DLA A-A-55458 D-2009 INTERRUPTER GROUND FAULT TWO-POLE THREE-WIRE 15-AMPERE.pdf
《DLA A-A-55458 D-2009 INTERRUPTER GROUND FAULT TWO-POLE THREE-WIRE 15-AMPERE.pdf》由会员分享,可在线阅读,更多相关《DLA A-A-55458 D-2009 INTERRUPTER GROUND FAULT TWO-POLE THREE-WIRE 15-AMPERE.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、Beneficial comments, recommendations, additions, deletions, clarifications, etc., and any data that may improve this document should be sent to: Defense Supply Center, Columbus, ATTN: DSCC-VAT, P.O. Box 3990, Columbus, OH 43218-3990, or email mailto:CircuitProtectdscc.dla.mil. Since contact informat
2、ion can change you may want to verify the currency of the address information using the ASSIST Online database at http:/assist.daps.dla.mil. AMSC N/A FSC 5925 INCH-POUND A-A-55458D 30 January 2009 SUPERSEDING A-A-55458C October 1, 2003 COMMERCIAL ITEM DESCRIPTION INTERRUPTER, GROUND FAULT, TWO-POLE,
3、 THREE-WIRE, 15-AMPERE The General Services Administration has authorized the use of this commercial item description for all federal agencies. 1. SCOPE. This commercial item description (CID) covers the general requirements for a 15-ampere ground fault interrupter. Ground fault interrupters covered
4、 by this CID are intended for commercial/industrial applications. 2. CLASSIFICATION/PART OR IDENTIFICATION NUMBER (PIN). This CID uses a classification system that is included in the PIN as shown in the following example (see 7.1). AA55458 - S B CID number Termination style (see table I) (S) for scr
5、ew terminals. (W) for wire leads. Color code (B) Brown (I) Ivory (R) Red (G) Gray (W) White 3. SALIENT CHARACTERISTICS. 3.1 Interface and physical dimensions. Ground fault interrupters supplied to this CID shall be as specified herein and shall meet the requirements of UL 943 for class A ground faul
6、t interrupters (see figure 1). 3.2. Ampere rating. The ampere rating shall be 15 amperes maximum. 3.3 Voltage rating. The voltage rating shall be 125 V ac maximum. 3.4 Frequency rating. The frequency rating shall be 60 Hz. Provided by IHSNot for ResaleNo reproduction or networking permitted without
7、license from IHS-,-,-A-A-55458D 2 NOTES: 1. Dimensions are in inches. 2. Unless otherwise specified, tolerance is .005 inch (0.13 mm). 3. Location of test and/or reset buttons optional. FIGURE 1. Configuration and dimensions. Inches mm 1.229 31.22 1.800 45.72 2.780 70.61 3.280 83.33 3.812 96.82 4.20
8、0 106.68 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-55458D 3 3.5 Trip threshold. This ground fault interrupter shall trip when a fault current to ground is 4-6 mA minimum. 3.6 Dimensions. Dimensions shall conform to NEMA standard WD 6 (refer
9、ence NEMA configuration 5-15R) (see figure 1). 3.7 Termination style. The termination style shall be either screw terminals or wire leads. 3.8 Wire size. The maximum wire size the screw terminal connectors shall accept is number 10 American Wire Gauge (AWG). The minimum wire size of the wire shall b
10、e number 14 AWG. 3.9 Wire lead length. The free length of the wire leads shall be 4 inches (101.6 millimeters) minimum. The free length of the ground lead shall be 6 inches (152.4 millimeters) minimum. 3.10 Marking. Ground fault interrupters or their unit package supplied to this CID shall be marked
11、 with the manufacturers (MFRs) standard commercial PIN and the ground fault interrupters shall bear the appropriate UL listing mark. (NOTE: The part number marked on the unit pack shall be the CID PIN.) 3.11 Recycled, recovered, or environmentally preferable materials. Recycled, recovered, or enviro
12、nmentally preferable materials should be used to the maximum extent possible provided that the material meets or exceeds the operational and maintenance requirements, and promotes economically advantageous life cycle costs. 3.12 Workmanship. Ground fault interrupters shall be processed in such a man
13、ner as to be uniform in quality and shall be free from other defects that will affect life, serviceability, or appearance. 4. REGULATORY REQUIREMENTS. The offeror/contractor is encouraged to use recovered materials to the maximum extent practicable, in accordance with 23.403 of the Federal Acquisiti
14、on Regulation (FAR). 5. PRODUCT CONFORMANCE PROVISIONS. 5.1 Product conformance. The products provided shall meet the salient characteristics of this CID, conform to the producers own drawings, specifications, standards, and quality assurance practices, and be the same product offered for sale in th
15、e commercial market. The Government reserves the right to require proof of such conformance. 5.2 Market acceptance. The following market acceptance criteria are necessary to document the quality of the product to be provided under this CID: a. The company producing the item must have been producing
16、a product meeting the requirements of this CID for at least 2 years. b. The company must have sold 1,000 units meeting this CID in the commercial marketplace over the past 2 years. 6. PACKAGING. Preservation, packing, and marking shall be as specified in the contract or order. 7. NOTES. 7.1 PIN. The
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAAA55458D2009INTERRUPTERGROUNDFAULTTWOPOLETHREEWIRE15AMPEREPDF

链接地址:http://www.mydoc123.com/p-686792.html