ARMY MIL-PRF-13312 R-1996 REFRIGERATION UNITS MECHANICAL PANEL MOUNTED 10 000 BTU FOR REFRIGERATOR PREFABRICATED PANEL TYPE [Use In Lieu Of ARMY MIL-R-0013312 P]《控电板式预制制冷器10 000 BT.pdf
《ARMY MIL-PRF-13312 R-1996 REFRIGERATION UNITS MECHANICAL PANEL MOUNTED 10 000 BTU FOR REFRIGERATOR PREFABRICATED PANEL TYPE [Use In Lieu Of ARMY MIL-R-0013312 P]《控电板式预制制冷器10 000 BT.pdf》由会员分享,可在线阅读,更多相关《ARMY MIL-PRF-13312 R-1996 REFRIGERATION UNITS MECHANICAL PANEL MOUNTED 10 000 BTU FOR REFRIGERATOR PREFABRICATED PANEL TYPE [Use In Lieu Of ARMY MIL-R-0013312 P]《控电板式预制制冷器10 000 BT.pdf(21页珍藏版)》请在麦多课文档分享上搜索。
1、 NIL-PRF-LIJR 94999Ob 2022003 b24 INCH-POUND I 31 July 1996 SUPERSEDING 19 June 1992 25 May 1988 MIL-PRF-133 12R MIL-R-O0133 12P (GL) MIL-R- 1 3 3 12N PERFORMANCE SPECIFICATION REFRIGERATION UNITS, MECHANICAL, PANEL MOUNTED, 10,000 BTU FOR REFRIGERATOR, PREFABRICATED, PANEL TYPE This specification i
2、s approved for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This document covers two types of panel mounted, mechanical, refrigeration units having a capacity of 10,000 British thermal units (Btu) per hour and used with the prefabricated, panel type refiigera
3、tor (see 6.1). 1.2 Classification. The refrigeration units shall be of the following types as specified (see 6.2): Type I - Diesel Engine Driven Type II - Electric Motor Driven 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3 and 4 of this specifi
4、cation. This section does not include documents cited in other sections of this specification or Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be addressed to: Commander, U.S. Army Natick Research, Development
5、, and Engineering Center, Natick, MA 01760-501 8 by using the Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter. AMSC NIA FSC 4110 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,- MIL-PRF-
6、13312R 9999406 2022004 560 MIL-PRF- 133 12R recommended for additional information or as examples. While every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements documents cited in sections 3 and 4 of this specifi
7、cation, whether or not they are listed. 2.2 Government documents. 2.2.1 Standards. The following standards form part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those listed in the issue of the Department of Defense Index of Specific
8、ations and Standards (DoDISS) and supplement thereto, cited in the solicitation (see 6.2). STANDARDS DEPARTMENT OF DEFENSE MIL-STD-46 1 MIL-STD-462 MIL-STD-8 1 O MIL-STD-1474 (Unless otherwise indicated, copies of the above standards are available from the Standardization Document Order Desk, 700 Ro
9、bbins Avenue, Building 4D, Philadelphia, PA - Requirements for the Control of Electromagnetic Interference - Measurement of Electromagnetic Interference Characteristics - Environmental Test Methods and Engineering Guidelines - Noise Limits for Military Materiel (Metric) Emissions and Susceptibility
10、191 11-5094). 2.3 fi n blica ons. The following documents form a part of this document to the extent specified herein. Unless otherwise specified, the issues of the documents which are DoD adopted are those listed in the issue of the DoDISS cited in the solicitation. Unless otherwise specified, the
11、issues of documents not listed in the DoDISS are the issues of the documents cited in the solicitation (see 6.2). NATIONAL, ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) MG-1 - Motors and Generators (Application for copies should be addressed to the National Electrical Manufacturers Association, 1300
12、No. 17th Street, Suite 1847, Rosslyn, VA 22209). 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-133L2R 9999906 2022005 4T7 MIL-PRF- 1 3 3 12R NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) Standard No. 70 - National Electrical Code (Applicati
13、on for copies should be addressed to the National Fire Protection Association, One Battery March Park, Quincy, MA 02269-9 1 O 1). UNDERWRITERS LABORATORIES INC. (UL) Standard 207 - Refrigerant Containing Components and Accessories, Nonelectrical Standard 486 - Wire Connectors and Solder Lugs (Applic
14、ation for copies should be addressed to the Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096). 2.4 Order of precedence. In the event of a conflict between the text of this document and the references cited herein, the text of this document takes precedence. Nothing in t
15、his document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained, 3. REQUIREMENTS 3.1 First article. When specified (see 6.2), a sample shall be subjected to first article inspection in accordance with 4.1.1. 3.2 Design. materials. and manufacturing pro
16、cesses. Unless otherwise specified, the design, materials, and manufacturing process selection is the prerogative of the contractor as long as all articles submitted to the Government fully meet the requirements specified. 3.3 ODerating reauirements. Refrigeration units shall satis the following fun
17、ctional, operational and performance requirements. 3.3.1 $:hour oDeration. Refrigeration units shall operate properly with suction and discharge pressures safely controlled. 3.3.2 72-hour operation. Refrigeration units shall operate properly and maintain noted conditions at thermostat settings of OF
18、 and 35F. 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,- NIL-PRF-13312R 9999906 2022006 333 E MIL-PRF-13312R . 3.3.3 Refrigeration capacity. Refrigeration units shall have minimum net capacities of 10,000 BtLJ/hr at a thermostat setting of OF and
19、 18,000 Btu/hr at a thermostat setting of 359. 3.3.4 Defrost svstem. Refrigeration units shall have a defrost cycle automatically initiated by a time control adjustable between 6 and 24 hours and producing not less than 1 O pounds of condensate within 30 minutes. 3.3.5 Moisture content. The moisture
20、 content of the refrigeration system shall be kept at a minimum to maintain proper operation of the refrigeration unit. 3.3.6 Refirrerant leakage. Refrigerant containing components shall be gastight. 3.3.7 Operation time. Type I refrigeration units shall operate for a minimum of 44 hours without ref
21、ueling. 3.3.8 Design reliability. Refrigeration units shall operate properly for 2500 hours. 3.3.9 Ozone-depleting substances. The refrigerant shall be commercially available nonozone- depleting, and environmentally safe. Class I ozone-depleting substances, as determined by the Environmental Protect
22、ion Agency, shall not be contained in, and shall be prohibited fiom use during the fabrication of, the refrigeration units (see 6.6). 3.3.1 O TemDerature control. The selected temperature of the refrigeration units shall be controlled automatically. The temperature control shall allow an incremental
23、 selection of normal refrigerator temperatures. 3.3.1 1 Diesel engine. Unless otherwise specified for type I refrigeration units (see 6.2), the diesel engines electrical system shall operate on 12-volt direct current (DC). The engine shall operate on diesel and JP-8 fuels. 3.3.12 Compressor. Unless
24、otherwise specified for type II refrigeration units (see 6.2), the compressor shall operate on 208/230 volt, 3-phase, 60-hertz (Hz) and 3-phase, 50-Hz power on the voltage specified in the contract or order (see 6.2). 3.3.13 Sdety. The refrigeration units shall minimize flammability, operational, to
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYMILPRF13312R1996REFRIGERATIONUNITSMECHANICALPANELMOUNTED10000BTUFORREFRIGERATORPREFABRICATEDPANELTYPEUSEINLIEUOFARMYMILR0013312P

链接地址:http://www.mydoc123.com/p-446994.html