ASHRAE LO-09-015-2009 Waterside Economizing in Data Centers Design and Control Considerations《数据中心的水边经济性 设计和控制注意事项》.pdf
《ASHRAE LO-09-015-2009 Waterside Economizing in Data Centers Design and Control Considerations《数据中心的水边经济性 设计和控制注意事项》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LO-09-015-2009 Waterside Economizing in Data Centers Design and Control Considerations《数据中心的水边经济性 设计和控制注意事项》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、192 2009 ASHRAEABSTRACTFree cooling was not common in data centers in the past for a variety of reasons including the philosophy that data center cooling should be designed for maximum reliability and not for energy efficiency. Recently times have changed. Energy and sustainability are more importan
2、t to many data center owners now and sophisticated owners and designers know that free cooling can provide a good return on investment while still maintaining adequate reliability. Many data centers are being designed or retrofitted with airside economizers, waterside economizers, and even “wet bulb
3、” economizers (direct evap-orative coolers). This paper briefly compares airside and waterside economizers, then briefly compares the two types of waterside economizers (CRAC and chiller plant) and then focuses on design and control considerations for chiller plant waterside economizers serving data
4、 centers.AIR VERSUS WATERAn airside economizer will generally be more energy effi-cient than a waterside economizer, if space humidity is not required to be tightly controlled. Airside free cooling is imple-mented at each air handler and thus the amount of free cooling can be maximized at each air h
5、andler. The energy savings of a chiller plant economizer, on the other hand, can be reduced or eliminated for the entire installation by a single “rogue” zone. Furthermore, waterside economizers (WSE) require pump and tower energy and typically three steps of heat trans-fer (e.g. ambient air to cond
6、enser water, to chilled water, to supply air). Airside economizers do not require pump or tower energy or any steps of heat transfer.If humidity is required to be tightly controlled and humid-ification is provided by steam, or infrared humidifiers then the energy savings from airside economizing are
7、 significantly reduced but can still be substantial1. However, if adiabatic humidification (direct evaporation) is used then the savings can be even greater than airside economizing without humidification2. Furthermore, more and more data center managers are realizing that humidity control has littl
8、e if any impact on data center operations and therefore more and more data centers are relaxing or eliminating humidity control.On the other hand, air economizers have some concerns that waterside economizers do not share including introducing unwanted particulates, and gaseous contaminants. Lawrenc
9、e Berkeley National Labs recently measured particulate concen-trations in several data centers with and without airside econ-omizers. They found that with proper filtration particulate concentrations in data centers with airside economizers are not necessarily higher than in data centers without air
10、side econo-mizers and can easily be maintained below the most conser-vative standards3. Recent research projects by Microsoft and Intel have also showed that airside economizers do not affect data center reliability4,5. More research is needed but so far there is no research showing that airside eco
11、nomizers compro-mise data center reliability.Air side economizers will generally be more expensive than waterside economizers. Furthermore, the deal killer for airside economizers in many installations is the extra space required for outside air intake and exhaust louvers, dampers and ducts, particu
12、larly when the data center is buried at the bottom of an office building. In many cases the only option for economizing is a waterside economizer.TYPES OF WATERSIDE ECONOMIZERSThere are two basic types of waterside economizers: CRAC (computer room air conditioner) unit economizers and Waterside Econ
13、omizing in Data Centers: Design and Control ConsiderationsJeff Stein, PEMember ASHRAEJeff Stein is a principal at Taylor Engineering in Alameda, CA.LO-09-015 2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009,
14、 vol. 115, part 2. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.ASHRAE Transactions 193chiller plant economizers. A typical water-side economizer in a CRAC unit is a water-coole
15、d direct expansion CRAC unit with a water coil upstream of the DX coil. The water coil can be served by chilled water or by condenser water (making it a waterside economizer coil). The free cooling provided by the waterside economizer coil is largely offset by the added pres-sure drop of the extra c
16、oil (e.g. selections from one major CRAC manufacturer indicate that the economizer coil increases fan brake horsepower by 40%).A chiller plant economizer consists of a heat exchanger that allows condenser water to cool the chilled water directly. Such an economizer would be used in a data center whe
17、re the data floor is served by chilled water computer room air handlers (CRAHs) rather than DX CRAC units. The CRAH units would only have the pressure drop of one coil, not two. Perhaps the biggest difference, however, between a CRAC unit economizer and a chiller plant economizer is that pack-aged D
18、X CRAC units usually have constant speed fans while chilled water CRAH units can have variable speed drives (VSDs) on the supply fans. Fan energy accounts for about half of data center cooling energy and properly controlled VSD CRAH fans can dramatically reduce fan energy. The rest of this paper is
19、devoted to plant economizers.INTEGRATED VERSUS NON-INTEGRATEDA chiller plant waterside economizer can be integrated, meaning the economizer can meet all or some of the load while the chiller meets the rest of the load, or non-integrated, mean-ing the economizer can only operate when it can meet the
20、entire load. Figure 1 shows an integrated waterside econo-mizer in a primary/secondary chiller plant with two chillers. The heat exchanger is in parallel with the chillers on the condenser water side and in series with the chillers on the chilled water return side.When the outdoor air wet-bulb tempe
21、rature is low, the cooling tower fans are run at high speed to produce cold condenser water (e.g. in the 40s or 50s). This water is pumped through the heat exchanger where it cools chilled water to within a couple degrees of the tower water tempera-ture. If the economizer cannot bring the chilled wa
22、ter temper-ature down to the supply temperature setpoint then the chiller(s) pick up the remaining load and bring the water leav-ing the plant down to setpoint.The HX is located in the secondary loop on the return side just before the common leg. Locating the HX in the secondary loop, rather than th
23、e primary loop is important because it allows the heat exchanger to see the warmest possible water which maximizes the hours when the economizer can operate. The secondary loop is also better than the primary loop because it allows the primary pumps to be shut off when the economizer can handle the
24、entire load.Figure 2 shows an integrated economizer in a primary-only chiller plant. The HX is located on the load side of the common leg so that it sees the warmest return water. If it were on the plant side of the common leg then it could see a blend of return water from the loads and cold supply
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELO090152009WATERSIDEECONOMIZINGINDATACENTERSDESIGNANDCONTROLCONSIDERATIONS 数据中心 水边 经济 设计 控制 注意事项

链接地址:http://www.mydoc123.com/p-455302.html