Constructionand MaterialsE176 Terminology of Fire StandardsE631 Terminology of Building ConstructionsE1529 Test Methods for Determining Effects of LargeHydrocarbon Pool Fires on Structural Members and As-sembliesE2226 Practice for Application of Hose StreamE2307 Test Method
17、 for Determining Fire Resistance ofPerimeter Fire Barriers Using Intermediate-Scale, Multi-story Test Apparatus3. Terminology3.1 For the purpose of this standard, the definitions given inTerminologies E176 and E631, together with the following,apply:3.1.1 fire-separating element, nfloors, walls, and
18、 parti-tions having a period of fire resistance determined in accor-dance with Test Methods E119 or E1529.3.1.2 fire resistive joint system, na device or designedfeature that provides a fire separating function along continu-ous linear openings, including changes in direction, between orbounded by f
19、ire separating elements.3.1.3 joint, nthe linear void located between juxtaposedfire-separating elements.3.1.4 maximum joint width, nthe widest opening of aninstalled joint system.3.1.5 minimum joint width, nthe narrowest opening of aninstalled joint system.3.1.6 movement cycle, nthe change between
20、the minimumand the maximum joint widths of a joint system.3.1.7 nominal joint width, nthe specified opening of ajoint in practice that is selected for test purposes.3.1.8 splice, nthe connection or junction within the lengthof a joint system.3.1.9 supporting construction, nthe arrangement of build-i
21、ng sections forming the fire-separating elements into whichthe joint systems are installed.3.1.10 test assembly, nthe complete assembly of testspecimens together with their supporting construction.3.1.11 test specimen, na joint system of a specific mate-rial(s), design, and width.4. Summary of Test
22、Method4.1 This test method describes the following test sequenceand procedure:4.1.1 When the maximum joint width does not equal theminimum joint width, joint systems shall be movement cycledbefore being fire tested.4.1.2 Joint systems and their supporting construction shallbe conditioned and fire te
23、sted.4.1.3 A duplicate test specimen, that is an extension of awall, is subject to a fire of lesser duration than the fireresistance rating. After which, the duplicate test specimen issubject to the hose stream test.5. Significance and Use5.1 This test method evaluates, under the specified testcondi
24、tions: (1) the ability of a fire resistive joint system toundergo movement without reducing the fire rating of theadjacent fire separating elements and (2) the duration for whichtest specimens will contain a fire and retain their integrityduring a predetermined test exposure.5.2 This test method pro
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME196620072011STANDARDTESTMETHODFORFIRERESISTIVEJOINTSYSTEMS 耐火 连接 系统 标准 试验 方法 PDF

链接地址:http://www.mydoc123.com/p-529941.html