ASTM D1816-2012 Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using VDE Electrodes《用VDE电极测量绝缘油介电击穿电压的标准试验方法》.pdf
《ASTM D1816-2012 Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using VDE Electrodes《用VDE电极测量绝缘油介电击穿电压的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D1816-2012 Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using VDE Electrodes《用VDE电极测量绝缘油介电击穿电压的标准试验方法》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D1816 12Standard Test Method forDielectric Breakdown Voltage of Insulating Liquids UsingVDE Electrodes1This standard is issued under the fixed designation D1816; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year
2、 of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This test method covers the determination of the dielec-tric breakdown voltage of insulating liquids (oils of pet
3、roleumorigin, silicone fluids, high fire-point mineral electrical insu-lating oils, synthetic ester fluids and natural ester fluids). Thistest method is applicable to insulating liquids commonly usedin cables, transformers, oil circuit breakers, and similar appa-ratus as an insulating and cooling me
4、dium. Refer to Terminol-ogy D2864 for definitions used in this test method.1.2 This test method is sensitive to the deleterious effects ofmoisture in solution especially when cellulosic fibers arepresent in the liquid. It has been found to be especially usefulin diagnostic and laboratory investigati
5、ons of the dielectricbreakdown strength of insulating liquid in insulating systems.21.3 This test method is used to judge if the VDE electrodebreakdown voltage requirements are met for insulating liquids.This test method should be used as recommended by profes-sional organization standards such as I
6、EEE C57.106.1.4 This test method may be used to obtain the dielectricbreakdown of silicone fluid as specified in Test Method D2225and Specification D4652, provided that the discharge energyinto the sample is less than 20 mJ (milli joule) per breakdownfor five consecutive breakdowns.1.5 Both the metr
7、ic and the alternative inch-pound units areacceptable.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility
8、of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:3D235 Specification for Mineral Spirits (Petroleum Spirits)(Hydrocarbon Dry Cleaning Solvent)D923 Practices for Sampling Electrical Insulating LiquidsD2225 Test Methods for Silicone Fluids Used for ElectricalInsulationD
9、2864 Terminology Relating to Electrical Insulating Liq-uids and GasesD3487 Specification for Mineral Insulating Oil Used inElectrical ApparatusD4652 Specification for Silicone Fluid Used for ElectricalInsulationD6871 Specification for Natural (Vegetable Oil) Ester FluidsUsed in Electrical Apparatus2
10、.2 IEEE Standard:Standard 4 IEEE Standard Techniques for High VoltageTesting4C57.106 Guide for Acceptance and Maintenance of Insulat-ing Oil in Equipment43. Significance and Use3.1 The dielectric breakdown voltage of an insulating liquidis of importance as a measure of the liquids ability towithstan
11、d electric stress without failure. The dielectric break-down voltage serves to indicate the presence of contaminatingagents such as water, dirt, cellulosic fibers, or conductingparticles in the liquid, one or more of which may be present insignificant concentrations when low breakdown voltages areob
12、tained. However, a high dielectric breakdown voltage doesnot necessarily indicate the absence of all contaminants; it maymerely indicate that the concentrations of contaminants that arepresent in the liquid between the electrodes are not largeenough to deleteriously affect the average breakdown volt
13、ageof the liquid when tested by this test method (see AppendixX1.)1This test method is under the jurisdiction of ASTM Committee D27 onElectrical Insulating Liquids and Gasesand is the direct responsibility of Subcom-mittee D27.05 on Electrical Test.Current edition approved June 15, 2012. Published J
14、uly 2012. Originallyapproved in 1960 as D1816 60 T. Last previous edition approved in 2004 asD1816 04. DOI: 10.1520/D1816-12.2Supporting data is available from ASTM Headquarters. Request RR:D27-1006.3For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service
15、 at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.4Available from the Institute of Electrical and Electronic Engineers, Inc., POBox 1331, Piscataway, NJ 08855.*A Summary of Changes section appears at the end of t
16、his standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States13.2 This test method is used in laboratory or field tests. Forfield breakdown results to be comparable to laboratory results,all criteria including room temperature (20 to 30
17、C) must bemet.4. Electrical Apparatus4.1 In addition to this section, use IEEE Standard 4 todetermine other requirements necesary for conducting testmeasurements, and maintaining error limits using alternatingvoltages. Procedures to ensure accuracy should follow therequirements of IEEE Standard 4. C
18、alibration(s) shall betraceable to national standards and calibration should beverified annually or more often to ensure accuracy require-ments. IEEE Standard 4 is required during the manufacturingof the test apparatus and utilized during calibration of theequipment.4.1.1 Test VoltageThe test voltag
19、e shall be an alternatingvoltage having a frequency in the range from 45 to 65 Hz,normally referred to as power-frequency voltage. The voltagewave shape should approximate a sinusoid with both halfcycles closely alike, and it should have a ratio of peak-to-rmsvalues equal to the square root of 2 wit
20、hin 65%.4.1.2 Generation of the Test Voltage The test voltage isgenerally supplied by a transformer or resonant circuit. Thevoltage in the test circuit should be stable enough to beunaffected by varying current flowing in the capacitive andresistive paths of the test circuit. Non-disruptive discharg
21、es inthe test circuit should not reduce the test voltage to such anextent, and for such a time, that the disruptive discharge(breakdown) voltage of the test specimen is significantlyaffected. In the case of a transformer, the short-circuit currentdelivered by the transformer should be sufficient to
22、maintainthe test voltage within 3 % during transient current pulses ordischarges, and a short circuit current of 0.1 A may suffice.4.1.3 Disruptive Voltage Measurement Design the mea-surement circuit so the voltage recorded at the breakdown isthe maximum voltage across the test specimen immediatelyp
23、rior to the disruptive breakdown, with an error no greater than3%.4.2 Circuit-Interrupting Equipment Design the circuitused to interrupt the disruptive discharge through the specimento operate when the voltage across the specimen has collapsedto less than 100 V. It is recommended that the circuit de
24、signlimit the disruptive current duration and magnitude to lowvalues that will minimize damage to the electrodes and limitformation of non-soluble materials resulting from the break-down, but consistent with the requirements of 4.1.2, but in nocase should the short-circuit current exceed 1 mA/kV ofa
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD18162012STANDARDTESTMETHODFORDIELECTRICBREAKDOWNVOLTAGEOFINSULATINGLIQUIDSUSINGVDEELECTRODES VDE

链接地址:http://www.mydoc123.com/p-510511.html