《NAVY MIL-T-15108 C-1975 TRANSFORMERS POWER STEP-DOWN SINGLE-PHASE 60 HERTZ 1-KILOVOLTAMPERE APPROXIMATE MINIMUM RATING DRY TYPE NAVAL SHIPBOARD《海军舰降压单相的60赫兹1千伏安进似最小值变形器》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-T-15108 C-1975 TRANSFORMERS POWER STEP-DOWN SINGLE-PHASE 60 HERTZ 1-KILOVOLTAMPERE APPROXIMATE MINIMUM RATING DRY TYPE NAVAL SHIPBOARD《海军舰降压单相的60赫兹1千伏安进似最小值变形器》.pdf(21页珍藏版)》请在麦多课文档分享上搜索。
1、MIL-T-15108C(NAVY)20 November 1975SUPERSEDINGMIL-T-15108B22 August 1955(See 6.4)MILITARY SPECIFICATIONTRANSFORMERS, POWER, STEP-DOWN, SINGLE-PHASE,60-HERTZ, 1-KILOVOLTAMPERE APPROXIMATEMINIMUM RATING, DRY TYPE, NAVAL SHIPBOARDThis specification is approved for use by all interested Commands of the D
2、epartment ofthe Navy and the Marine Corps and is available for use by all other Departments and Agenciesof the Department of Defense.1. SCOPE1.1 This specification covers dry type, 60-hertz (Hz), single-phase, electric trans-formers of standard mounting dimensions for shipboard use.2. APPLICABLE DOC
3、UMENTS2.1 The following documents, of the issue in effect on date of invitation for bids orrequest for proposal, form a part of this specification to the extent specified herein.SPECIFICATIONSFEDERALJ-W-1177 - Wire, Magnet, Electrical.MILITARYMIL-S-901-Shock Tests, H.I. (High-Impact); Shipboard Mach
4、inery,Equipment and Systems, Requirements for.MIL-E-917 - Electric Power Equipment, Basic Requirements (NavalShipboard Use).MIL-E-2036 - Enclosures For Electric and Electronic Equipment, NavalShipboard.MIL-P-15024 - Plates, Tags and Bands For Identification of Equipment.MIL-P-15024/5 - Plates Identi
5、fication.MIL-E-16366 - Electrical Clamps, Lug Terminals and Conductor Splices-Pressure Grip.MIL-W-16878/7 - Wire, Electrical, Type F, 200C, 600 Volts, (Insulated,High Temperature).MIL-E-17555 - Electronic and Electrical Equipment Accessories, and RepairParts; Packaging and Packing of.STANDARDSMILITA
6、RYMIL-STD-108 - Definitions of and Basic Requirements for Enclosures forElectric and Electronic Equipment.MIL-STD-195 - Marking of Connections for Electric Assemblies.(Copies of specifications, standards, drawings and publications required by suppliersin connection with specific procurement function
7、s should be obtained from the procuringactivity or as directed by the contracting officer.)3. REQUIREMENTSThe transformers furnished under this specification shall beproducts which are qualified for listing on the applicable qualified products list at timeset for opening of bids (see 4.3 and 6.3) .3
8、.2 Definitions. The definitions specified in 3.2.1 through 3.2.11 shall apply to thevarious technical terms specified herein.3.2.1 Transformer. A transformer is an electric device without continuously movingparts which by electromagnetic induction transfers electric energy from one or more circuitst
9、o one or more other circuits at the same frequency usually with changed values of voltageand current.FSC 6120Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-T-15108C(NAVY)3.2.2 Dry type transformer. A dry type transformer is a transformer cooled
10、by thenatural circulation of air.3.2.3 Primary winding. Primary winding is the winding on the input side.3.2.4 Secondary winding. Secondary winding is the winding on the output side.3.2.5 Tap in a transformer. A tap in a transfer-r is a connection brought out of awinding at some point between its ex
11、tremities, usually to permit changing the voltage ratio.3.2.6 Rated kilovoltampere kVA of a transformer. Rated kVA of a transformer is theoutput which can be delivered for the time specified at approximately rated secondary voltageand rated frequency without exceeding the specified temperature limit
12、ations.3.2.7 Ratio of a transformer. Ratio of a transformer is the turn ratio of the trans-former.3.2.8 Regulation of a transformer. Regulation of a transformer is the change insecondary voltage, expressed in percent of rated secondary voltage, which occurs when ratedkVA output at a specified power
13、factor is reduced from rated value to zero, with the primaryimpressed terminal voltage maintained constant. 3.2.9 Impedance voltage of a transformer. Impedance voltage of a transformer is thevoltage required to circulate rated current through a winding of the transformer when anotherwinding is short
14、-circuited, with the respective windings connected for rated voltage operationand is expressed in percent of the rated voltage of the winding in which the voltage ismeasured.3.2.10 Exciting current of a transformer.current which flows in any winding used to excite the transformer when all other wind
15、ings areExciting current of a transformer is theopen-circuited, and is expressed in percent of the rated current of the winding in which itis measured.3.2.11 Lead polarity of a transformer. Lead polarity of a transformer is a designationof the relative instantaneous directions of currents in its lea
16、ds. Primary and secondaryleads are said to have the same polarity when at a given instant the current enters theprimary lead in question and leaves the secondary lead in question in the same direction asthough the two leads formed a continuous circuit. The lead polarity of a single-phasedistribution
17、 or power transformer may be either additive or subtractive. If one pair ofadjacent leads from the windings in question is connected together and voltage applied toone of the windings:(a) Lead polarity is additive if the voltage across the other two leadsof the windings in question is greater than t
18、hat of the highervoltage winding alone.(b) Lead polarity is subtractive if the voltage across the other two leadsof the windings in question is less than that of the higher voltagewinding alone.# 3.3 General requirements. Transformers shall comply with the requirement of MIL-E-917and the requirement
19、s of this specification, except as otherwise specified in the contractor order. If any requirement specified herein conflicts with the requirements of MIL-E-917,the requirements of this specification shall govern.# 3.4 Insulation system. The insulation system shall be class 130 as specified inMIL-E-
20、917 or higher. The whole core and coil of each transformer shall have varnish appliedby the dipping process or vacuum-pressure process specified in MIL-E-917.# 3.5 Painting Painting shall comply with the requirements of MIL-E-917, except thatonly one coat of gray enamel need be applied. Marks or scr
21、atches made due to handling dur-ing fabrication and testing shall be repainted by either complete repainting of equipmentor by touchup method. Parts to be painted shall consist of those not having a corrosion-resisting treatment or not fabricated of corrosion-resisting materials of the types speci-f
22、ied in MIL-E-917 and shall include exterior and interior surfaces of the enclosure.# 3.6 Enclosure. Unless otherwise specified in the contract or order, transformers shallbe driproof (45 degree), in accordance with class I of MIL-E-2036 for electric equipment andwith MIL-STD-108. Enclosure shall pro
23、vide for the entrance of the ships cables. Readyaccessibility shall be provided with clearance in the vertical direction for installationand maintenance or electrical connections (see table III). Sufficient space shall be provided2Provided by IHSNot for ResaleNo reproduction or networking permitted
24、without license from IHS-,-,-MIL-T-15108C(NAVY)in the terminal compartment for making connections of single-phase transformers in closeddelta banks. The terminal compartment shall be so constructed that it is possible to dis-connect readily a transformer connected in a three-phase bank without distu
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILT15108C1975TRANSFORMERSPOWERSTEPDOWNSINGLEPHASE60HERTZ1KILOVOLTAMPEREAPPROXIMATEMINIMUMRATINGDRYTYPENAVALSHIPBOARD

链接地址:http://www.mydoc123.com/p-982497.html