ASTM C1015-2006 Standard Practice for Installation of Cellulosic and Mineral Fiber Loose-Fill Thermal Insulation《纤维素和矿物纤维松充填热绝缘料装配的标准规范》.pdf
《ASTM C1015-2006 Standard Practice for Installation of Cellulosic and Mineral Fiber Loose-Fill Thermal Insulation《纤维素和矿物纤维松充填热绝缘料装配的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1015-2006 Standard Practice for Installation of Cellulosic and Mineral Fiber Loose-Fill Thermal Insulation《纤维素和矿物纤维松充填热绝缘料装配的标准规范》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 1015 06Standard Practice forInstallation of Cellulosic and Mineral Fiber Loose-FillThermal Insulation1This standard is issued under the fixed designation C 1015; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the ye
2、ar of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This practice covers procedure
3、s for the installation ofcellulosic and mineral fiber loose-fill insulation in ceilings,attics, and floor and wall cavities of new or existing housingand other framed buildings.1.2 This practice applies only to the installation of dryloose-fill thermal insulation consisting of cellulosic materialsor
4、 mineral fiber by pneumatic or pouring application.1.3 This practice covers the installation process from pre-installation inspection through post-installation procedure. Itdoes not cover the production of the insulation materials.1.4 This practice is not intended to replace the manufactur-ers insta
5、llation instructions, but shall be used in conjunctionwith such instructions. This practice is not intended to super-sede local, state, or federal codes.1.5 This practice assumes that the installer possesses a goodworking knowledge of the applicable codes and regulations,safety practices, tools, equ
6、ipment, and methods necessary forthe installation of thermal insulation materials. It also assumesthat the installer understands the fundamentals of residentialconstruction that affect the installation of insulation.1.6 The values stated in inch-pound units are to be regardedas standard. The values
7、given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.7 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establi
8、sh appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For specificprecautionary statements, see Section 5.2. Referenced Documents2.1 ASTM Standards:2C 168 Terminology Relating to Thermal InsulationC 739 Specification for Cellulosic Fiber
9、 Loose-Fill ThermalInsulationC 755 Practice for Selection of Water Vapor Retarders forThermal InsulationC 764 Specification for Mineral Fiber Loose-Fill ThermalInsulation2.2 NFPA Standards:3NFPA 31 Standard for the Installation of Oil BurningEquipmentNFPA 54 National Fuel Gas CodeNFPA 70 National El
10、ectrical CodeNFPA 211 Standard for Chimneys, Fireplaces, Vents andSolid-Fuel Burning Appliances2.3 ICC Document:4International Residential Code 20032.4 Federal Standard:5FTC Trade Regulation Rule 16 CRF 460, Labeling andAdvertising of Home Insulation3. Terminology3.1 DefinitionsFor definitions of te
11、rms used in this prac-tice, see Terminology C 168.3.2 Definitions of Terms Specific to This Standard:1This practice is under the jurisdiction of ASTM Committee C16 on ThermalInsulation and is the direct responsibility of Subcommittee C16.23 on Blanket andLoose Fill Insulation.Current edition approve
12、d May 1, 2006. Published May 2006. Originallyapproved in 1984. Last previous edition approved in 2002 as C 1015 02.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to t
13、he standards Document Summary page onthe ASTM website.3Available from National Fire Protection Association (NFPA), 1 BatterymarchPark, Quincy, MA 02269-9101.4Available from International Code Council (ICC), 5203 Leesburg Pike, Suite600, Falls Church, VA 22041.5Federal Register Vol 70, No 103, May 31
14、, 2005. Available from NationalArchives and Records Administration, 8601 Adelphi Road, College Park Maryland,207406001.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2.1 installerthe person or persons who apply thermalinsulation m
15、aterials in residential buildings whether or not suchperson or persons have contracted with the owner to performthe work.3.2.2 cellulosic loose-fill thermal insulating materialsthose materials that meet the minimum requirements specifiedin Specification C 739.3.2.3 conditioned spacea space in a resi
16、dential buildingthat is served by a heating or cooling system.3.2.4 mineral fiber loose-fill thermal insulating materialsthose materials that meet the minimum requirements specifiedin Specification C 764.3.2.5 ownerthe person, partnership, corporation, agency,or other entity who owns the residential
17、 building to beinsulated whether such ownership is by virtue of deed, con-tract, or any other instrument for acquiring legal title under thelaws of the state in which the building is located.3.2.6 residential buildinga building used for residentialoccupancy and that has a mechanical or electrical sy
18、stem forheating or for cooling, or for both.3.2.7 vapor retardera material (membrane or paint) thathas a water vapor permeance rating of 1 perm (5.7 310-8/Pasm2) or less. See Practice C 755 for more information onvapor retarders.4. Significance and Use4.1 This practice recognizes that effectiveness,
19、 safety, anddurability of insulation depend not only on the quality of theinsulating materials, but also on their proper installation.4.2 Improper installation of insulation can reduce its ther-mal effectiveness, cause fire risks and other unsafe conditions,and promote deterioration for the structur
20、e in which it isinstalled. Specific hazards that can result from improperinstallation include fires caused by (1) heat build-up in recessedlighting fixtures; (2) deterioration or failure of electrical wiringcomponents; (3) heat build-up resulting from overcurrentprotection devices incorrectly matche
21、d to wiring; or (4) dete-rioration in wood structures and paint failure due to moistureaccumulation.4.3 This practice provides general procedures that will helpensure the installation of insulation in a safe and effectivemanner. It must be noted that actual conditions in existingbuildings vary great
22、ly, and in some cases substantial additionalcare and precaution must be taken to ensure effective and safeinstallation.5. Safety Precautions5.1 All pneumatic equipment shall be operated in accor-dance with the recommended operating and safety proceduresof the equipment manufacturer and the insulatio
23、n manufac-turer.5.2 The installer shall wear proper clothing and equipmentas recommended by the insulation manufacturer. If in doubt ofthe effects of the insulation, wear protective clothing, gloves,eye and breathing protection.NOTE 1For breathing protection use a NIOSH approved N95 orhigher disposa
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC10152006STANDARDPRACTICEFORINSTALLATIONOFCELLULOSICANDMINERALFIBERLOOSEFILLTHERMALINSULATION 纤维素

链接地址:http://www.mydoc123.com/p-463058.html