ANSI NEIS 402-2014 Standard for Installing and Maintaining Motor Control Centers.pdf
《ANSI NEIS 402-2014 Standard for Installing and Maintaining Motor Control Centers.pdf》由会员分享,可在线阅读,更多相关《ANSI NEIS 402-2014 Standard for Installing and Maintaining Motor Control Centers.pdf(46页珍藏版)》请在麦多课文档分享上搜索。
1、AN AMERICAN NATIONAL STANDARDNECA 402-2014 Standard forInstalling and Maintaining Motor Control CentersPublished byNational Electrical Contractors AssociationStandard forInstalling and MaintainingMotor Control CentersNECA 402-2014An AmericanNational StandardPublished byNational Electrical Contractor
2、s AssociationNOTICE OF COPYRIGHTThis document is copyrighted by NECAReproduction of these documents either in hard copy or soft (including posting on the web) is prohibited without copyright permission. For copyright permission to reproduce portions of this document, please contact NECA Standards th
3、e phase conductors are physically isolated from each other. Consult local building codes and coordinate seismic requirements for motor control centers prior to installation. In seismic locations, provide a minimum of 4000 psi concrete for foundations. Use manufacturer-recommended anchoring means, su
4、ch as stud anchors, sleeve anchors, or concrete anchor bolts.n 101. ScopeProper installation is essential to the successful operation of all motor control center components. Advance preparation and planning for installation is advisable. Request the manufacturers instruction manuals, related literat
5、ure, and drawings before the motor control center is delivered, and study this material thoroughly before installation.6.1 General Install motor control centers in accordance with contract documents, manufacturer instructions, and approved shop drawings. Install motor control center sections in fina
6、l positions, progressively leveling each section and bolting frames of shipping splits together. Secure the motor control center to walls or other supporting surfaces in accordance with manufacturer recommendations, if necessary. Do not secure motor control centers with wooden plugs driven into hole
7、s in masonry, concrete, plaster, or similar materials. Install motor control center sections starting with the most restrictive section first. If the motor control center has incoming cables or busway near or in its center, start with that vertical section first and work outwardly on each side. If t
8、he motor control center is fed from the left-most section, start from the left and work toward the right. If the motor control center is fed from the right-most section, start from the right and work toward the left. If the motor control center is close-coupled to a transformer, start at the transfo
9、rmer and work away from the transformer. Clean dirt and debris from the concrete equipment foundation and the surrounding area where the motor control center will be located before moving the motor control center into its final position. Remove shipping skids before installing the motor control cent
10、er on the foundation.6.2 Installing Vertical Sections If the motor control center sections are equipped with bottom closure plates, temporarily remove these plates. Cut holes in motor control center bottom closure plates that correspond to the conduits entering the bottom of each enclosure based on
11、that sections conduits. Saw kerfs between conduit holes in bottom closure plates for isolated phase installations where individual phase conductors are run in individual conduits, such as duct bank risers. Reinstall bottom closure plates after the vertical sections of the motor control center have b
12、een installed. Ensure that steel bottom plates are provided for motor control centers installed on combustible surfaces. Install motor control center vertical sections in sequence. Position each section carefully. Follow handling instructions in Section 4.2. Level sections with shims, if necessary,
13、and align each section with the previous section. Ensure proper alignment for joining structures and through-bus. Improper alignment of the through-bus can result in personal injury, death, and/or property loss. Lift each shipping section vertically into place using a crane, timbers, jacks, or a for
14、klift to clear embedded conduit projections above the finished concrete equipment foundation, when necessary. Remove lifting straps or slings so that vertical sections can be joined flush. Leave lifting hardware on the section if their removal is not required to join adjacent sections flush together
15、.6. Installation11 nStandard for Installing and Maintaining Motor Control Centers NECA 4026.3 Joining and Anchoring Motor Control Center Sections Open all doors or remove all panels that provide access for bolting adjacent sections together. Bolt sections together in accordance with manufacturers in
16、structions, keeping in mind that the authority having jurisdiction may require that all bolts connecting bus sections be inspected for proper torque prior to closing up the motor control center. Anchor each vertical section to the base channel or foundation to protect against bumping or shifting tha
17、t can damage interior components, conduit hubs, and cable and busway connections (see Figure 4). Anchor motor control centers for seismic conditions in accordance with contract documents and local building codes. Seal completely between the concrete foundation and the motor control center structure
18、to prevent the entry of rodents, rain, and snow.6.4 Electrical Interconnections Between Vertical Sections Vertical sections of motor control centers are electrically linked together using through-bus or cables. Through-bus splice connections are extremely important to the performance of the motor co
19、ntrol center, because these connections carry the full current intended for the operation of the motor control center. Failure to properly make through-bus splice connections can result in property damage, death, or serious injury. Ensure that each source is in phase across tie-breakers in double-en
20、ded equipment.6.4.1 Through-bus Splices Through-bus splice kits are provided by the motor control center manufacturer when more than one section is required to be electrically connected together by through-bus. The splice kits may be in separate boxes, be shipped inside the sections to be spliced, o
21、r be installed on the through-bus of one or more vertical sections. Follow the proper sequence of hardware installation, as specified in the manufacturers installation instructions. Conical washers should be installed with the convex or “top” side against the nut (see Figure 5). Torque each splice b
22、olt to the values recommended by the manufacturer. In the absence of manufacturers torque tables, terminals should be tightened in compliance with Annex I of NFPA 70. Mark each torqued connection with a permanent marker. The through-bus of some motor control centers is covered with an insulating mat
23、erial. Follow the manufacturers instructions for installing insulation on each through-bus splice connection.1.13 in(29 mm)Motor Control Center FrameSecure the motor control centerto the mounting surface usingthe holes closest to the surface.Formed Base ChannelMounting SurfaceDiameter hole in eachco
24、rner for anchoring.Figure 4: Anchoring the motor control centerFigure 5: Proper positioning of conical washersHex NutBolt HeadWasherMarked “Top”WasherMarked “Top”n 12NECA 402 Standard for Installing and Maintaining Motor Control Centers6.4.2 Cable Interconnections For cable interconnections between
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSINEIS4022014STANDARDFORINSTALLINGANDMAINTAININGMOTORCONTROLCENTERSPDF

链接地址:http://www.mydoc123.com/p-437449.html