《ASTM D2655-2000(2006) Standard Specification for Crosslinked Polyethylene Insulation for Wire and Cable Rated 0 to 2000 V《额定电压为0到2000V的电线和电缆用交联聚乙烯绝缘材料的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM D2655-2000(2006) Standard Specification for Crosslinked Polyethylene Insulation for Wire and Cable Rated 0 to 2000 V《额定电压为0到2000V的电线和电缆用交联聚乙烯绝缘材料的标准规范》.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 2655 00 (Reapproved 2006)An American National StandardStandard Specification forCrosslinked Polyethylene Insulation for Wire and CableRated 0 to 2000 V1This standard is issued under the fixed designation D 2655; the number immediately following the designation indicates the year ofori
2、ginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers a crosslinked polyethyleneinsulatio
3、n for electrical wires and cables in conductor sizes 14AWG 2.08 mm2 and larger. The base polymer of thisinsulation consists substantially of polyethylene or a polyeth-ylene copolymer.1.2 This type of insulation is suitable for continuous use onpower cables in wet and dry locations, for voltage ratin
4、gs notexceeding 2000 V and at conductor temperatures not exceeding90 C for normal operation. For copper conductors, theinsulation may be applied over the uncoated metal.1.3 Materials covered by this specification are not sunlightand weather resistant unless they are carbon black pigmentedor contain
5、an additive system designed for this protection.1.4 In many instances the insulation cannot be tested unlessit has been formed around a conductor. Therefore, tests aredone on insulated wire in this standard solely to determine therelevant property of the insulation and not to test the conductoror co
6、mpleted cable.1.5 Whenever two sets of values are presented, in differentunits, the values in the first set are the standard, while those inparentheses are for information only.2. Referenced Documents2.1 ASTM Standards:2D 470 Test Methods for Crosslinked Insulations and Jacketsfor Wire and CableD 12
7、48 Specification for Polyethylene Plastics ExtrusionMaterials for Wire and CableD 1711 Terminology Relating to Electrical InsulationD 2765 Test Methods for Determination of Gel Content andSwell Ratio of Crosslinked Ethylene Plastics2.2 ICEA Standard:ICEAT-28-562 Test Method for Measurement of Hot Cr
8、eepof Polymeric Insulations33. Terminology3.1 Definitions:3.1.1 For definitions of terms used in this specification referto Terminology D 1711.3.2 Definitions of Terms Specific to This Standard:3.2.1 aging (act of), nexposure of materials to air at 121C for 168 h.4. Physical Properties4.1 The requir
9、ements for the insulation are listed in Table 1.5. Electrical Requirements5.1 Order of TestingPerform the ac voltage, insulationresistance, and dc voltage tests in that order when any of thesetests are required. The sequence for other testing is notspecified.5.2 AC Voltage TestSubject wires and cabl
10、es to an ac testvoltage for a period of 5 min. Unless otherwise specified, omitthis test if the dc voltage test described in 5.4 is to beperformed. Test at a voltage of 100 V/mil 4 kV/mm based onthe specified nominal thickness of insulation for the ratedcircuit voltage, phase to phase. Conduct the t
11、ests in accordancewith Test Methods D 470.5.3 Insulation ResistanceThe insulated conductor shallhave an insulation resistance equal to or greater than thatcorresponding to a constant of 10 000 at 60 F 15.6 C.When the temperature of the water in which the insulation istested differs from 60 F, apply
12、a correction factor. Table 2 ofTest Methods D 470 contains the correction factors. Eachinsulation manufacturer can furnish the 1 F coefficient for theinsulation material by using the procedure given in TestMethods D 470. Multiply the measured value by the correctionfactor to obtain the insulation-re
13、sistance value corrected to 60F.5.3.1 Where a nonconducting separator is applied betweenthe conductor and insulation or where an insulated conductor is1This specification is under the jurisdiction of ASTM Committee D09 onElectrical and Electronic Insulating Materials and is the direct responsibility
14、 ofSubcommittee D09.18 on Solid Insulations, Non-Metallic Shieldings, and Cover-ings for Electrical and Telecommunications Wires and Cables.Current edition approved April 1, 2006. Published April 2006. Originallyapproved in 1967. Last previous edition approved in 2000 as D 2655 00.2For referenced AS
15、TM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from Insulated Cable Engineers Association, P. O. Box 440, SouthYarm
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD265520002006STANDARDSPECIFICATIONFORCROSSLINKEDPOLYETHYLENEINSULATIONFORWIREANDCABLERATED0TO2000V

链接地址:http://www.mydoc123.com/p-513250.html