ASTM E1354-2015 Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter《采用耗氧热量计的材料与产品的热和可视烟雾释放率的标准试验方法》.pdf
《ASTM E1354-2015 Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter《采用耗氧热量计的材料与产品的热和可视烟雾释放率的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E1354-2015 Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter《采用耗氧热量计的材料与产品的热和可视烟雾释放率的标准试验方法》.pdf(21页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E1354 15 An American National StandardStandard Test Method forHeat and Visible Smoke Release Rates for Materials andProducts Using an Oxygen Consumption Calorimeter1This standard is issued under the fixed designation E1354; the number immediately following the designation indicates the
2、year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This fire-test-response standard provides for measur
3、ingthe response of materials exposed to controlled levels ofradiant heating with or without an external ignitor.1.2 This test method is used to determine the ignitability,heat release rates, mass loss rates, effective heat of combustion,and visible smoke development of materials and products.1.3 The
4、 rate of heat release is determined by measurementof the oxygen consumption as determined by the oxygenconcentration and the flow rate in the exhaust product stream.The effective heat of combustion is determined from a con-comitant measurement of specimen mass loss rate, in combi-nation with the hea
5、t release rate. Smoke development ismeasured by obscuration of light by the combustion productstream.1.4 Specimens shall be exposed to initial test heat fluxes inthe range of 0 to 100 kW/m2. External ignition, when used,shall be by electric spark. The value of the initial test heat fluxand the use o
6、f external ignition are to be as specified in therelevant material or performance standard (see X1.2). Thenormal specimen testing orientation is horizontal, independentof whether the end-use application involves a horizontal or avertical orientation. The apparatus also contains provisions forvertica
7、l orientation testing; this is used for exploratory ordiagnostic studies only.1.5 Ignitability is determined as a measurement of timefrom initial exposure to time of sustained flaming.1.6 This test method has been developed for use for materialand product evaluations, mathematical modeling, designpu
8、rposes, or development and research. Examples of materialspecimens include portions of an end-use product or thevarious components used in the end-use product.1.7 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.8 This standard
9、 is used to measure and describe theresponse of materials, products, or assemblies to heat andflame under controlled conditions, but does not by itselfincorporate all factors required for fire hazard or fire riskassessment of the materials, products, or assemblies underactual fire conditions.1.9 Thi
10、s standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For specific hazardst
11、atements, see Section 7.1.10 Fire testing is inherently hazardous. Adequate safe-guards for personnel and property shall be employed inconducting these tests.2. Referenced Documents2.1 ASTM Standards:2D5865 Test Method for Gross Calorific Value of Coal andCokeE176 Terminology of Fire StandardsE177 P
12、ractice for Use of the Terms Precision and Bias inASTM Test MethodsE603 Guide for Room Fire ExperimentsE662 Test Method for Specific Optical Density of SmokeGenerated by Solid MaterialsE691 Practice for Conducting an Interlaboratory Study toDetermine the Precision of a Test MethodE906 Test Method fo
13、r Heat and Visible Smoke ReleaseRates for Materials and Products Using a ThermopileMethod2.2 ISO Standards:3ISO 5657-1986(E) Fire Testsreaction to fireignitabilityof building materialsISO 5725-2 (1994) Accuracy (trueness and precision) ofmeasurement methods and results Part 2: Basic method1This test
14、 method is under the jurisdiction of ASTM Committee E05 on FireStandardsand is the direct responsibility of Subcommittee E05.21 on Smoke andCombustion Products.Current edition approved May 15, 2015. Published June 2015. Originallyapproved in 1990. Last previous edition approved in 2014 as E1354 - 14
15、1. DOI:10.1520/E1354-15.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Sta
16、ndards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1for the determination of repeatability and reproducibilityof a standard measurement method3. Ter
17、minology3.1 DefinitionsFor definitions of terms used in this testmethod, refer to Terminology E176.3.2 Definitions of Terms Specific to This Standard:3.2.1 critical heat flux for ignition, nthe midpoint withinthe range of heat fluxes between the maximum (highest) heatflux that produces no ignition a
18、nd the minimum (lowest) heatflux that produces ignition, for a specified exposure time.3.2.2 effective heat of combustion, nthe amount of heatgenerated per unit mass lost by a material, product or assembly,when exposed to specific fire test conditions (contrast grossheat of combustion).3.2.2.1 Discu
19、ssionThe effective heat of combustion de-pends on the test method and is determined by dividing themeasured heat release by the mass loss during a specifiedperiod of time under the specified test conditions.Typically, thespecified fire test conditions are provided by the specificationsof the fire te
20、st standard that cites effective heat of combustionas a quantity to be measured. For certain fire test conditions,involving very high heat and high oxygen concentrations underhigh pressure, the effective heat of combustion will approxi-mate the gross heat of combustion. More often, the fire testcond
21、itions will represent or approximate certain real fireexposure conditions, and the effective heat of combustion is theappropriate measure. Typical units are kJ/g or MJ/kg.3.2.3 gross heat of combustion, nthe maximum amount ofheat per unit mass that theoretically can be released by thecombustion of a
22、 material, product, or assembly; it can bedetermined experimentally and only under conditions of highpressure and in pure oxygen (contrast effective heat of com-bustion).3.2.4 heat flux, nheat transfer to a surface per unit area,per unit time (see also initial test heat flux).3.2.4.1 DiscussionThe h
23、eat flux from an energy source,such as a radiant heater, can be measured at the initiation of atest (such as Test Method E1354 or Test Method E906) andthen reported as the incident heat flux, with the understandingthat the burning of the test specimen can generate additionalheat flux to the specimen
24、 surface. The heat flux can also bemeasured at any time during a fire test, for example asdescribed in Guide E603, on any surface, and with measure-ment devices responding to radiative and convective fluxes.Typical units are kW/m2, kJ/(s m2), W/cm2, or BTU/(s ft2).3.2.5 heat release rate, nthe heat
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME13542015STANDARDTESTMETHODFORHEATANDVISIBLESMOKERELEASERATESFORMATERIALSANDPRODUCTSUSINGANOXYGENCONSUMPTIONCALORIMETER

链接地址:http://www.mydoc123.com/p-528521.html