1、 AMERICAN NATIONAL STANDARD ANSI/ISA-60079-27 (12.02.04)-2006 Fieldbus Intrinsically Safe Concept (FISCO) and Fieldbus Non-Incendive Concept (FNICO) Approved 29 January 2007 ANSI/ISA-60079-27 (12.02.04)-2006, Fieldbus intrinsically safe concept (FISCO) and Fieldbus non-incendive concept (FNICO) ISBN
2、: 978-1-55617-971-6 Copyright 2006 by IEC and ISA. All rights reserved. Printed in the United States of America. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), w
3、ithout the prior written permission of the Publisher. ISA 67 Alexander Drive P. O. Box 12277 Research Triangle Park, North Carolina 27709 USA 3 ANSI/ISA-60079-27 (12.02.04)-2006 Preface This preface, as well as all footnotes and annexes, is included for information purposes and is not part of ANSI/I
4、SA-60079-27 (12.02.04)-2006. This document has been prepared as part of the service of ISA toward a goal of uniformity in the field of instrumentation. To be of real value, this document should not be static but should be subject to periodic review. Toward this end, the Society welcomes all comments
5、 and criticisms and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549-8411; Fax (919) 549-8288; E-mail: standardsisa.org. The ISA Standards and Practices Department is aware of
6、the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. The Department is further aware of the benefits to USA users of ISA standards of incorporating suitable references to th
7、e SI (and the metric system) in their business and professional dealings with other countries. Toward this end, this Department will endeavor to introduce SI-acceptable metric units in all new and revised standards, recommended practices, and technical reports to the greatest extent possible. Standa
8、rd for Use of the International System of Units (SI): The Modern Metric System, published by the American Society for Testing b) the bus terminals shall be isolated from earth ground in accordance with ANSI/ISA-60079-11 IEC 60079-11; 15 ANSI/ISA-60079-27 (12.02.04)-2006 c) the bus terminals of separ
9、ately powered field devices shall be galvanically isolated so as to ensure that these terminals remain passive and multiple earthing grounding of the bus is avoided; d) the maximum unprotected internal capacitance Ciof each field device shall not be greater than 5 nF. No specification of the input a
10、nd internal parameters is required on the certificate, control drawing or label. 5.2 FISCO field devices The additional requirements of FISCO field devices are as follows: a) apparatus shall have minimum input parameters of Ii: 380 mA and Pi: 5,32 W; b) apparatus shall have a internal inductance Lin
11、ot greater than 10 H; c) under normal or fault conditions as specified in ANSI/ISA-60079-11 IEC 60079-11 the bus terminals shall remain passive, i.e. the terminals shall not be a source of energy to the system except for a leakage current not greater than 50 A; d) field devices shall be allocated a
12、category, be suitable for IIC apparatus group and temperature classified and constructed in accordance with ANSI/ISA-60079-11 for apparatus group IIC IEC 60079-11; e) the apparatus documentation shall state that the apparatus is suitable for use in a FISCO system in accordance with this standard. 5.
13、3 FNICO field devices The additional requirements for FNICO field devices are as follows: a) apparatus shall have an internal inductance Li not greater than 20 H; b) under normal conditions as specified in ANSI/ISA-60079-15 IEC 60079-15, the bus terminals shall remain passive, i.e. the terminals sha
14、ll not be a source of energy to the system except for a leakage current not greater than 50 A; c) field devices shall be suitable for IIC apparatus group and temperature classified and constructed in accordance with ANSI/ISA-60079-15 for apparatus group IIC and IEC 60079-15 with the protection type
15、nL nC in accordance with Clause 22 of ANSI/ISA-60079-15 at the bus terminals; NOTE: At the time that this standard was prepared, the National Electrical Codedid not recognize protection type “nL”. d) the control drawing apparatus documentation shall state that the apparatus is suitable for use in a
16、FNICO system in accordance with this standard. 6 Terminator 6.1 General The line terminators required by the system shall comprise a resistor-capacitor combination which presents at its terminals a circuit equivalent to a resistor of value 90 to 102 in series with a capacitor of 0 F to 2,2 F (includ
17、ing tolerances). NOTE 1 IEC 61158-2 requires an operational capacitance value of 0,8 F to 1,2 F. The terminator shall ANSI/ISA-60079-27 (12.02.04)-2006 - 16 - a) have minimum input parameters of Ui: 17,5 V; b) be isolated from earth ground in accordance with ANSI/ISA-60079-11 IEC 60079-11; c) have a
18、 maximum unprotected internal inductance Linot greater than 10 H. The terminators may be incorporated within field devices or power supplies. NOTE 2 For safety assessment purposes the effective capacitance of the terminator Ciis considered not to affect the intrinsic safety or incendivity of the sys
19、tem. 6.2 FISCO terminator The additional requirements are that a FISCO terminator shall a) have minimum input parameters of Ii: 380 mA and Pi: 5,32 W; b) be allocated a category, be suitable for apparatus group IIC and be temperature classified and constructed in accordance with ANSI/ISA-60079-11 IE
20、C 60079-11. The terminator control drawing documentation shall state that the terminator is suitable for use in a FISCO system in accordance with this standard. 6.3 FNICO terminator The additional requirements are that a FNICO terminator shall be suitable for apparatus group IIC and be temperature c
21、lassified and constructed in accordance with ANSI/ISA-60079-15 IEC 60079-15 nL nC apparatus. The terminator control drawing documentation shall state that the terminator is suitable for use in a FNICO system in accordance with this standard. 7 System requirements 7.1 General A system is usually of t
22、he form illustrated in Figure 1. The cable used in the system shall comply with the following parameters: loop resistance Rc15 /km to 150 /km; loop inductance Lc0,4 mH/km to 1 mH/ km; capacitance Cc45 nF/km to 200 nF/km; maximum length of each spur cable 60 m in IIC and IIB; maximum length of each t
23、runk cable, including the length of all spurs, 1 km in IIC and 5 km in IIB. When the cable, which complies with this standard, is used, no further consideration of cable parameters is necessary. The cable parameters may be determined in accordance with Annex C of IEC 60079-14. Where a system compris
24、es one source of power, 17 ANSI/ISA-60079-27 (12.02.04)-2006 any number of field devices up to 32, and two terminators, all complying with the requirements of this standard combined with a cable to the above specification, then that system shall be considered to be adequately safe. The two terminato
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIISA60079272006FIELDBUSINTRINSICALLYSAFECONCEPTFISCOANDFIELDBUSNONINCENDIVECONCEPTFNICO120204PDF

链接地址:http://www.mydoc123.com/p-436918.html