1、MIL-G-3LLLC bL 999990b IlO4441 i4 - MIL-G-3 11 lC(SHIPs) 25 April 1961 SUPERSEDING 14 October 1955 MIL-G-SIllB(SHIPS) MILITARY SPECIFICATION GENERATORS, ELECTRIC, DIRECT-CURRENT (NAVAL SHIPBOARD USE) 1. SCOPE 1.1 Generators. - This specification covers direct-current (d. c.) generators up to 1,000 k
2、ilo- watt (kw.). 2. APPLICABLE DOCUMENTS 2.1 The following documents, of the issue in ef- fect on date of invitation for bids, form a part of this specification, to the extent specified herein: SPECIFICATIONS FEDERAL FF-B-171 - Bearing Ball, Annular, (General FF-B-185 - Bearings, Roller, Cylindrical
3、; Purpose). and Bearings, Roller, Self- Aligning MILITARY MIL-W-806 - Wire, Armature-Banding, Steel, Tinned. MIL-S-901 - Shockproof -Equipment, Class HI (High-Impact); Shipboard Application, Tests for. Power, Basic Require- ments for (Naval Ship- board Use). cedure For Procurement of. MIL-E-2036 - E
4、nclosures for Electric and Electronic Equipment (Naval Shipboard Use). Nonmagnetic, Iron- Chrome-Nickel-Alloy. tact; and Carbon Stock Electrical Contact, Brush. MIL -Q-9858 - Quaiity Control System Re- quirements. MIL-M-15071 - Manual, Technical, for Mechanical and Electrical Equipment (less Elec- t
5、ronics). MIL-T-15108 - Transformers, Power, Step- Down, Single Phase, 60 Cycle. 1-KVA Approximate MIL-E-917 - Equipment, Electric MIL-D-963 - Drawings, Production, Pro- MIL-W-3068 - Wire, Armature-Banding, MIL-B-3743 - Brushes, Electrical Con- - ._ .- Minimum Rating; And Re- actors (Balance coils)-
6、Dry, Naval Shipboard MIL-R-15109 - Resistors and Rheostats, Shockproof (Naval Ship- board Use). MIL-E-17555 - Electronic And Electrical Equipment And Associated Repair Parts, Preparation For Delivery Of. STANDARDS MILITARY MIL-STD-167 - Mechanical Vibrations of Shipboard Equipment. MIL-STD-740 - Noi
7、se Measurements of Shipboard Machinery and Equipment. (Copies of specifications, standards, drawings, and publications required by contractors in connection with specific procurement functions should be ob- tained from the procuring activity or as directed by the contracting officer. ) 2.2 Other pub
8、lications. - The following docu- ments form a part of this specification to the extent specified herein. Unless otherwise indicated, the issue in effect on date of invitation for bids shall apply. AMERICAN SOCIETY FOR TESTING MATERIALS ASTM A27-58 - Mild To Medium Strength Carbon Steel Castings For
9、General Application - Malleable Iron Castings - Carbon And Alloy Steel Ring And Disk Forgings - Nodular Iron Castings - White Metal Bearing Alloys - Aluminum Base Alloy Sand Castings - Aluminum Base Alloy Die Castings - Phosphor Bronze Rod, Bar, And Shapes - Leaded Yellow Brass Sand Castings For Gen
10、eral Purposes Plate ASTM A47-52 ASTM A243-55 ASTM A339-55 ASTM B23-49 ASTM B26-58T ASTM B85-58T ASTM B139-58 ASTM B146-52 ASTM B209-59T - Aluminum Alloy Sheet and /FSC 6115 I Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-G-JlllC(SHIPS) (Applica
11、tion for copies should be addressed to the American Society for Testing Materials, 1916 Race Street, Philadelphia 3, Pa. ). 3. REQUIREMENTS , 3.1 Definitions.- 3.1.1 Continuous duty. - Operation at a substan- tially constant load for an indefinite period of time. 3.1.2 Efficiency. - Ratio of the use
12、ful power out- put to the total power input. input where input is determined by addition of all component losses to the output. 3.1.3 Conventional efficiency. - Ratio of output to 3.1.4 Air-gap line. - Extended straight line part of the no-load saturation curve. 3.2 Performance requirements. - 3.2.1
13、 Rating. - The rating in kw, voltage and revolutions per minute (r. p. m. ) shall be as specified (see 6.1). 3.2.2 Efficiency. - The efficiency of the gener- ator shall be as specified (see 6.1). for the following voltages, as specified (see 6.1): 3.2.3 Voltage. - Generators shall be designed 120 Vo
14、lts 240 Volts 120/240 Volts 3.2.4 Dus. - Generators shall deliver rated cur- rent continuously at rated voltage and rated r. p. m 3.2.5 Overload. - When specified (see 6. i), each generator shaii also be capable of delivering at rated voltage and r.p. m., 125 percent rated kw load for 2 hours and 15
15、0 percent rated kw load for 5 minutes. 3.2.6 Unbalanced load rating (three wire gener- ators only). - The unbalanced load rating shall be 15 percent of the rated fui1 load current unless the gen- erator rating is 100 Kw or less, in which case it shall be 25 percent. 3.2.7 Overspeed. - Generators sha
16、ll be designed and constructed to withstand safely an overspeed of 25 percent (see 4.4.7). 3.2.8 Parallel operation. - When specified (see 6.1) generators shall be designed for parallel oper- ation. 3.2.9 Ambient temperatures. - Generators shall be designed for operation in an ambient temperature of
17、 50“ Centigrade (C). 2 3.2.10 Ripple voltage. - At any load from no load to full load and considering only peak-to-peak volt- age values, the commutator ripple at any frequency from zero to 16 kilocycles shall not exceed 2 percent of the rated output voltage. 3.2.11 Voltage regulation. - At rated r.
18、 p. m. the following requirements shall apply: (a) With the field rheostat so adjusted that the generator is operating at rated voltage at no load, the drop in voltage shall be not more than 10 percent when rated load is applied to the generator (see 4.4.11). (b) With the field rheostat so adjusted
19、that the generator is operating at rated voltage at rated load, the rise in voltage shall not be more than 6 percent when the load is reduced to zero (see 4.4.11). (c) At any point on the voltage-load curve with the generator field rheostat adjusted as specified in (a) and (b) above, there shall be
20、no rise in voltage with increase in load, or any drop in voltage with a drop in load. 3.2.12 Prime movers. - Generators shall operate satisfactorily with the following types of prime movers as specified (see 6.1): Steam turbine Gas turbine Diesel engine Gasoline engine. 3.2.13 Responsibility of prim
21、e mover manufac- turer. - It shall be the responsibiiity of the prime mover manufacturer to provide a prime mover of sufficient capacity to drive the generator under ail conditions of load and overload specified herein (see 6.3). 3.3 Design and construction. - 3.3.1 Basic requirements. - Generators
22、shall conform to Specification MIL-E-917 and the require- ments specified herein. tures which will result in reliable and stable opera- tion with minimum need for adjustment and aign- ment, minimum frequency of failure and minimum requirements for maintenance. 3.3.3 Distribution system. - The distri
23、bution system shall be two-wire unless three-wire is speci- fied (see 6.1). 3.3.2 Reliability. - The design shaU include fea- 3.3.4 Winding. - Generators shall be either shunt- wound where no series field is provided or stabiiized shunt wound where a light series field winding is pro- vided to maint
24、ain the required voltage regulation. For stabilized shunt wound generators, at rated full Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-G-31 1 lC(SHIPS) load voltage and current, the ratio of series field ampere-turns to shunt field ampere-turn
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILG3111C1961GENERATORELECTRICDIRECTCURRENTNAVALSHIPBOARDUSE 海军 军舰 直流 发生器 PDF

链接地址:http://www.mydoc123.com/p-979352.html