NEMA GD 1-2016 Evaluating Water-Damaged Electrical Equipment.pdf
《NEMA GD 1-2016 Evaluating Water-Damaged Electrical Equipment.pdf》由会员分享,可在线阅读,更多相关《NEMA GD 1-2016 Evaluating Water-Damaged Electrical Equipment.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、 Evaluating Water-Damaged Electrical Equipment www.nema.org 2016 National Electrical Manufacturers Association Page 1 1 USE OF THIS PUBLICATION This publication serves as a guide that represents the consensus of NEMA member companies and is not intended to override the recommendations of the specifi
2、c equipment manufacturer. These guidelines provide information on how to evaluate electrical equipment that has been exposed to water through flooding, fire-fighting activities, hurricanes, and other events involving large quantities of water. It is designed for use by suppliers, installers, inspect
3、ors, and users of electrical products. Where additional information is required, it is recommended that the specific electrical equipment manufacturers be consulted. Evaluation of electrical equipment should be conducted by qualified personnel. Electrical equipment exposed to water can be extremely
4、hazardous if reenergized without performing a proper evaluation and taking necessary actions. Reductions in the integrity of electrical equipment due to moisture can affect the ability of the equipment to perform its intended function. Damage to electrical equipment can also result from flood waters
5、 contaminated with chemicals, sewage, oil, and other debris, which will affect the integrity and performance of the equipment. Ocean water and salt spray can be particularly damaging due to the corrosive and conductive nature of the saltwater residue. Distributors of electrical equipment should not
6、supply any inventory that has been subjected to water damage. This can lead to the continued use of damaged equipment, creating a hazard to individuals or property. 2 CONTACT THE MANUFACTURER Working knowledge of electrical systems and the equipment in question is required to evaluate damage due to
7、contact with water. The original manufacturer of the equipment should be contacted if any questions arise or specific recommendations are needed. In many cases, a replacement will be necessary. After consultation with the manufacturer, some larger types of electrical equipment may be reconditioned b
8、y properly trained personnel. The potential to recondition the equipment may vary with the nature of the electrical function, the degree of flooding, the age of the equipment, and the length of time the equipment was exposed to water. Attempts to recondition equipment without consulting the manufact
9、urer can result in additional hazards due to the use of improper cleaning agents, which can further damage the equipment (see National Electrical CodeNEC section 110.11, Informational Note No. 2) or due to improper reconditioning techniques. NEMA member companies are committed to safety. For specifi
10、c contacts within these manufacturing firms, call or write: National Electrical Manufacturers Association 1300 North 17th Street, Suite 900 Rosslyn, Virginia 22209 Telephone: (703) 841-3236 Fax: (703) 841-3336 ATTN: Vince Baclawski email: vin_baclawskinema.org Page 2 2016 National Electrical Manufac
11、turers Association 3 ELECTRICAL EQUIPMENT REPLACEMENT/RECONDITIONING REQUIREMENTS The table shown below provides the requirements and recommendations associated with various categories of electrical equipment that have been subjected to water damage. Where it is shown that the equipment “may be reco
12、nditioned,” it is critical that the manufacturer of the equipment be contacted for specific guidance. Equipment Replace equipment May be reconditioned (contact the manufacturer) Additional standards reference (if available) ELECTRICAL DISTRIBUTION EQUIPMENT (refer to 4.1) Molded-case circuit breaker
13、s X Low-voltage fuses X Switches X NEMA KS 3-2010 Guidelines for Inspection and Preventive Maintenance of Switches Used in Commercial and Industrial Applications Busway (Mylar wrapped bars) X NEMA BU 1.1-2000 General Instructions for Handling, Installation, Operation, and Maintenance of Busway Rated
14、 600 Volts or Less, par. 3.4.4, 9.2.4.2 Busway (powder-coated bars) XPanelboards X NEMA PB 1.1-2013 General Instructions for Proper Installation, Operation, and Maintenance of Panelboards Rated 600 Volts or Less, par. 10.3, 10.8, 10.8.3, 10.8.4, 10.9 Switchboards X NEMA PB 2.1-2013 General Instructi
15、ons for Proper Handling, Installation, Operation and Maintenance of Deadfront Distribution Switchboards Rated 600 Volts or Less, par. 9.1, 9.8, 9.8.3, 9.8.4, 9.9 MOTOR CONTROL EQUIPMENT (refer to 4.2) Adjustable speed drives X Components containing semiconductors and transistors X Electronically con
16、trolled and solid-state contactors and starters X Overload relays X Manual and magnetic controllers XMotor control centers (see 4.2.2) 2016 National Electrical Manufacturers Association Page 3 Equipment Replace equipment May be reconditioned (contact the manufacturer) Additional standards reference
17、(if available) POWER EQUIPMENT (refer to 4.3) Electronic trip units of LV power circuit breakers X High-voltage circuit breakers (AC) X Low-voltage power circuit breakers Electromechanical protective relays, meters, and current transformers (see section 4.11 for devices that contain electronic compo
18、nents) X Electronic protective relays, meters, and current transformers (see section 4.11) X Low-voltage switchgear X Medium-voltage switchgear X Medium-voltage fuses X TRANSFORMERS (refer to 4.4) All dry-type transformers regardless of kVA ratings X All dry-type control circuit transformers X Liqui
19、d-filled transformers X (Analysis of the insulating medium is required for evaluation of this equipment.) Cast-resin transformers X CONDUIT, TUBING, FITTINGS, OUTLET BOXES, AND JUNCTION BOXES (refer to 4.5) Fittings X NEMA FB 1-2007(R2010) Fittings, Cast Metal Boxes and Conduit Bodies for Conduit, E
20、lectrical Metallic Tubing (EMT) and Cable Outlet and junction boxes X NEMA OS 1-2008 (R2010) Sheet-Steel Outlet Boxes, Device Boxes, Covers and Box Supports NEMA OS 2-2008 Nonmetallic Outlet Boxes, Device Boxes, Covers and Box Supports Conduit and tubing X Page 4 2016 National Electrical Manufacture
21、rs Association Equipment Replace Equipment May be Reconditioned (Contact the manufacturer.) Additional Standards Reference (if available) WIRE, CABLE, AND FLEXIBLE CORDS (refer to 4.6) Wire or cable listed for dry locations (such as NM-B) X Wire or cable that is suitable for wet locations (Provided
22、the ends of the wire or cable have not been exposed to water, and the wire is not damaged.) X AFCIs, GFCIs, SURGE PROTECTIVE DEVICES AND WIRING DEVICES (refer to 4.7) Arc-fault circuit interrupters (AFCI) and ground-fault circuit interrupters (GFCI) X Surge-protective devices (transient voltage surg
23、e suppressors, surge arresters, lightning arresters) X Wiring devices (switches, receptacles, dimmers, etc.) X OTHER DEVICES Batteries (refer to 4.12) X Cable tray (refer to 4.8) X (Replace damaged labels.) Fire pump controllers X NEMA ICS 15-2011 Instructions for the Handling, Installation, Operati
24、on, and Maintenance of Electric Fire Pump Controllers Rated Not More Than 600V Luminaires (lighting fixtures), ballasts, and LED drivers (refer to 4.9) X Motors (refer to 4.10) X ANSI/IEEE 43-2013, A2 and A3, ANSI/EASA AR100 Signaling, protection, and communications systems (refer to 4.11) X Uninter
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NEMAGD12016EVALUATINGWATERDAMAGEDELECTRICALEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-994206.html