AASHTO M 273M-2011 Standard Specification for Precast Reinforced Concrete Box Sections for Culverts Storm Drains and Sewers with Less Than 0.6 m of Cover Subjected to Highway Loadi.pdf
《AASHTO M 273M-2011 Standard Specification for Precast Reinforced Concrete Box Sections for Culverts Storm Drains and Sewers with Less Than 0.6 m of Cover Subjected to Highway Loadi.pdf》由会员分享,可在线阅读,更多相关《AASHTO M 273M-2011 Standard Specification for Precast Reinforced Concrete Box Sections for Culverts Storm Drains and Sewers with Less Than 0.6 m of Cover Subjected to Highway Loadi.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、Standard Specification for Precast Reinforced Concrete Box Sections for Culverts, Storm Drains, and Sewers with Less Than 0.6 m of Cover Subjected to Highway Loadings Metric AASHTO Designation: M 273M-111ASTM Designation: C 850-98 American Association of State Highway and Transportation Officials 44
2、4 North Capitol Street N.W., Suite 249 Washington, D.C. 20001 TS-4a M 273M-1 AASHTO Standard Specification for Precast Reinforced Concrete Box Sections for Culverts, Storm Drains, and Sewers with Less Than 0.6 m of Cover Subjected to Highway Loadings Metric AASHTO Designation: M 273M-111ASTM Designa
3、tion: C 850-98 1. SCOPE 1.1. This specification covers single-cell, precast reinforced concrete box sections with less than 0.6 m of cover subjected to highway loadings and intended to be used for the construction of culverts and for the conveyance of storm water, industrial wastes, and sewage. 1.2.
4、 This metric specification is equivalent to M 273 and is compatible in technical content. Note 1This specification is primarily a manufacturing and purchasing specification. However, standard designs are included and the criteria used to develop these designs are given in Appendix X1. The successful
5、 performance of this product depends upon the proper selection of the box section, bedding, backfill, controlled manufacture in the plant, and care that the installation conforms to the construction specifications. The owner of the precast reinforced concrete box sections specified herein is caution
6、ed that the loading conditions and the field requirements must be correlated with the box sections specified and inspection must be provided at the construction site. Note 2AASHTO M 259M is to be used for box sections subjected to highway loading with 0.6 m or more earth cover, or subjected to dead
7、load only. Note 3If load-and-resistance factor design (LRFD) is required, then use ASTM C 1577. 2. REFERENCED DOCUMENTS 2.1. AASHTO Standards: M 6, Fine Aggregate for Hydraulic Cement Concrete M 31M/M 31, Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement M 32M/M 32, Steel Wire, Plain,
8、for Concrete Reinforcement M 55M/M 55, Steel Welded Wire Reinforcement, Plain, for Concrete M 80, Coarse Aggregate for Hydraulic Cement Concrete M 85, Portland Cement M 221M/M 221, Steel Welded Wire Reinforcement, Deformed, for Concrete M 225M/M 225, Steel Wire, Deformed, for Concrete Reinforcement
9、M 240, Blended Hydraulic Cement 2011 by the American Association of State Highway and Transportation Officials.All rights reserved. Duplication is a violation of applicable law.TS-4a M 273M-2 AASHTO M 259M, Precast Reinforced Concrete Box Sections for Culverts, Storm Drains, and Sewers Metric M 262,
10、 Concrete Pipe and Related Products M 295, Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete T 22, Compressive Strength of Cylindrical Concrete Specimens T 23, Making and Curing Concrete Test Specimens in the Field T 280, Concrete Pipe, Manhole Sections, or Tile Standard Specific
11、ations for Highway Bridges 2.2. ASTM Standards: C 1116/C 1116M, Standard Specification for Fiber-Reinforced Concrete C 1577, Standard Specification for Precast Reinforced Concrete Monolithic Box Sections for Culverts, Storm Drains, and Sewers Designed According to AASHTO LRFD 3. TERMINOLOGY 3.1. Def
12、initionsFor definitions of terms relating to concrete pipe, see M 262. 4. TYPES 4.1. Precast reinforced concrete box sections manufactured in accordance with this specification shall be of the types identified in Tables 1 and 2, and shall be designated by type, span, and rise. 2011 by the American A
13、ssociation of State Highway and Transportation Officials.All rights reserved. Duplication is a violation of applicable law.TS-4a M 273M-3 AASHTO Table 1Design Requirements for Precast Reinforced Concrete Box Sections with Less Than 0.6 m of Cover Subjected to HS20 LoadingaThickness, mm Circumferenti
14、al Reinforcement AreascDistribution Reinforcement AreasdBox Section S R, mmbTop Slab Bottom Slab Wall As1As2As3As4As7As8As5As6900 600 175 150 100 360 720 420 280e360e300e360e360e900 900 175 150 100 280e760 470 280e360e300e380e360e1200 600 190 150 125 440 780 420 280e380e300e380e380e1200 900 190 150
15、125 380 870 490e280e380e300e420e380e1200 1200 190 150 125 340 910 510 280e380e300e440e380e1500 900 200 175 150 470 870 470 300e400e360e400e400e1500 1200 200 175 150 400 930 510 300e400e360e440 400e1500 1500 200 175 150 340 970 550 300e400e360e470 400e1800 900 200 175 175 640 890 440 360e400e360e400e
16、400e1800 1200 200 175 175 550 970 510 360e400e360e420 400e1800 1500 200 175 175 490 1020 550 360e400e360e440 400e1800 1800 200 175 175 420 1080 610 360e400e360e470 400e2100 1200 200 200 200 680 950 510 400e400e400e400e400e2100 1500 200 200 200 610 1020 570 400e420 400e400e400e2100 1800 200 200 200 5
17、70 1080 610 400e420 400e420 400e2100 2100 200 200 200 530 1120 680 400e490 400e440 400e2400 1200 200 200 200 780 1080 570 400e400e400e400e400e2400 1500 200 200 200 720 1120 640 400e400e400e440 400e2400 1800 200 200 200 680 1190 700 400e530 400e440 400e2400 2100 200 200 200 640 1230 740 400e570 470 4
18、70 400e2400 2400 200 200 200 590 1270 800 490 610 550 470 400e2700 1500 225 225 225 720 1060 610 470e470e470e470e470e2700 1800 225 225 225 680 1120 680 470e470e470e470e470e2700 2100 225 225 225 640 1160 740 470e530 470e470e470e2700 2400 225 225 225 590 1210 800 470e570 510 470e470e2700 2700 225 225
19、225 570 1230 870 530 640 590 470e470e3000 1500 250 250 250 720 1020 610 510e510e510e510e510e3000 1800 250 250 250 680 1060 680 510e510e510e510e510e3000 2100 250 250 250 660 1100 740 510e510e510e510e510e3000 2400 250 250 250 610 1140 800 510e550 510e510e510e3000 2700 250 250 250 570 1160 850 510e590
20、550 510e510e3000 3000 250 250 250 570 1210 910 570 680 660 510e510e3300 1200 275 275 275 800 930 550e550e550e550e550e550e3300 1800 275 275 275 700 1020 680 550e550e550e550e550e3300 2400 275 275 275 610 1080 800 550e550e550e550e550e3300 3000 275 275 275 590 1140 910 550e610 610 550e550e3300 3300 275
21、275 275 590 1190 970 640 720 720 550e550e3600 1200 300 300 300 850 890 610e610e610e610e610e610e3600 1800 300 300 300 740 970 680 610e610e610e610e610e3600 2400 300 300 300 660 1040 800 610e610e610e610e610e3600 3000 300 300 300 610e1120 910 610e610e610e610e610e3600 3600 300 300 300 610e1210 1060 700 7
22、60 780 610e610eaDesign requirements are based on maximum effects resulting from cover conditions ranging from 0 to 0.6 m and the material and soil properties and loading data shown in Appendix X1. For modified or special designs, see Section 7.2. bThe box section designation, for example 900 by 600,
23、 indicates interior horizontal span, in millimeters, by interior vertical rise, in millimeters. cDesign reinforcement areas in square millimeters per linear meter of box section length at those locations as shown in Figure 1. dDesign reinforcement areas in square millimeters per linear meter of box
24、section width at those locations as shown in Figure 1. eMinimum reinforcement area is specified. Notes: 1. Reinforcement areas are based on the mass of column of earth over the width of the box section plus live loads as defined in Appendix X1. 2. Concrete design strength, 35 MPa. 2011 by the Americ
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AASHTOM273M2011STANDARDSPECIFICATIONFORPRECASTREINFORCEDCONCRETEBOXSECTIONSFORCULVERTSSTORMDRAINSANDSEWERSWITHLESSTHAN06MOFCOVERSUBJECTEDTOHIGHWAYLOADIPDF

链接地址:http://www.mydoc123.com/p-417758.html