ASTM D2656-2006 Standard Specification for Crosslinked Polyethylene Insulation for Wire and Cable Rated 2001 to 35 000 V《额定电压 2001~35000V的电线和电缆用交联聚乙烯绝缘材料的标准规范》.pdf
《ASTM D2656-2006 Standard Specification for Crosslinked Polyethylene Insulation for Wire and Cable Rated 2001 to 35 000 V《额定电压 2001~35000V的电线和电缆用交联聚乙烯绝缘材料的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM D2656-2006 Standard Specification for Crosslinked Polyethylene Insulation for Wire and Cable Rated 2001 to 35 000 V《额定电压 2001~35000V的电线和电缆用交联聚乙烯绝缘材料的标准规范》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 2656 06An American National StandardStandard Specification forCrosslinked Polyethylene Insulation for Wire andCable Rated 2001 to 35 000 V1This standard is issued under the fixed designation D 2656; the number immediately following the designation indicates the year oforiginal adoptio
2、n or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This specification covers a crosslinked polyethyleneinsulation for electr
3、ical wires and cables for conductor sizes 8AWG (8.37 mm2) and larger. The base polymer of thisinsulation consists substantially of polyethylene.1.2 This type of insulation is suitable for use on powercables in wet and dry locations at conductor temperatures notexceeding 90 C for continuous operation
4、, 130 C for emer-gency overload conditions, and 250 C for short-circuit con-ditions. It is considered suitable for all sizes and voltageclassifications of single- and multiple-conductor power cablesat voltage ratings of 2001 to 35 000 V phase-to-phase at the100 % insulation level and at voltage rati
5、ngs of 2001 to 25 000V at the 133 % insulation level as listed in Table 1C of TestMethods D 470.1.3 Materials covered by this specification are not sunlight-and weather-resistant unless they are carbon black pigmentedor contain an additive system designed for this protection.1.4 In many instances th
6、e insulation cannot be tested unlessit has been formed around a conductor. Therefore, tests aredone on insulated wire in this standard solely to determine therelevant property of the insulation and not to test the conductoror completed cable.1.5 Whenever two sets of values are presented, in differen
7、tunits, the values in the first set are the standard, while those inparentheses are for information only.2. Referenced Documents2.1 ASTM Standards:2D 470 Test Methods for Crosslinked Insulations and Jacketsfor Wire and CableD 1248 Specification for Polyethylene Plastics ExtrusionMaterials for Wire a
8、nd CableD 1711 Terminology Relating to Electrical InsulationD 2765 Test Methods for Determination of Gel Content andSwell Ratio of Crosslinked Ethylene Plastics2.2 ICEA Standard:ICEAT-28-562 Test Method for Measurement of Hot Creepof Polymeric Insulation33. Terminology3.1 Definitions:3.1.1 For defin
9、itions of terms used in this specification referto Terminology D 1711.3.2 Definitions of Terms Specific to This Standard:3.2.1 aging (act of), nexposure of materials to air at 121C for 168 h.4. Physical Properties4.1 The requirements for the insulation are listed in Table 1.5. Electrical Requirement
10、s Electrical Requirements5.1 Order of TestingPerform the partial-discharge, acvoltage, insulation resistance, and dc voltage tests in that orderwhen any of these tests are specified. The sequence for othertesting is not specified.5.2 Partial Discharge (Corona) Extinction VoltageEachlength of complet
11、ed power cable with shielded conductorsshall comply with the minimum level specified in Table 2.Conduct the tests in accordance with Test Methods D 470.5.3 AC Voltage TestSubject the wires and cables to an actest voltage for a period of 5 min. Unless otherwise specified,omit this test if the dc volt
12、age test described in 5.5 is to beperformed. Test at a voltage of 125 V/mil (5 kV/mm) based onthe specified nominal thickness of insulation for the ratedcircuit voltage, phase to phase. Conduct the test in accordancewith Test Methods D 470.5.4 Insulation ResistanceThe insulated conductor shallhave a
13、n insulation resistance equal to or greater than thatcorresponding to a constant of 20 000 at 60 F (15.6 C).When the temperature of the water in which the insulation istested differs from 60 F, apply a correction factor. Table 2 ofTest Methods D 470 contains the correction factors. Each1This specifi
14、cation is under the jurisdiction of ASTM Committee D09 onElectrical and Electronic Insulating Materials and is the direct responsibility ofSubcommittee D 09.18 on Solid Insulations, Non-Metallic Shieldings, and Cover-ings for Electrical and Telecommunications Wires and Cables.Current edition approve
15、d Oct. 1, 2006. Published October 2006. Originallyapproved in 1967. Last previous edition approved in 2000 as D 2656 00.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer
16、 to the standards Document Summary page onthe ASTM website.3Available from The Insulated Cable Engineers Association, Inc. (ICEA), P.O.Box 1568, Carrollton, GA 30112, http:/.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive, PO Box
17、 C700, West Conshohocken, PA 19428-2959, United States.insulation manufacturer can furnish the 1 F coefficient for theinsulation material by using the procedure given in TestMethods D 470. Multiply the measured value by the correctionfactor to obtain the insulation-resistance value corrected to 60F.
18、5.4.1 Where a nonconducting separator is applied betweenthe conductor and insulation or where an insulated conductor iscovered with a nonmetallic jacket so that the insulationresistance can be measured only on the completed assembly,the required insulation resistance shall be at least 60 % of thatre
19、quired for the primary insulation based on the nominalthickness of that insulation.5.5 DC Voltage TestAfter the insulation resistance test hasbeen completed, subject wires and cables rated 5001 V andabove to a dc voltage test for a period of 15 min. Use a dcvoltage three times the ac voltage based o
20、n the specifiednominal thickness of insulation for the rated circuit voltage,phase to phase. Conduct the tests in accordance with TestMethods D 470.5.5.1 Upon completion of the insulation resistance test, eachnonshielded insulated conductor rated up to 5000 V shallwithstand for 5 min a dc test volta
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD26562006STANDARDSPECIFICATIONFORCROSSLINKEDPOLYETHYLENEINSULATIONFORWIREANDCABLERATED2001TO35000V

链接地址:http://www.mydoc123.com/p-513253.html