ASHRAE LO-09-032-2009 Contaminant Transport and Filtration Issues with DOAS《用DOAS垃圾运输和过滤处理问题》.pdf
《ASHRAE LO-09-032-2009 Contaminant Transport and Filtration Issues with DOAS《用DOAS垃圾运输和过滤处理问题》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LO-09-032-2009 Contaminant Transport and Filtration Issues with DOAS《用DOAS垃圾运输和过滤处理问题》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、350 2009 ASHRAEABSTRACTDedicated outdoor air systems (DOAS) are often thought to be inferior to all air systems when contaminant flushing rates from occupied spaces are considered. This is a particu-larly prevalent attitude when the parallel terminal sensible cooling equipment provides no, or minima
2、l, filtration of termi-nal air, such as the case with chilled ceilings, beams, and even fan coil units. The central thrust of this paper is to determine if the attitude concerning the perceived inferiority of DOASs contaminant flushing rate is warranted. The investigation is carried out via an analy
3、tical case study involving a multi zone facility served by either a DOAS or a Variable Air Volume (VAV) system.DOAS BRIEFLY DEFINEDA DOAS delivers 100% outdoor air (OA) to each individ-ual space in the building via its own duct system, at flow rates generally as dictated by ASHRAE Std. 62.1 or highe
4、r. Elevated design ventilation flow rates may be necessary for latent load control, building pressurization, or to garner LEED green building points. Based upon the requirements of ASHRAE Std. 90.1, most DOAS applications require the use of total energy recovery. As a general rule a DOAS operates at
5、 constant volume during all occupied hours.Consequently, for most applications, the DOAS is not capable of meeting all of the thermal loads in the space by itself, and requires a parallel system to accommodate any sensible and latent loads the DOAS cant accommodate. The DOAS is not to be confused wi
6、th what is commonly called a “100% OA system”, whose flow rate is selected to meet the entire building sensible and latent loads. In other words, a DOAS generally delivers only about 20% as much air to a space as a “100% OA system”.The thermodynamic state of the delivered air varies1, but as a minim
7、um it should condition the air to the desired space dew point temperature (DPT), thus decoupling much of the latent load from the parallel system charged with the bulk of the space sensible load control.From a contaminant transport point of view, the constant volume DOAS leads to predictable pressur
8、e differentials (including neutral if desirable) between adjoining spaces or zones, thus minimizing the potential for interzonal transfer of airborne contaminants. Also since it does not use any recircu-lated air, airborne contaminants that may be present in one zone are not immediately distributed
9、throughout a facility by the mechanical system, as is common with mixing air systems ( i . e . VAV ) . The selection of the parallel system based upon contam-inant transport is important for two main reasons: first the parallel system may or may not recirculate and filter air locally, and second the
10、 parallel system may recirculate and filter air centrally, such as an all-air VAV system. THE FACILITY AND ASSUMPTIONS FOR THE CASE STUDYConsider a 20,000 ft2(1,858 m2) facility with 10 ft (3 m) high ceilings, Figure 1, consisting of a 2 zone perimeter region; 1,000 ft2(93 m2) zone 1 and 9,000 ft2(8
11、36 m2) zone 2 respectively. The facility also has a large interior 10,000 ft2(929 m2) zone 3. For the sake of the study, the following air flow rates will be used in the analysis:Contaminant Transport and Filtration Issues with DOASStanley A. Mumma, PhD, PEFellow/Life Member ASHRAES.A. Mumma is prof
12、essor emeritus in the Department of Architectural Engineering, Penn State University, University Park, PA. LO-09-032 2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, vol. 115, part 2. For personal use only.
13、 Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.ASHRAE Transactions 351VAV system. Supply air (SA) flow rate, 16,000 cfm (7,550 l/s), of which 4,000 cfm (1,888 l/s) is OA. Perim-eter zones 1 and 2, each
14、 receives 1 cfm/ft2(5 l/s-m2) of supply air via a shut off box VAV system, Figure 2 (from here on just referred to as a VAV system). Since the SA is 25% OA, then each perimeter zone is receiving 0.25 cfm/ft2(1.3 l/s-m2) OA. Interior zone 3 receives 0.6 cfm/ft2(3 l/s-m2) of supply air via a VAV syste
15、m. That translates to 0.15 cfm/ft2(0.76 l/s-m2) OADOAS. OA flow for the facility, 4,000 cfm (1,888 l/s) uniformly distributed in each zone, Figure 3, or 0.2 cfm/ft2(1 l/s-m2).The analysis is based upon the following additional assumptions:Well mixed zones, i.e. uniform concentrations.No interzonal t
16、ransfer, i.e. neglect influence of pres-sure differentials, human activity and or infiltration/exfiltration.Contaminants stay suspended, i.e. they do not settle or plate out in the zone.VAV system is analyzed while operating in the mini-mum OA mode (4,000 cfm (1,888 l/s) OA), and at the design suppl
17、y airflow rate, i.e. 16,000 cfm (7,550 l/s). Contaminate releases during full economizer mode (resulting in very high peak space concentrations when releases occur near the OA inlet) will not be presented.The capacitance of the duct system, and its associated influence on the transient response, is
18、neglected.The governing equations for the VAV follow: and DOAS follow: Figure 1 Floor plan, zone labels, and areas. V1dC1dt- Q1CmC1()=Figure 2 Schematic for the VAV system.Figure 3 Schematic for the DOAS.V2dC2dt- Q2CmC2()=V3dC3dt- Q3CmC3()=CexhQ1C1Q2C2Q3C3+Q1Q2Q3+-=Cm1 f()QOACOAQrecCexh+Q1Q2Q3+-=Qre
19、cQ1Q2Q3+()QOA=V1dC1dt- Q1CinC1()=352 ASHRAE TransactionsWhere: = concentration of contaminant = SA flow rates =space volume= filter efficiencyCONTAMINANT INTRODUCTION NEAR THE OA INTAKEOnly contaminant sources near the OA intake are presented. Contaminant transport from internal sources2will not be
20、presented since filtration has no bearing on concentra-tions for DOAS. The contaminant source is assumed to be near the OA stream and of 5 minute duration. Filter efficiency can significantly impact the peak concentrations and transient response of the zone concentra-tions when the contaminant sourc
21、e is near the OA intake. First consider the case where the filters have no impact on contaminant removal, i.e. zero percent filter efficiency. Figure 4 illustrates such a case with the release near the OA intake. Since the VAV supply air quantity to the exterior zones 1 and 2 is higher than that of
22、the interior zone 3, their peak concen-trations are different. For the DOAS system, since the supply airflow rate is a constant 0.2 cfm/ft2(1 l/s-m2) the peak concentration in all zones and the subsequent response is uniform throughout the facility. Note: the zone transient concentrations are presen
23、ted in dimensionless form, refer-enced in all cases to the peak concentration experienced by the DOAS system with zero percent filtration efficiency. Since the VAV supply airflow rates differ between the interior and perimeter zones, their peak concentrations differ (with the higher flow/unit floor
24、area perimeter zones OA/ unit floor area exceeds that of a DOAS 20% and the interior zone OA/ unit floor area is 20% lower than DOAS). The higher VAV supply airflow rate to the zones 1 and 2 not only causes their peak concentrations to be higher than that of the interior zone 3, but also causes them
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELO090322009CONTAMINANTTRANSPORTANDFILTRATIONISSUESWITHDOAS DOAS 垃圾 运输 过滤 处理 问题 PDF

链接地址:http://www.mydoc123.com/p-455318.html