1、BRITISH STANDARD BS 5067:1985 Specification for Flameproof transformers for use in mines UDC 622.005:621.314.2213.34BS5067:1985 This British Standard, having been prepared under the directionof the Mining and Quarrying Requisites Standards Committee, was published under the authority of the Board of
2、 BSI and comes into effect on 31July1985 BSI 10-1999 First published January1974 First revision July1985 The following BSI references relate to the work on this standard: Committee reference MQE/15 Draft for comment83/78987 DC ISBN 0 580 14478 X Committees responsible for this British Standard The p
3、reparation of this British Standard was entrusted by the Mining and Quarrying Requisites Standards Committee (MQE/-) to Technical Committee MQE/15, upon which the following bodies were represented: Association of British Mining Equipment Companies BEAMA Transmission and Distribution Association Heal
4、th and Safety Executive National Coal Board Amendments issued since publication Amd. No. Date of issue CommentsBS5067:1985 BSI 10-1999 i Contents Page Committees responsible Inside front cover Foreword ii 1 Scope 1 2 General 1 3 Insulation and temperature rise 1 4 kVA Ratings 1 5 Voltages and connec
5、tions 1 6 Frequency 1 7 Voltage adjustment tappings 1 8 General design and construction 1 9 Lifting and anchoring of core 2 10 Removable covers 2 11 Wheels 2 12 Mounting flanges and terminals 2 13 Provision for cable terminations 7 14 Over-voltage protection and earthing 8 15 Marking and rating plat
6、es 8 Appendix A Information to be supplied by the purchaser with enquiry and order 10 Appendix B Earth fault protection 10 Figure 1 Example of a terminal marking plate showing standard items of information to be provided and their arrangement 1 Figure 2 Mounting flange at lower-voltage end of transf
7、ormer 3 Figure 3 Mounting flange at higher-voltage end of transformer (for voltages not exceeding6.6kV) 4 Figure 4 Mounting flange at higher-voltage end of transformer (for voltages exceeding6.6kV and up to11kV) 5 Figure 5 Equipment flange (for voltages not exceeding6.6kV) 6 Figure 6 Equipment flang
8、e (for voltages exceeding6.6kV and up to11kV) 7 Figure 7 Example of rating plate for flameproof transformer showing standard items of information to be provided and their arrangement 9 Figure 8 System b type earth fault protection circuit 11 Table 1 Clearance and creepage distances in air 7 Publicat
9、ions referred to Inside back coverBS5067:1985 ii BSI 10-1999 Foreword This revision of BS5067 has been prepared under the direction of the Mining and Quarrying Requisites Standards Committee. It extends the scope of the1974 edition to include higher voltages up to11kV. BS5067:1974 is superseded and
10、withdrawn. Transformers complying with this standard are suitable for Group I enclosures and may also be suitable for other groups of gases (seeBS4683-2 and BS229). NOTEFor the purposes of this British Standard, the IEC convention for expressing the symbol for the unit kilovolt amperes, i.e.kVA, has
11、 been used as this is in general use in the electrical industry, rather than the convention indicated in BS5775 (ISO31). Attention is drawn to the Health and Safety at Work etc. Act1974, the Factories Act1961, the Mines and Quarries Act1954, the Regulations made under these Acts, and also any other
12、appropriate statutory requirements or Bye-laws. These place responsibility for complying with certain specific safety requirements on the manufacturer and the user. The address of the recognized certification authority in the UK for Group I (coal mining) apparatus for flameproof purposes is as follo
13、ws: Health and Safety Executive HSE (M) Certification Support Unit Harpur Hill Buxton Derbyshire SK179JN. A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct application. Compliance with a British Sta
14、ndard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pagesi andii, pages1 to12, an inside back cover and a back cover. This standard has been updated (see copyright date) and may have had amendments incorporat
15、ed. This will be indicated in the amendment table on the inside front cover.BS5067:1985 BSI 10-1999 1 1 Scope This British Standard specifies design requirements for dry-type flameproof three-phase power transformers intended for use below ground in mines. This standard does not apply to transformer
16、s of the types covered by BS2538 1)and BS5126-4. Appendix A lists information to be supplied by the purchaser with the enquiry and order. NOTEThe titles of the publications referred to in this standard are listed on the inside back cover. 2 General Transformers shall comply with BS171 for the rating
17、 and performance of the main component within the flameproof enclosure, except where specifically modified or extended in this standard. 3 Insulation and temperature rise The insulation materials of components within the transformer enclosure shall comply with either classH or class C of BS2757. The
18、 temperature rise of any part of the external surface of the enclosure(s) shall not exceed60 C when the transformer is tested at normal continuous full load current with the rated primary voltage applied to the principal tapping as described in3.6 of BS171-2:1978. 4 kVA Ratings The three-phase kVA r
19、atings shall be one of the following: 50,150,300,500,750 and1000. 5 Voltages and connections 5.1 Voltages The no-load voltages shall be selected from the following: NOTESeeAppendix A for information that should be provided by the purchaser. 5.2 Connections The connections shall be either delta-star
20、or star-star, as designated by the symbols Dy11 or Yy0, respectively, in Figure5a of BS171-4:1978. 6 Frequency The designed frequency of operation shall be50Hz. 7 Voltage adjustment tappings The primary windings shall be provided with tappings at 5% and10% of the rated voltage in addition to the pri
21、ncipal tapping at the rated primary voltage. A readily accessible off-circuit selecting device, having the positions clearly marked, for example as shown in Figure 1, shall be provided to enable the tappings to be changed. 8 General design and construction 8.1 Flameproof construction Transformers sh
22、all comply with Group I enclosures of either BS4683-2 or BS5501-1 and BS5501-5. 1) Under revision. Nominal primary voltage: 3.3kV,6.6kV,11kV No-load secondary voltage: 565V,1130V, 3.4kV,6.8kV Figure 1 Example of a terminal marking plate showing standard items ofinformationtobeprovided and their arra
23、ngementBS5067:1985 2 BSI 10-1999 Transformers designed before the date of publication of this standard and certified as flameproof in compliance with BS229 for Group I enclosures shall be deemed to comply with this standard if they comply with all other requirements of this standard. 8.2 Materials T
24、he transformer enclosure shall be of mild steel. NOTE 1It is essential that enclosures should be substantially constructed sufficient to withstand rough conditions of handling, e.g.being slung or pushed into or out of cages, and being transported below ground. No part external to the flameproof encl
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS50671985SPECIFICATIONFORFLAMEPROOFTRANSFORMERSFORUSEINMINES 矿山 防火 变压器 规范 PDF

链接地址:http://www.mydoc123.com/p-544829.html