ASTM E1105-2015 Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows Skylights Doors and Curtain Walls by Uniform or Cyclic Static Air Pr.pdf
《ASTM E1105-2015 Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows Skylights Doors and Curtain Walls by Uniform or Cyclic Static Air Pr.pdf》由会员分享,可在线阅读,更多相关《ASTM E1105-2015 Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows Skylights Doors and Curtain Walls by Uniform or Cyclic Static Air Pr.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E1105 00 (Reapproved 2008)E1105 15Standard Test Method forField Determination of Water Penetration of InstalledExterior Windows, Skylights, Doors, and Curtain Walls, byUniform or Cyclic Static Air Pressure Difference1This standard is issued under the fixed designation E1105; the number
2、immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1
3、This test method covers the determination of the resistance of installed exterior windows, curtain walls, skylights, and doorsto water penetration when water is applied to the outdoor face and exposed edges simultaneously with a static air pressure at theoutdoor face higher than the pressure at the
4、indoor face.1.2 This test method is applicable to any curtain-wall area or to windows, skylights, or doors alone. It is intended primarily fordetermining the resistance to water penetration through such assemblies for compliance with specified performance criteria, butit may also be used to determin
5、e the resistance to penetration through the joints between the assemblies and the adjacentconstruction. Other procedures may be appropriate to identify sources of leakage.1.3 This test method addresses water penetration through a manufactured assembly. Water that penetrates the assembly, but doesnot
6、 result in a failure as defined herein, may have adverse effects on the performance of contained materials such as sealants andinsulating or laminated glass. This test method does not address these issues.1.4 The proper use of this test method requires a knowledge of the principles of pressure measu
7、rement.1.5 The values stated in SIinch-pound units are to be regarded as the standard. The inch-pound equivalents of SI units may beapproximate.standard. The values given in parentheses are mathematical conversions to SI units that are provided for informationonly and are not considered standard.1.6
8、 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use. For specific hazard
9、 statements, see 7.1.2. Referenced Documents2.1 ASTM Standards:2E331 Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static AirPressure DifferenceE547 Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by C
10、yclic StaticAir PressureDifferenceE631 Terminology of Building Constructions3. Terminology3.1 DefinitionsFor definitions of general terms relating to building construction used in this test method, see TerminologyE631.3.2 Definitions of Terms Specific to This Standard:3.2.1 specimen, nthe entire ass
11、embled unit submitted for test as installed in the exterior wall of a building.3.2.1.1 Discussion1 This test method is under the jurisdiction ofASTM Committee E06 on Performance of Buildings and is the direct responsibility of Subcommittee E06.51 on Performanceof Windows, Doors, Skylights and Curtai
12、n Walls.Current edition approved April 1, 2008Aug. 1, 2015. Published May 2008September 2015. Originally approved in 1986. Last previous edition approved in 20002008 asE1105 00.E1105 00(2008). DOI: 10.1520/E1105-00R08.10.1520/E1105-15.2 For referencedASTM standards, visit theASTM website, www.astm.o
13、rg, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what chang
14、es have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the offici
15、al document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1The test specimen consists of the major components of the assembly, including all joints, cracks, or openings between suchcomponents and any panning, receptors, extenders, si
16、lls, mullions, or other parts or components used for assembling anyinstallation. The joints between assemblies and the openings into which they are mounted (masonry openings, for example) arenot part of the test specimen. However, these joints may be tested by this procedure.3.2.2 test pressure diff
17、erence, nthe specified difference in static air pressure across the closed and locked or fixed specimenexpressed in pascalslbf/ft2 (lbf/ft(pascals).2).3.2.3 water penetration, npenetration of water beyond a plane parallel to the glazing (the vertical plane) intersecting theinnermost projection of th
18、e test specimen, not including interior trim and hardware, under the specified conditions of air pressuredifference across the specimen. For products with non-planer surfaces (domes, vaults, pyramids, etc.) the plane defining waterpenetration is the plane defined by the innermost edges of the unit f
19、rame.4. Summary of Test Method4.1 This test method consists of sealing a chamber to the interior or exterior face of specimen to be tested, supplying air to achamber mounted on the exterior or exhausting air from a chamber mounted on the interior, at the rate required to maintain thetest pressure di
20、fference across the specimen while spraying water onto the outdoor face of the specimen at the required rate andobserving any water penetration.5. Significance and Use5.1 This test method is a standard procedure for determining the resistance to water penetration under uniform or cyclic staticair pr
21、essure differences of installed exterior windows, skylights, curtain walls, and doors. The air-pressure differences acting acrossa building envelope vary greatly. These factors should be considered fully prior to specifying the test pressure difference to be used.NOTE 1In applying the results of tes
22、ts by this test method, note that the performance of a wall or its components, or both, may be a function of properinstallation and adjustment. In service, the performance will also depend on the rigidity of supporting construction and on the resistance of componentsto deterioration by various cause
23、s, vibration, thermal expansion and contraction, and so forth. It is difficult to simulate the identical complex wettingconditions that can be encountered in service, with large wind-blown water drops, increasing water drop impact pressures with increasing wind velocity,and lateral or upward moving
24、air and water. Some designs are more sensitive than others to this upward moving water.NOTE 2This test method does not identify unobservable liquid water which may penetrate into the test specimen.5.2 Laboratory tests are designed to give an indication of the performance of an assembly. Field perfor
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME11052015STANDARDTESTMETHODFORFIELDDETERMINATIONOFWATERPENETRATIONOFINSTALLEDEXTERIORWINDOWSSKYLIGHTSDOORSANDCURTAINWALLSBYUNIFORMORCYCLICSTATICAIRPRPDF

链接地址:http://www.mydoc123.com/p-527915.html