ASTM F2249-2003(2015) Standard Specification for In-Service Test Methods for Temporary Grounding Jumper Assemblies Used on De-Energized Electric Power Lines and Equipment《断电电源线和设备用.pdf
《ASTM F2249-2003(2015) Standard Specification for In-Service Test Methods for Temporary Grounding Jumper Assemblies Used on De-Energized Electric Power Lines and Equipment《断电电源线和设备用.pdf》由会员分享,可在线阅读,更多相关《ASTM F2249-2003(2015) Standard Specification for In-Service Test Methods for Temporary Grounding Jumper Assemblies Used on De-Energized Electric Power Lines and Equipment《断电电源线和设备用.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F2249 03 (Reapproved 2015)Standard Specification forIn-Service Test Methods for Temporary Grounding JumperAssemblies Used on De-Energized Electric Power Lines andEquipment1This standard is issued under the fixed designation F2249; the number immediately following the designation indicat
2、es the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 These specifications cover the in-service ins
3、pection andelectrical testing of temporary protective grounding jumperassemblies which have been used by electrical workers in thefield.1.2 These specifications discuss methods for testing ground-ing jumper assemblies, which consist of the flexible cables,ferrules, clamps and connectors used in the
4、temporary protec-tive grounding of de-energized circuits.1.3 Manufacturing specifications for these groundingjumper assemblies are in Specifications F855.1.4 The application, care, use, and maintenance of thisequipment are beyond the scope of this specification.1.5 Units of measurement used in this
5、specification are inthe Metric system (SI) with English units given in parentheses.1.6 The following safety hazards caveat pertains only to thetest portions of this specification. This standard does notpurport to address all of the safety concerns, if any, associatedwith its use. It is the responsib
6、ility of the user of this standardto establish appropriate safety and health practices anddetermine the applicability of regulatory requirements prior touse.2. Referenced Documents2.1 ASTM Standards:2B193 Test Method for Resistivity of Electrical ConductorMaterialsF855 Specifications for Temporary P
7、rotective Grounds to BeUsed on De-energized Electric Power Lines and Equip-ment2.2 IEEE Standards:3IEEE Standard 801986 IEEE Guide for Safety in ACSubstation GroundingIEEE Standard 10481990 IEEE Guide for the ProtectiveGrounding of Power Lines3. Terminology3.1 Definitions of Terms Specific to This S
8、tandard:3.1.1 grounding jumper assemblygrounding cable withconnectors and ground clamps attached, also called a ground-ing jumper or a protective ground assembly installed tempo-rarily on de-energized electric power circuits for the purpose ofpotential equalization and to conduct a short circuit cur
9、rent fora specified duration (time).4. Significance and Use4.1 Grounding jumper assemblies can be damaged by roughhandling, long term usage, weathering, corrosion, or a combi-nation thereof. This deterioration may be both physical andelectrical.4.2 The test procedures in this specification provide a
10、nobjective means of determining if a grounding jumper assem-bly meets minimum electrical specifications. These methodspermit testing of grounding jumper assemblies under con-trolled conditions.4.3 Each responsible entity must determine the requiredsafety margin for their workers during electrical fa
11、ult condi-tions. Guidelines for use in the determination of these condi-tions are beyond the scope of this specification and can befound in such standards as IEEE Standard 801986 and IEEEStandard 10481990.4.4 Mechanical damage, other than broken strands, may notsignificantly affect the cable resista
12、nce. Close manual andvisual inspection is required to detect some types of mechani-cal damage.4.5 The test procedures in this specification should beperformed at a time interval established by the user to ensure1This specification is under the jurisdiction of ASTM Committee F18 onElectrical Protecti
13、ve Equipment for Workers and is the direct responsibility ofSubcommittee F18.45 on Mechanical Apparatus.Current edition approved May 1, 2015. Published July 2015. Originally approvedin 2003. Last previous edition approved in 2009 as F2249-03(2009). DOI:10.1520/F2249-03R15.2For referenced ASTM standa
14、rds, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from the Institute of Electrical and Electronics Engineers, Inc. (IEEE)1828 L
15、 St., NW, Suite 1202, Washington, CD 200365104.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1that defective grounding jumper assemblies are detected andremoved from service in a timely manner.4.6 Retest the grounding jumper assembly
16、 after performingany maintenance, in order to ensure its integrity.5. Inspection of Grounding Jumper Assemblies5.1 Visual inspection shall be made of all grounding jumperassemblies prior to testing.5.1.1 If the following defects are evident, the groundingjumpers may be rejected without electrical te
17、sting:5.1.1.1 Cracked or broken ferrules and clamps,5.1.1.2 Exposed broken strands,5.1.1.3 Cut or badly mashed or flattened cable,5.1.1.4 Extensively damaged cable- covering material,5.1.1.5 Swollen cable jacket or soft spots, indicating inter-nal corrosion, and5.1.1.6 Cable strands with a black dep
18、osit on them.5.1.2 Grounding jumper assemblies which are visually de-fective shall be removed from service and permanentlymarked, tagged or destroyed (if beyond repair) to preventre-use.5.1.3 Before the grounding jumper assembly can be placedback in service, it must pass the inspection requirements
19、in5.1.1, and the electrical requirements in Section 7.5.1.4 All physical connections should be checked for tight-ness with specified torque values.6. Cleaning and Measuring of Grounding JumperAssembly Prior to Electrical Testing6.1 Identify the cable gage (AWG) and a make a precisemeasurement of the
20、 cable length. See Fig. 1.6.2 Thoroughly clean the jaws of the clamps with a stiffwire brush.6.3 Attach the grounding jumper assembly clamps firmly tothe test set.7. Electrical Requirements7.1 The user must select the test method with the desiredprecision and repeatability. The test instrument shoul
21、d besufficiently accurate to detect at least a one foot or less changein cable length to ensure that the cable meets requirements.7.2 Each method must take into account a precise cableresistance per foot and the length of the cable being tested.7.3 Electrical tests relative to this standard are:7.3.
22、1 DC resistance measurements,7.3.2 AC impedance measurements, and7.3.3 Temperature rise measurements (supplementarymethod).7.4 DC Resistance or AC Impedance MethodEquipmentrequired includes:7.4.1 A minimum 10 A dc source controllable to 5 % ofoutput current, short circuit protected, or7.4.2 A minimu
23、m 10 A ac source controllable to 5 % ofoutput current, short circuit protected.7.4.3 Measuring method for measurements of cable lengthcalibrated in inches or centimetres.7.5 In-Service Electrical Resistance Pass/Fail CriteriaThe pass/fail criterion of a grounding jumper assembly isbased on the resis
24、tance value of the assembly (cable, ferrulesand clamps) which is higher than the established resistancevalue for new assemblies. This increase in resistance accountsfor the expected normal deterioration of the assembly due toaging, contamination and corrosion, particularly in the contactareas of the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF224920032015STANDARDSPECIFICATIONFORINSERVICETESTMETHODSFORTEMPORARYGROUNDINGJUMPERASSEMBLIESUSEDONDEENERGIZEDELECTRICPOWERLINESANDEQUIPMENT

链接地址:http://www.mydoc123.com/p-538205.html