ASHRAE LO-09-033-2009 Role of Safety Factors in the Design of Dedicated Outdoor-Air Systems《专用室外空气系统设计安全系数的作用》.pdf
《ASHRAE LO-09-033-2009 Role of Safety Factors in the Design of Dedicated Outdoor-Air Systems《专用室外空气系统设计安全系数的作用》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LO-09-033-2009 Role of Safety Factors in the Design of Dedicated Outdoor-Air Systems《专用室外空气系统设计安全系数的作用》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、358 2009 ASHRAEABSTRACTExcessive use of safety factors in the design of a dedicated outdoor-air system (DOAS) can result in significant over-ventilation and larger-than-necessary equipment. However, design decisions are often based on incomplete information and assumptions that may or may not be val
2、id, so safety factors are important tools for the design engineer. This paper discusses several of the common uses of safety factors in the design of a DOAS, and provides recommendations on how to design a system with “reserve capacity” to accommodate unexpected loads and the need for increased airf
3、low or dehu-midification capacity, while minimizing the impact on installed cost and energy use.INTRODUCTIONSafety factors are commonly used by engineers when designing various types of HVAC systems for use in all types of buildings. Excessive use of safety factors in the design process can result i
4、n larger-than-necessary equipment, inflated installed costs, and sometimes excessive energy use. This is especially true when safety factors are used during several steps of the design process, which “compounds” their impact along the way.However, many of the decisions made during the design process
5、 are based on incomplete information, assumptions that may turn out to be invalid, or valid assumptions that may no longer be valid one, five, or ten years after the system or equipment is installed. Therefore, safety factors are important tools for design engineers, allowing the HVAC system to be d
6、esigned with “reserve capacity” to accommodate unexpected loads and the need for increased airflow or dehumidification capacity.A dedicated outdoor-air system (DOAS) uses a separate piece of equipment to condition (filter, heat, cool, humidify, dehumidify) all of the outdoor air brought into the bui
7、lding for ventilation. This conditioned outdoor air is then delivered either directly to each occupied space or to local HVAC units serving those spaces. Meanwhile, the local units (such as fan-coils, water-source heat pumps, PTACs, small packaged units, VAV terminals, chilled ceiling panels, or chi
8、lled beams) located in or near each space provide cooling and/or heating to maintain space temperature (Coad 1999, Shank and Mumma 2001)Treating the outdoor air separately can make it easier to verify that sufficient ventilation airflow reaches each occupied space and can help avoid high indoor humi
9、dity levels. The latter is accomplished by dehumidifying the outdoor air to remove the entire ventilation latent load and most (or all) of the space latent loads, leaving the local HVAC units to primarily handle space sensible cooling loads. Some types of local HVAC equipment, such as chilled ceilin
10、g panels or chilled beams, must operate dry and avoid condensation. This limits their duty to handling sensible loads only.Figure 1 shows several example DOAS configurations. Some deliver the conditioned outdoor air (CA) directly to each zone (Mumma 2008), while other configurations deliver the air
11、to the intakes of local, single-zone units (such as fan-coils, water-source heat pumps, dual-duct VAV terminals, small packaged rooftop units, or single-zone air handlers) or to centralized, multiple-zone units (such as floor-by-floor VAV air handlers or self-contained units).In addition, there are
12、many types of dedicated outdoor-air equipment available (Figure 2). Dehumidification is usually provided by direct-expansion (DX) refrigeration, a chilled-water coil, a desiccant-based dehumidification device, or Role of Safety Factors in the Design of Dedicated Outdoor-Air SystemsJohn MurphyMember
13、ASHRAEJohn Murphy is an applications engineer with Trane Commercial Systems, La Crosse, WI. LO-09-033 2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, vol. 115, part 2. For personal use only. Additional rep
14、roduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.ASHRAE Transactions 359Figure 1 Example dedicated OA system configurations.Figure 2 Example dedicated OA equipment types.360 ASHRAE Transactionssome combination of these
15、 technologies. Often, the dedicated outdoor-air unit includes an exhaust-air energy recovery device (such as a total-energy wheel, fixed-plate heat exchanger, coil runaround loop, or heat pipe), which can reduce energy use and allow for downsizing of the cooling and heating equipment. In fact, ASHRA
16、E Standard 90.1 requires the use of an exhaust-air energy recovery device for many DOAS applications (ASHRAE 2007).SAFETY FACTORS WHEN DETERMINING DESIGN AIRFLOWThis section discusses how safety factors impact the calcu-lation of the design airflow for the dedicated outdoor-air unit.Calculating the
17、Design Airflow of the Dedicated Outdoor-Air UnitIn most applications, the design airflow for a dedicated outdoor-air unit is dictated by the amount of ventilation air required by industry standard or local code (Stanke 2004). In some cases, the owner or design team may choose to deliver more than co
18、de-minimum ventilation airflow to improve indoor air quality or to earn the “Increased Ventilation” credit when certi-fying a project using the LEED Green Building Rating System (USGBC 2009). Finally, in applications with very low ventilation requirements or very high indoor latent loads, the design
19、 engineer may chose to increase the airflow delivered by the dedicated outdoor-air unit so that the conditioned outdoor air can be deliv-ered at a higher dew point (not as dry).Table 6-1 of ASHRAE Standard 62.1-2007 (ASHRAE 2007) prescribes two ventilation rates for each occupancy cate-gory: one for
20、 people-related sources of contaminants (Rp) and another for building-related sources (Ra). Equation 6-1 from ASHRAE 62.1 is used to determine the minimum outdoor airflow (Vbz) that must be delivered to each breathing zone:(1)where= outdoor airflow required in the breathing zone of the occupiable sp
21、ace, cfm (L/s)= outdoor airflow rate required per person, cfm/person (L/sperson)= largest number of people expected to occupy the zone during typical usage= outdoor airflow rate required per unit area, cfm/ft2(L/sm2)= occupiable floor area of the zone, ft2(m2)Next, Equation 6-2 and Table 6-2 from AS
22、HRAE 62.1 are used to account for zone air distribution effectiveness (Ez), and to calculate the design outdoor airflow for the zone (Voz). This is the outdoor airflow that must be provided to the zone by the air distribution system (that is, through the supply-air diffusers).Finally, for a 100% out
23、door-air system in which one air handler supplies only outdoor air to one or more zones, Equation 6-4 from ASHRAE 62.1 is used to calculate the system-level outdoor air intake flow (Vot), by summing the zone outdoor airflows of all zones served by the dedicated outdoor-air unit:(2)In some system con
24、figurations, the dedicated outdoor-air unit provides conditioned OA to the intakes of local or centralized HVAC units, rather than directly to each zone. In these configurations, the dedicated OA unit must be sized to deliver the sum of the outdoor air intake flows (Vot) required by each of the syst
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELO090332009ROLEOFSAFETYFACTORSINTHEDESIGNOFDEDICATEDOUTDOORAIRSYSTEMS 专用 室外 空气 系统 设计 安全系数 作用 PDF

链接地址:http://www.mydoc123.com/p-455319.html